一、WBYD2000變頻諧振耐壓試驗儀基本原理
耐(nai)壓(ya)試驗是(shi)利用電(dian)(dian)(dian)抗(kang)器(qi)的電(dian)(dian)(dian)感(gan)與被試品電(dian)(dian)(dian)容組成LC串(chuan)聯回路,調節變頻電(dian)(dian)(dian)源輸出的電(dian)(dian)(dian)壓(ya)頻率,在被試品上獲得(de)高(gao)電(dian)(dian)(dian)壓(ya),是(shi)當(dang)前高(gao)電(dian)(dian)(dian)壓(ya)試驗的一(yi)種(zhong)新方法,深(shen)受專家好評(ping),在國內外已經得(de)到廣泛的使用。
根據(ju)諧振(zhen)原理,我們知(zhi)道(dao)當電抗(kang)(kang)器L的感抗(kang)(kang)值Xl與(yu)回(hui)(hui)(hui)路(lu)中(zhong)的容抗(kang)(kang)值Xc相(xiang)等時(shi)(shi),回(hui)(hui)(hui)路(lu)達到諧振(zhen)狀態,此(ci)時(shi)(shi)回(hui)(hui)(hui)路(lu)中(zhong)僅(jin)回(hui)(hui)(hui)路(lu)電阻R消(xiao)耗有功(gong)功(gong)率(lv),而無功(gong)功(gong)率(lv)則在電抗(kang)(kang)器與(yu)試品(pin)電容之間來(lai)回(hui)(hui)(hui)振(zhen)蕩,從(cong)而在試品(pin)上(shang)產生高壓。
二、WBYD2000變頻諧振耐壓試驗儀系統構成
全套試(shi)驗系統(tong)由調頻電(dian)源主(zhu)機、電(dian)抗器(qi)、分壓(ya)器(qi)、激勵變壓(ya)器(qi)和補(bu)償電(dian)容器(qi)(可選器(qi)件)組(zu)(zu)成,接入被試(shi)品(pin)后組(zu)(zu)成一個(ge)諧(xie)振(zhen)系統(tong)進(jin)行交(jiao)流耐壓(ya)實驗。
主機: 就(jiu)是(shi)一臺幅值和頻(pin)率可調(diao)的正弦波交流調(diao)頻(pin)電(dian)源,給(gei)諧振回路提供激勵源,同時(shi)提供電(dian)壓顯(xian)示、電(dian)流顯(xian)示、計(ji)時(shi)、保護(hu)、報(bao)警(jing)等功(gong)能。
電(dian)抗(kang)器(qi)(qi):就是一個(ge)大電(dian)感(gan)線圈,與(yu)被試(shi)品(pin)(相當(dang)于(yu)電(dian)容)構成回(hui)路(lu),可配置(zhi)電(dian)抗(kang)器(qi)(qi)多節電(dian)抗(kang)器(qi)(qi),使用時(shi)通過不(bu)同的串聯(lian)、并聯(lian)組合(he)、實(shi)現不(bu)同的電(dian)感(gan)量以(yi)適用不(bu)同的試(shi)驗條件(jian)。
分(fen)壓(ya)(ya)器:內部(bu)通過電(dian)(dian)容器分(fen)壓(ya)(ya),從試品(pin)上高電(dian)(dian)壓(ya)(ya)分(fen)得低電(dian)(dian)壓(ya)(ya)供主(zhu)機測量、控制使用。
勵磁(ci)變壓(ya)器:隔離主(zhu)機電源(yuan)與諧振回路電源(yuan),并升高主(zhu)機的輸出電壓(ya)。
補償(chang)電(dian)(dian)容(rong)(rong)器:當試品電(dian)(dian)容(rong)(rong)量很小時(shi),如(ru)果要(yao)實現(xian)系統諧振可(ke)能(neng)要(yao)求的電(dian)(dian)源頻率(lv)超出試驗標(biao)準的規定(ding),可(ke)在(zai)試品上并聯一個補償(chang)電(dian)(dian)容(rong)(rong),以(yi)實現(xian)試驗要(yao)求,稱此電(dian)(dian)容(rong)(rong)器為(wei)補償(chang)電(dian)(dian)容(rong)(rong)器。
三、WBYD2000變頻諧振耐壓試驗儀主要技術性能
功率電(dian)源電(dian)壓:AC380V±10%、50Hz;
儀器(qi)電源:220V±10%、50Hz;
諧(xie)振輸(shu)出(chu)容量:200kVA;
儀器額定電壓:0~200kV;
輸出頻(pin)率范圍(wei):30~300Hz;
輸出電(dian)壓(ya)波形:正弦波,波形畸變率<0.5%;
頻率(lv)調節靈敏度:0.1Hz,不穩定度≤0.05%;
系(xi)統噪聲:≤60db;
9、系統測量(liang)精(jing)度:<1級;
10.輸出(chu)電(dian)壓不穩定:<0.5%;
11.保護響(xiang)應時間(jian):1us;
12.電感非線性度:≤0.05%;;
13.滿功率輸出下(xia),連(lian)續工作(zuo)時間為60min
14.環境溫(wen)度:-15℃~+50℃;
15.相對濕度:≤90%RH;
16.海拔高度:≤2000米(mi)。
四、WBYD2000變頻諧振耐壓試驗儀面板及部件名稱
五、WBYD2000變頻諧振耐壓試驗儀操作步驟
1、正確連線(xian),檢(jian)查無誤后(hou)方可送(song)電(dian)。
必要時工作(zuo)電源的跳過現(xian)場(chang)漏電保安器,以免不必要的跳閘。
2、打開(kai)電源開(kai)關,主(zhu)機開(kai)始工作,液晶(jing)屏顯示版權頁,該頁標(biao)明本(ben)裝(zhuang)置的軟件版本(ben)號。
觸按確認鍵,進入系(xi)統(tong)菜(cai)(cai)單,該主菜(cai)(cai)單下有(you):試(shi)(shi)(shi)驗(yan)方案(an)、開始(shi)試(shi)(shi)(shi)驗(yan)、試(shi)(shi)(shi)驗(yan)幫(bang)助、系(xi)統(tong)設置(zhi)、實(shi)用工具和試(shi)(shi)(shi)驗(yan)記錄等(deng)六個子菜(cai)(cai)單項。
3、 系(xi)統設(she)(she)置(zhi)(zhi)菜(cai)(cai)單下有電抗器電感、日(ri)期時間設(she)(she)置(zhi)(zhi)和(he)(he)采樣(yang)系(xi)數設(she)(she)置(zhi)(zhi)等三個子(zi)菜(cai)(cai)單項(xiang)。按上(shang)下鍵,上(shang)下移(yi)動(dong)光標系(xi)統參(can)數設(she)(she)置(zhi)(zhi)菜(cai)(cai)單項(xiang),觸按確定(ding)鈕后,進入系(xi)統參(can)數設(she)(she)置(zhi)(zhi)菜(cai)(cai)單,可以分別(bie)設(she)(she)定(ding)電抗器的(de)電感—H、-年-月-日(ri)、-時-分-秒(miao)和(he)(he)電壓和(he)(he)電流的(de)采樣(yang)系(xi)數也就是(shi)采樣(yang)倍率,設(she)(she)定(ding)完成后,觸按返(fan)(fan)還鍵返(fan)(fan)回上(shang)**菜(cai)(cai)單。
電抗(kang)器電感(gan)量(liang)的(de)設(she)定(ding):按確(que)定(ding)鍵(jian)(jian)選擇到(dao)此項,按左右鍵(jian)(jian)移動光(guang)標需要改變(bian)的(de)數(shu)(shu)位(wei),按上下(xia)鍵(jian)(jian)改變(bian)數(shu)(shu)值,達到(dao)所要達到(dao)的(de)數(shu)(shu)值按確(que)定(ding)鍵(jian)(jian)確(que)認。
日期時(shi)間的(de)設定(ding):按確定(ding)鍵選擇到此(ci)項,按左右鍵移動光標(biao)需要改(gai)變(bian)的(de)數位(wei),按上下鍵改(gai)變(bian)數值(zhi),按照所要設置的(de)年月(yue)日時(shi)間數值(zhi)按確定(ding)鍵確認。
采(cai)樣(yang)系(xi)數的(de)設定(ding):按(an)確定(ding)鍵選擇到高壓/電流采(cai)樣(yang)系(xi)數項(xiang),此(ci)項(xiang)為電壓或電流采(cai)樣(yang)倍率的(de)設定(ding)。一般出廠前設定(ding)好了。如需修改,要輸(shu)入密碼。(密碼廠家與設備一起提供一般設定(ding)為:188888)
警告(gao):系(xi)統默認上一次電(dian)(dian)抗器(qi)(qi)電(dian)(dian)感(gan)、日(ri)期時間和(he)采樣系(xi)數設(she)(she)(she)定值。如果(guo)需改(gai)變要重新設(she)(she)(she)定。電(dian)(dian)抗器(qi)(qi)電(dian)(dian)感(gan)量設(she)(she)(she)定值與實際使用的電(dian)(dian)抗器(qi)(qi)電(dian)(dian)感(gan)量不(bu)(bu)對,會導致試(shi)驗(yan)報告(gao)中的被試(shi)品(pin)電(dian)(dian)容量不(bu)(bu)準(zhun)。其他并不(bu)(bu)會影(ying)響。采樣系(xi)數設(she)(she)(she)置(zhi)不(bu)(bu)正確,會導致顯示電(dian)(dian)壓(ya)電(dian)(dian)流不(bu)(bu)準(zhun)將很(hen)有可能會對被試(shi)品(pin)或試(shi)驗(yan)設(she)(she)(she)備(bei)造(zao)成損(sun)壞。
4、試(shi)驗方案菜單下(xia)有預(yu)置(zhi)保護(hu)(hu)電流、找(zhao)(zhao)頻(pin)起始(shi)頻(pin)率(lv)、找(zhao)(zhao)頻(pin)結(jie)束頻(pin)率(lv)、預(yu)定(ding)起始(shi)功率(lv)四個子菜單項(xiang),分別設定(ding)本次(ci)試(shi)驗的保護(hu)(hu)電流、找(zhao)(zhao)頻(pin)起始(shi)頻(pin)率(lv)、找(zhao)(zhao)頻(pin)結(jie)束頻(pin)率(lv)、輸出起始(shi)功率(lv),全(quan)部設定(ding)完成后,觸(chu)按(an)返還鍵進入(ru)預(yu)置(zhi)試(shi)驗電壓和(he)預(yu)置(zhi)試(shi)驗時間設置(zhi)菜單。
可(ke)以分3段(duan)時(shi)間設置試驗電(dian)壓和試驗時(shi)間, 實際試驗時(shi),若設定為自(zi)動試驗, 裝置將(jiang)按設定的3段(duan)電(dian)壓及(ji)時(shi)間,按順序分別(bie)加(jia)壓, 全部(bu)完成后自(zi)動退出(chu).
如(ru)果(guo)**段(duan)(duan)電(dian)(dian)壓設為(wei)0, 或時(shi)間設為(wei)0, 那么執行完**段(duan)(duan)試驗電(dian)(dian)壓加壓后退出試驗, 只加壓**段(duan)(duan)設定的電(dian)(dian)壓.
如果(guo)第(di)三段(duan)電壓設為(wei)0, 或(huo)時(shi)間設為(wei)0, 不執(zhi)行第(di)三段(duan)加壓.
試驗方案設置的(de)(de)設定(ding)(ding):在試驗電壓項中,按(an)確定(ding)(ding)單鈕,移動左(zuo)右(you)光標到需要改變的(de)(de)數位(wei)(wei),按(an)上下單鈕以改變當前數位(wei)(wei)的(de)(de)數值大小(xiao),觸按(an)返回鈕完(wan)成當前數位(wei)(wei)的(de)(de)數值設定(ding)(ding),依次選擇下一項數值的(de)(de)設定(ding)(ding),直至分別完(wan)成試驗時間、起始頻率(lv)、起始功(gong)率(lv)的(de)(de)設置,方可(ke)完(wan)成本次試驗的(de)(de)試驗方案設置的(de)(de)設定(ding)(ding)。
出廠默認值:試(shi)驗(yan)電壓(ya) 20kV、加(jia)壓(ya)時間 2min、激勵強(qiang)度 2%、輸出電流20A、頻率范(fan)圍30-300Hz。
5、實用工具(ju)菜單下有
頻(pin)(pin)率(lv)計算:在實驗(yan)(yan)前(qian)可對諧(xie)振(zhen)頻(pin)(pin)率(lv)進(jin)行(xing)計算。只(zhi)需輸入具體參與試驗(yan)(yan)的電(dian)感、電(dian)容(rong)值并按確定(ding)鍵試驗(yan)(yan)頻(pin)(pin)率(lv)即直接生成(cheng)。
6、開始試(shi)驗(yan)菜單(dan)下(xia)有自動(dong)試(shi)驗(yan)模(mo)式(shi)和手(shou)動(dong)試(shi)驗(yan)模(mo)式(shi)兩(liang)種子菜單(dan)可供選擇。
按確認(ren)鍵(jian)進入所選(xuan)試驗步驟.
自(zi)動(dong)試(shi)驗(yan)模式的(de)操作:選(xuan)中自(zi)動(dong)試(shi)驗(yan)模式后,觸(chu)按(an)菜(cai)單鈕進(jin)入(ru)正在(zai)自(zi)動(dong)尋找(zhao)諧(xie)振(zhen)點菜(cai)單項,裝置在(zai)設定的(de)頻(pin)率(lv)(lv)范(fan)圍內自(zi)動(dong)尋找(zhao)諧(xie)振(zhen)點(如(ru)果被(bei)試(shi)品(pin)電(dian)容C和電(dian)抗器(qi)電(dian)感L的(de)實際(ji)諧(xie)振(zhen)頻(pin)率(lv)(lv)不在(zai)設定的(de)頻(pin)率(lv)(lv)范(fan)圍內,將找(zhao)不到諧(xie)振(zhen)點,此時根據(ju)需要調整頻(pin)率(lv)(lv)范(fan)圍或(huo)調整被(bei)試(shi)品(pin)回路的(de)LC參數)。當找(zhao)到諧(xie)振(zhen)點時,會有(you)聲音提示。
找到(dao)諧振點后(hou),裝(zhuang)置自(zi)動進入正在(zai)自(zi)動升壓(ya)菜(cai)單項,當升到(dao)試驗電壓(ya)設定的電壓(ya)時,裝(zhuang)置停止加壓(ya)。
當(dang)裝置(zhi)升(sheng)到試(shi)(shi)驗(yan)(yan)電(dian)壓設(she)定的電(dian)壓時(shi),設(she)備停止加(jia)壓,自動進入(ru)正(zheng)在加(jia)壓試(shi)(shi)驗(yan)(yan)菜單項,并自動記錄試(shi)(shi)驗(yan)(yan)的加(jia)壓時(shi)間,當(dang)加(jia)壓時(shi)間到達設(she)定時(shi)間時(shi),設(she)備逐(zhu)步降壓退出試(shi)(shi)驗(yan)(yan),完成本(ben)次(ci)試(shi)(shi)驗(yan)(yan),進入(ru)試(shi)(shi)驗(yan)(yan)結束(shu)菜單項。并可選擇保存(cun)試(shi)(shi)驗(yan)(yan)數(shu)據或(huo)打印試(shi)(shi)驗(yan)(yan)數(shu)據。
試(shi)驗(yan)(yan)時間的一行顯示(shi)(shi)末(mo)端,會顯示(shi)(shi)[一段]或(huo)[二段]或(huo)[三段]字樣,表示(shi)(shi)當前正(zheng)在進行的加壓(ya)試(shi)驗(yan)(yan)是預置(zhi)的一段,二段或(huo)三段.
手(shou)動試(shi)(shi)驗(yan)模式(shi)的(de)操作:選中手(shou)動試(shi)(shi)驗(yan)模式(shi)后觸按(an)確(que)定(ding)鈕(niu)(niu),進入(ru)正在試(shi)(shi)驗(yan)菜單項;手(shou)動按(an)調(diao)頻(pin)(pin)(pin)鈕(niu)(niu),對(dui)應的(de)光標(biao)隨(sui)之改變(bian)到輸出(chu)頻(pin)(pin)(pin)率(lv)項,可以通過上下(xia)左右(you)鍵改變(bian)頻(pin)(pin)(pin)率(lv)大小(xiao)使其試(shi)(shi)驗(yan)電(dian)壓(ya)(ya)(ya)逐(zhu)步(bu)(bu)升(sheng)高(gao),當升(sheng)到*高(gao)電(dian)壓(ya)(ya)(ya)時(shi),繼續向(xiang)上或向(xiang)下(xia)調(diao)整(zheng)(zheng)頻(pin)(pin)(pin)率(lv)按(an)鈕(niu)(niu),直至試(shi)(shi)驗(yan)電(dian)壓(ya)(ya)(ya)開始下(xia)降;這時(shi)反(fan)調(diao)頻(pin)(pin)(pin)率(lv),試(shi)(shi)驗(yan)電(dian)壓(ya)(ya)(ya)又逐(zhu)步(bu)(bu)回升(sheng),上下(xia)回調(diao)頻(pin)(pin)(pin)率(lv),從頻(pin)(pin)(pin)率(lv)的(de)高(gao)位到低位逐(zhu)位調(diao)整(zheng)(zheng)*高(gao)電(dian)壓(ya)(ya)(ya)值時(shi)的(de)頻(pin)(pin)(pin)率(lv)就是當前(qian)的(de)諧振頻(pin)(pin)(pin)率(lv)。
找到(dao)諧振點后,手(shou)動按電(dian)壓(ya)(ya)鈕,光標(biao)到(dao)了輸(shu)出(chu)功(gong)率,隨之(zhi)按上(shang)下鍵(jian)增(zeng)加輸(shu)出(chu)功(gong)率,試(shi)(shi)驗(yan)(yan)(yan)電(dian)壓(ya)(ya)也逐(zhu)步升高,當升到(dao)試(shi)(shi)驗(yan)(yan)(yan)電(dian)壓(ya)(ya)設(she)定電(dian)壓(ya)(ya)值時(shi)(shi),裝置停(ting)止加壓(ya)(ya),并(bing)有屏幕(mu)顯示(shi)提示(shi)和聲音提示(shi);自動進入正在加壓(ya)(ya)試(shi)(shi)驗(yan)(yan)(yan)菜(cai)(cai)單(dan)項(xiang),并(bing)自動記錄試(shi)(shi)驗(yan)(yan)(yan)的加壓(ya)(ya)時(shi)(shi)間,當到(dao)達加壓(ya)(ya)時(shi)(shi)間設(she)定時(shi)(shi)間時(shi)(shi),設(she)備逐(zhu)步降壓(ya)(ya)退出(chu)試(shi)(shi)驗(yan)(yan)(yan),完成本次試(shi)(shi)驗(yan)(yan)(yan),進入試(shi)(shi)驗(yan)(yan)(yan)結(jie)束菜(cai)(cai)單(dan)項(xiang)。
注意:在調(diao)(diao)節(jie)頻(pin)率調(diao)(diao)整(zheng)鈕的(de)過程(cheng)中,觸(chu)(chu)按(an)左(zuo)右(you)(you)鈕,可以改變頻(pin)率調(diao)(diao)節(jie)的(de)速(su)度實現(xian)粗(cu)細調(diao)(diao)的(de)切換(huan)。在調(diao)(diao)節(jie)電壓調(diao)(diao)整(zheng)鈕的(de)過程(cheng)中,向下觸(chu)(chu)按(an)左(zuo)右(you)(you)鈕,可以改變電壓的(de)升降(jiang)的(de)速(su)度實現(xian)粗(cu)細調(diao)(diao)的(de)切換(huan)。觸(chu)(chu)按(an)調(diao)(diao)頻(pin)、調(diao)(diao)壓鈕,實現(xian)調(diao)(diao)頻(pin)與(yu)調(diao)(diao)壓間的(de)切換(huan)。
7、進(jin)入(ru)試驗記錄查(cha)(cha)詢菜單項,查(cha)(cha)詢以(yi)往和當(dang)(dang)前(qian)試驗數據(ju)。選(xuan)(xuan)擇(ze)上下(xia)鍵翻看(kan)前(qian)一組數據(ju)后(hou)一組數據(ju);選(xuan)(xuan)擇(ze)左右鍵可選(xuan)(xuan)擇(ze)打印(yin)或(huo)刪除當(dang)(dang)前(qian)頁(ye)的內容。
125/456為試(shi)(shi)驗數(shu)(shu)據(ju)(ju)庫指針,分(fen)子(zi)是試(shi)(shi)驗數(shu)(shu)據(ju)(ju)的(de)在(zai)數(shu)(shu)據(ju)(ju)庫的(de)順序(xu)數(shu)(shu),分(fen)母是當前的(de)數(shu)(shu)據(ju)(ju)總數(shu)(shu),*多可(ke)儲存999組試(shi)(shi)驗數(shu)(shu)據(ju)(ju)。
8、裝置和(he)試(shi)驗狀(zhuang)態(tai)菜(cai)單提(ti)示(shi):設(she)(she)(she)備的使(shi)用和(he)升壓(ya)(ya)和(he)耐壓(ya)(ya)試(shi)驗過程中,如果出現(xian)影響試(shi)驗設(she)(she)(she)備、被試(shi)驗設(she)(she)(she)備以(yi)及(ji)操作人的**情(qing)況,設(she)(she)(she)備可能出現(xian)自(zi)動保護轉臺,并在屏幕有相應的提(ti)示(shi)。
不能(neng)諧振:如果諧振點不在諧振頻率(lv)設置的范圍內;系統連線不正確等(deng)現象,裝置將找不到諧振點,這時裝置和試驗狀(zhuang)態菜單中的不能(neng)諧振項被反(fan)白并閃爍。
輸(shu)(shu)出保護:如果裝置(zhi)(zhi)(zhi)的(de)(de)電(dian)源輸(shu)(shu)出電(dian)流大于輸(shu)(shu)出保護設定的(de)(de)電(dian)流值,裝置(zhi)(zhi)(zhi)自動(dong)保護,這時(shi)裝置(zhi)(zhi)(zhi)和試驗狀態菜單中的(de)(de)輸(shu)(shu)出保護項被反白并(bing)閃爍(shuo)。
試(shi)(shi)驗(yan)中(zhong)止:如果(guo)在試(shi)(shi)驗(yan)升壓或加壓過(guo)程(cheng)出(chu)現閃絡現象(xiang),裝置自動(dong)保護,這時裝置和(he)試(shi)(shi)驗(yan)狀態菜單(dan)中(zhong)的(de)輸出(chu)保護項被反白并閃爍。
9、試(shi)驗幫(bang)助內容包(bao)括五大項分別(bie)為:1.版本信息2.接(jie)線(xian)示意(yi)3.使用說明4.常(chang)見(jian)問(wen)題(ti)5.參(can)考資料.如常(chang)見(jian)問(wen)題(ti)FAQ分五幅畫面顯示、各種被(bei)試(shi)品電(dian)力電(dian)纜、變壓(ya)器、發電(dian)機(ji)電(dian)容參(can)數(shu)的查詢:
接線示(shi)意圖:
10、設(she)備出(chu)廠參數設(she)置(zhi)是生產廠家的出(chu)廠設(she)置(zhi)參術和(he)校(xiao)驗(yan)參數,不適當的設(she)置(zhi)和(he)修(xiu)改(gai)會(hui)影響設(she)備性能和(he)高壓(ya)試驗(yan)的**性,未經廠家授權密碼(ma),無法修(xiu)改(gai)。
警(jing)告:正(zheng)常試驗(yan)狀態下(xia),按(an)返回鍵即可中止試驗(yan)。中止或結束試驗(yan)后,應分離刀(dao)閘切斷電源。在升壓或加壓過(guo)程中,非緊(jin)急情況(kuang),不要按(an)下(xia)急停鍵。
六、本說明書的專屬名詞的定義
自(zi)動試驗:高壓試驗全過程(cheng)(cheng)由主機(ji)按程(cheng)(cheng)序和(he)預(yu)置參數(shu)自(zi)動完成(cheng)。
自(zi)動(dong)(dong)調諧(xie):調諧(xie)由主機按程序自(zi)動(dong)(dong)完成,升壓手(shou)動(dong)(dong)完成。
手動試驗(yan):尋(xun)找諧振點和升(sheng)壓(ya)均為手動,通過面板(ban)旋鈕完(wan)成。
系統參數設(she)置是指對設(she)備部(bu)件(jian)參數的設(she)置。
試(shi)驗(yan)參(can)數設置是指對試(shi)驗(yan)過程參(can)數的設置。
試驗模式選擇是指對試驗模式的(de)選擇。
試驗結果(guo)查詢是(shi)指對試驗數據的(de)查詢。
分(fen)壓(ya)器變(bian)比是指對分(fen)壓(ya)器的分(fen)壓(ya)比設置。
電抗器電感是指對電抗器電抗值(zhi)的設(she)置(zhi)。
激勵變(bian)(bian)變(bian)(bian)比(bi)是指對(dui)勵磁變(bian)(bian)壓器的變(bian)(bian)比(bi)設置。
設置電壓是(shi)高壓試驗時的保(bao)護(hu)電壓設置。
試(shi)驗電(dian)(dian)壓(ya)是高壓(ya)試(shi)驗時的試(shi)驗電(dian)(dian)壓(ya)。
加(jia)壓時(shi)間是(shi)施加(jia)試驗(yan)電壓的時(shi)間。
激勵強度是指(zhi)主機電源輸出的大小(xiao)。
輸出(chu)電(dian)(dian)流是(shi)主機電(dian)(dian)源的輸出(chu)電(dian)(dian)流。
頻(pin)率范圍是(shi)試(shi)驗(yan)的頻(pin)率范圍。
自動(dong)試(shi)驗模式是指試(shi)驗過(guo)程全部自動(dong)完成(cheng)。
自動(dong)(dong)調(diao)諧(xie)(xie)模(mo)式是指自動(dong)(dong)尋找(zhao)諧(xie)(xie)振點后,手動(dong)(dong)加壓完成試驗。
手動試驗(yan)模式(shi)全部(bu)由人工完成試驗(yan)過(guo)程。
未接地(di)線主機電源為(wei)接地(di)。
不能(neng)(neng)諧振未能(neng)(neng)找(zhao)到諧振點。
輸出保護主機(ji)電(dian)源輸出電(dian)流大于(yu)整定電(dian)流。
試驗中止指(zhi)在升壓或加壓過程裝置自動(dong)保護。
設(she)備出廠(chang)參(can)數設(she)置是廠(chang)家對設(she)備有關參(can)數的設(she)置。
確認鍵(jian):確認當前操作。
返回鍵:返回上**菜單(dan)。
七、變(bian)頻(pin)電源技術參數(shu):
1.額定輸出容量:15kvA;
2.儀器電(dian)源:220v±10% 50Hz;
功率電源:380v±10% 50Hz;
3.額定輸(shu)入(ru)電流:39.5A;
4.額定輸出(chu)(chu)電(dian)壓:0-340v可調、單相(xiang)、輸出(chu)(chu)電(dian)壓不穩定度(du)0.05%;
5.額定(ding)輸出電流:44A;
6.頻率(lv)調節范(fan)圍:25~320Hz;
7.額定容量(liang)下連續運行為(wei)規定工作(zuo)時間下*高溫(wen)升≤60K;
8.顯(xian)示(shi)以下參數:
a.經變頻輸出的頻率、電壓、電流;
b.過壓保護電壓值,并可(ke)任意整(zheng)(zheng)定(ding),當成套(tao)裝(zhuang)置的輸出電壓值達(da)到保護整(zheng)(zheng)定(ding)時,可(ke)自(zi)動(dong)切除成套(tao)裝(zhuang)置;
c.過(guo)流保(bao)護:當調頻電源的輸出電流達到保(bao)護整定值時(shi),可(ke)自動切除成套(tao)裝置;
d.擊穿(chuan)保護:當高壓側發生對(dui)地閃絡時,可(ke)自(zi)動切除成套裝置,裝置帶有隔離裝置,可(ke)確(que)保設(she)備和人(ren)身不受損害;
e.具有全電壓(ya)(ya)輸出保護,在調壓(ya)(ya)過程(cheng)中,一旦調壓(ya)(ya)失控,調頻(pin)電源立(li)即閉鎖(suo);
9.可實現以下操(cao)作(zuo):
a.頻率的調(diao)節(jie),上升和下降頻率調(diao)節(jie)分粗調(diao)和細(xi)調(diao)兩種,并(bing)可自動(dong)尋找試(shi)(shi)驗(yan)諧振點,保證諧振頻率在(zai)整個試(shi)(shi)驗(yan)過(guo)程中(zhong)不發生漂(piao)移;
b.帶有設(she)置(zhi)電壓、設(she)置(zhi)時(shi)間,電壓自動上升(sheng)到設(she)置(zhi)值而停止并自動計時(shi);
c.帶有各(ge)(ge)種(zhong)保護功能的整定按鈕,可(ke)在面板(ban)上對(dui)各(ge)(ge)種(zhong)保護值進行整定;
d.帶有手動(dong)試驗(yan)功(gong)能和自動(dong)試驗(yan)功(gong)能;
e.帶(dai)有試驗(yan)數據打印功(gong)能。
八、勵磁(ci)變壓器技術參(can)數:
1.結(jie)構(gou)形式:干式;
2.額定容量(liang):15kVA;
3.輸(shu)入電(dian)壓:0~340V;
4.輸出電壓:四(si)(si)組并聯(lian)3.75KV;四(si)(si)組串聯(lian)15KV;二(er)串二(er)并7.5KV;
5.輸(shu)出電(dian)流:四(si)組(zu)(zu)并(bing)聯4A;四(si)組(zu)(zu)串聯1A;二串二并(bing)2A;
6.工作頻率(lv)范圍:30~300Hz;
勵(li)磁變壓器的接線端(duan)子,如圖(tu)所(suo)示:
1.輸出端尾—與接地端連接。
2.輸出(chu)端頭—與電(dian)抗(kang)器連(lian)接(jie)。
3.接地端—與變頻電源、分壓器及(ji)被試品(pin)共同接地。
4.輸入端—接調頻電(dian)源功率輸出端。
九(jiu)、諧振電抗器(qi)技術參(can)數(shu):
額定(ding)容量:55KVA;
額定電壓:55kV;
額定電流:1.5A;
電 感 量:160H;
品質因(yin)數:Q≥30
采(cai)用環(huan)氧干式。
7.接線端(duan)了(le)如圖所示:
a.高壓側接線(xian)端子(zi)—與被試品高壓端連接。
b.低壓側接(jie)(jie)線端子—與勵磁變輸出(chu)端連接(jie)(jie)。
c.多臺(tai)電抗器串聯時上節(jie)的低壓側(ce)與下節(jie)高壓側(ce)連接。諧振電抗器采用多臺(tai)串聯或并聯的連接方式。
8.額定容量(liang)下連續運行為規定工(gong)作時(shi)間下,電抗器對空(kong)氣(qi)的溫升(sheng)不大于60K;
9.性能(neng)及(ji)特點(dian):電(dian)抗(kang)器(qi)(qi)設計干(gan)式、環氧澆鑄(zhu),電(dian)抗(kang)器(qi)(qi)可以(yi)自由方便疊裝。環氧樹脂(zhi)絕緣(yuan)筒外殼(ke),具有足夠的(de)電(dian)氣、機械強度,必(bi)要的(de)散熱能(neng)力(li)以(yi)及(ji)油熱脹冷縮的(de)裕(yu)度。外殼(ke)上(shang)下蓋板,顏色為橘紅色。
十、電容分壓器技術參(can)數:
額定電(dian)壓:200kV;
工作頻率(lv):30~300Hz;
分壓比:2000:1;
分壓比誤差:1%;
電容(rong)分壓器(qi)接(jie)線端子如圖所示:
高壓端(duan)—與(yu)電抗器高壓側(ce)及被試品(pin)高壓側(ce)相連。
測(ce)量插座—采(cai)用專配(pei)的測(ce)量電纜與控制(zhi)箱背板測(ce)量輸入端連接(jie)。
接地端—采(cai)用專配接地線按接線圖(tu)指示接地。
4.性能(neng)及特點:
a.額定(ding)電壓下可連續運行2小時。
b.在30~300Hz范圍(wei)內(nei),其精(jing)度和(he)穩定度保持不變(bian)。
c.在20℃溫度下電容分壓器介質損耗值≤0.0025
d.電容分壓(ya)器配有支撐(cheng)底架(jia),具(ju)有足夠的穩定性。
e.電壓(ya)測量通過(guo)專用(yong)測試引線引至調頻電源進(jin)行測量。
試驗接線圖:
110kv主變、GIS試(shi)驗接(jie)線
35kv電纜試驗(yan)接線(xian)圖(tu)
10kv電纜試驗接(jie)線(xian)圖
十二(er)、設備保(bao)存和維護
1、存放于干燥、清潔場地,防止雨(yu)水(shui)、灰塵進入(ru)部件內部;
2、如若長期(qi)不(bu)使用(yong),正(zheng)(zheng)常天氣至少(shao)2個(ge)月應通電一(yi)次時間不(bu)少(shao)于半小時,雨季及潮濕期(qi)應每(mei)隔一(yi)個(ge)月通電一(yi)次,通電時間半小時,以驅除(chu)設備內的潮氣防止電子元器(qi)件的銹蝕(shi),影響(xiang)正(zheng)(zheng)常使用(yong)。
3、定期檢查裝置各部(bu)件,確保各接(jie)頭緊固無松動;
4、更(geng)換(huan)打(da)印紙(zhi)(zhi),機器采(cai)用熱敏打(da)印紙(zhi)(zhi)并(bing)且是前換(huan)紙(zhi)(zhi)式當需要換(huan)紙(zhi)(zhi)時(shi)只要按POST鍵鈕打(da)印紙(zhi)(zhi)艙門就會(hui)打(da)開可(ke)以將新打(da)印紙(zhi)(zhi)裝入;
十三、常見故(gu)障排除
故障現象(xiang)
|
發 生(sheng) 原 因(yin)
|
排 除 方 法
|
找不到諧振(zhen)點(dian)
|
接線(xian)有(you)誤(wu)。
輸(shu)出開關未開,;
3、做GIS時PT二次回路(lu)未打開(kai);
4、試品Q值太低;
5、起始激勵功率(lv)太低;
6、試驗回路有短(duan)路現象;
7、找頻范(fan)圍(wei)不對。
|
退出(chu)試驗狀態,合上輸(shu)出(chu)開(kai)關,檢查接線;打開(kai)PT二次回路;
調高起始功(gong)率(∠30%);
用兆(zhao)歐(ou)表測量試品絕緣
重新設置找頻范圍
|
諧振后,電壓(ya)升不上去
|
1、試品Q值太低;
2、激勵電壓(ya)不夠;
3、電抗器底部有鐵磁物體;
4、3次諧波(bo)諧振。
|
檢查(cha)試品;
改變(bian)激勵變(bian)壓器繞組(zu)接法,提高(gao)勵磁(ci)電(dian)壓
絕(jue)緣筒架高電抗(kang)器或離開鐵(tie)磁(ci)物(wu)體。
|
主機自動復位(wei)
|
供(gong)電電源容量不夠;
電源引線過長或線徑過小(xiao);
接頭處(chu)接觸**;
供電(dian)電(dian)壓波動;
按鍵(jian)死(si)接觸。
|
增(zeng)加(jia)供電電源容量;
換較粗導線(xian),減小導線(xian)長度(du);
檢查接(jie)頭;
減小(xiao)供(gong)電電壓波動。
|
開機后線路跳(tiao)閘(zha)
|
線路漏電保護器較為敏感(gan);
空氣開關(guan)容量不夠(gou)。
|
跨過漏電保護(hu)器或空氣(qi)開關的接線;
改(gai)換較(jiao)大(da)容量的空(kong)氣開關。
|
電(dian)壓跌落
|
試品放電或(huo)擊穿
|
檢查試品
|
輸出短(duan)路
|
電流(liu)超過本機(ji)限流(liu)值。
|
檢查接線和試(shi)品。
|
試品電壓不準
|
分壓比(bi)設置(zhi)錯誤或分壓器信號傳(chuan)輸有問題。
|
重(zhong)設分壓比或檢查(cha)分壓器接線。
|
電壓閃變
|
試驗(yan)電壓劇烈波(bo)動,變化率超(chao)過本機限定值(zhi)。
|
檢查供(gong)電電源電壓(ya)穩(wen)定性或試(shi)品參(can)數的變化。
|
回路無(wu)電流
|
|
檢查接線和試品。
|
未(wei)接好地線(xian)
|
|
檢(jian)查接(jie)地線和地樁,按說(shuo)明(ming)書要求連接(jie)。
|
試品過電(dian)壓(ya)
|
手動升壓太(tai)快或失控。
|
改(gai)變調壓(ya)步距或(huo)改(gai)用自動升壓(ya) 。
|
系統不諧振
|
接線有誤或試品Q值太低。
|
檢(jian)查接線和試品
|
十四(si)、常用設(she)備資料(liao)參考
交聯聚乙(yi)烯電纜(lan)單位長度電容(rong)量
電(dian)纜導體截面積(ji)(平(ping)方毫(hao)米)
|
電 容 (μ/km)
|
YJV、YJLV
|
YJV、YJLV
|
YJV、YJV、YJLV
|
YJV、YJLV
|
YJV、YJLV
|
6/6kV、6/10kV
|
8.7/10kV、8.7/15kV
|
12/35kV
|
21/35kV
|
26/35kV
|
1×35
|
0.212
|
0.173
|
0.152
|
|
|
1×50
|
0.237
|
0.192
|
0.166
|
0.118
|
0.114
|
1×70
|
0.270
|
0.217
|
0.187
|
0.131
|
0.125
|
1×95
|
0.301
|
0.240
|
0.206
|
0.143
|
0.135
|
1×120
|
0.327
|
0.261
|
0.223
|
0.153
|
0.143
|
1×150
|
0.358
|
0.284
|
0.241
|
0.164
|
0.153
|
1×185
|
0.388
|
0.307
|
0.267
|
0.180
|
0.163
|
1×240
|
0.430
|
0.339
|
0.291
|
0.194
|
0.176
|
1×300
|
0.472
|
0.370
|
0.319
|
0.211
|
0.190
|
1×400
|
0.531
|
0.418
|
0.352
|
0.231
|
0.209
|
1×500
|
0.603
|
0.438
|
0.388
|
0.254
|
0.232
|
1×600
|
0.667
|
0.470
|
0.416
|
0.287
|
0.256
|
2、交(jiao)聯聚乙烯電(dian)纜單位長度(du)電(dian)容(rong)量(liang)
電纜導(dao)體(ti)截(jie)面(mian)積(平(ping)方毫(hao)米)
|
電 容(rong) (μF/km)
|
YJV、YJLV
|
YJV、YJLV
|
YJV、YJV、YJLV
|
YJV、YJLV
|
YJV、YJLV
|
6/6kV、6/10kV
|
8.7/10kV、8.7/15kV
|
12/35kV
|
21/35kV
|
26/35kV
|
3×35
|
0.212
|
0.173
|
0.152
|
|
|
3×50
|
0.237
|
0.192
|
0.166
|
0.118
|
0.114
|
3×70
|
0.270
|
0.217
|
0.187
|
0.131
|
0.125
|
3×95
|
0.301
|
0.240
|
0.206
|
0.143
|
0.135
|
3×120
|
0.327
|
0.261
|
0.223
|
0.153
|
0.143
|
3×150
|
0.358
|
0.284
|
0.241
|
0.164
|
0.153
|
3×185
|
0.388
|
0.307
|
0.267
|
0.180
|
0.163
|
3×240
|
0.430
|
0.339
|
0.291
|
0.194
|
0.176
|
3×300
|
0.472
|
0.370
|
0.319
|
0.211
|
0.190
|
3×400
|
0.531
|
0.418
|
0.352
|
0.231
|
0.209
|
3×500
|
0.603
|
0.438
|
0.388
|
0.254
|
0.232
|
3×600
|
0.667
|
0.470
|
0.416
|
0.287
|
0.256
|
3、交(jiao)聯聚乙烯電(dian)纜(lan)單位(wei)長度(du)電(dian)容量
電纜(lan)導(dao)體截面積(平(ping)方毫米)
|
電(dian) 容 (μF/km)
|
YJV、YJLV
|
YJV、YJLV
|
64/110kV
|
128/220kV
|
3×240
|
0.129
|
|
3×300
|
0.139
|
|
3×400
|
0.156
|
0.118
|
3×500
|
0.169
|
0.124
|
3×630
|
0.188
|
0.138
|
3×800
|
0.214
|
0.155
|
3×1000
|
0.231
|
0.172
|
3×1200
|
0.242
|
0.179
|
3×1400
|
0.259
|
0.190
|
3×1600
|
0.273
|
0.198
|
3×1800
|
0.284
|
0.297
|
3×2000
|
0.296
|
0.215
|
3×2200
|
|
0.221
|
3×2500
|
|
0.232
|
4、60kV級全絕緣變壓器的電容(pF)
類 型
|
變 壓(ya) 器 容 量(liang) kVA
|
630
|
2000
|
3150
|
6300
|
8000
|
1600
|
高壓-地
|
2700
|
4100
|
4600
|
5900
|
7000
|
8200
|
低(di)壓-地
|
4200
|
6600
|
7900
|
10000
|
11000
|
15300
|
對于表中沒(mei)有的產品(pin)(pin),可根據表中的上(shang)、下容(rong)量(liang)近似(si)地估算。同容(rong)量(liang)的雙繞組(zu)變壓器,其繞組(zu)電容(rong)要(yao)比三繞組(zu)產品(pin)(pin)小。
5、110kV級中性點分級絕緣變壓器的(de)電容(pF)
類 型
|
變 壓 器(qi) 容(rong) 量kVA
|
50000
|
31500
|
20000
|
10000
|
5600
|
高壓-中壓、低壓、地(di)
|
14200
|
11400
|
8700
|
6150
|
4200
|
中壓-高(gao)壓、低(di)壓、地
|
24800
|
11800
|
13200
|
9600
|
-
|
低(di)壓-高壓、中壓、地
|
19300
|
19300
|
12000
|
9400
|
6800
|
6、220kV級中性點非全(quan)級絕緣部分(fen)變壓(ya)器的電容(pF)
試 品 型 號(hao)
|
SEPSL-63000
|
SSPSL-120000
|
SSPSL-240000
|
類 型
|
高(gao)壓-中壓、低壓及(ji)地
|
12100
|
13500
|
17050
|
中壓-高壓、低壓及地
|
18500
|
19700
|
23260
|
低壓-高(gao)壓、中壓及(ji)地
|
18200
|
23600
|
29940
|
試 品 型 號
|
SFPL-240000
|
SFP-360000
|
SFPSZL-120000
|
類 型
|
高壓(ya)-中壓(ya)、低壓(ya)及地
|
32230
|
33910
|
38020
|
中壓-高(gao)壓、低壓及地
|
-
|
-
|
23260
|
低壓(ya)-高(gao)壓(ya)、中壓(ya)及地
|
22470
|
23790
|
22160
|
7、油浸式電力變壓(ya)器交流試(shi)驗電壓(ya)
額定電壓
(k V)
|
*高(gao)工(gong)作
電壓(k V)
|
線端交流試驗電壓(ya)值(kV)
|
中性點交(jiao)流試(shi)驗電壓值(kV)
|
全部(bu)更換繞組(zu)
|
部分(fen)更(geng)換(huan)繞組或(huo)交(jiao)接(jie)
|
全(quan)部(bu)更換(huan)繞組
|
部(bu)分更換繞組(zu)或交接
|
<1
|
≤1
|
3
|
2.5
|
3
|
2.5
|
3
|
3.5
|
18
|
15
|
18
|
15
|
6
|
6.9
|
25
|
21
|
25
|
21
|
10
|
11.5
|
35
|
30
|
35
|
30
|
15
|
17.5
|
45
|
38
|
45
|
38
|
20
|
23.0
|
55
|
47
|
55
|
47
|
35
|
40.5
|
85
|
72
|
85
|
72
|
110
|
126.0
|
200
|
170(195)
|
95
|
80
|
220
|
252.0
|
360
|
306
|
85
|
72
|
395
|
336
|
(200)
|
(170)
|
500
|
550.0
|
630
|
536
|
85
|
72
|
680
|
578
|
140
|
120
|
8、部分型號發電機定子繞(rao)組(zu)的(de)單(dan)相對地(di)電容量
類別(bie)
|
發 電 機
|
型號
|
生產廠家
|
額定容量(MW)
|
額定電壓(kV)
|
相(xiang)電容(mF)
|
火(huo)
力
發(fa)
電
機(ji)
|
QFS-125-2
|
上海電機(ji)廠
|
125
|
13.8
|
0.08-0.12
|
QFSN-200-2
|
哈(ha)爾濱(bin)電機廠
|
200
|
15.75
|
0.19-0.21
|
QFQS-200-2
|
東方電機廠(chang)
|
200
|
15.75
|
0.1928-0.21
|
QFQS-200-2
|
北京(jing)重(zhong)型電(dian)機廠
|
200
|
15.75
|
0.18-0.19
|
QFS-300-2
|
上海(hai)電機廠
|
300
|
18.0
|
0.16-0.20
|
QFSN-300-2
|
上海電機廠
|
300
|
18.0
|
0.18-0.20
|
ATB-2
|
美國GE公司
|
352
|
23.0
|
0.268(設(she)計(ji)值)
|
TBB-320-2
|
(前蘇(su)聯)
|
320
|
20.0
|
0.31
|
2-105×234
|
美國(guo)西屋公司
|
600
|
20.0
|
0.2(工廠試驗(yan)值)
|
50WT23E-138
|
ABB
|
600
|
22.0
|
0.253(設計值(zhi))
|
水 發
力 電
機
|
|
|
72.5 - 85
|
10.5
|
0.694
|
|
|
300
|
15.75
|
1.7-2.5
|
|
|
400
|
18.0
|
2-2.5
|
9、同步(bu)發電(dian)機定子(zi)繞(rao)組交流試(shi)驗(yan)電(dian)壓
1
|
全部更換(huan)定子繞組并修(xiu)好(hao)后的試(shi)驗電壓
|
容量kW或(huo)kVA
|
小于10000
|
10000及以上
|
額(e)定電壓Un (V)
|
36以上(shang)
|
6000以下
|
6000~18000
|
18000以上
|
試驗電壓V
|
2Un+1000但*低為1500
|
2.5Un
|
2Un
+3000
|
按專門協議
|
2
|
大修(xiu)前或局部更換定子(zi)繞組并修(xiu)好后的試(shi)驗電壓
|
運行20年及以下者
|
1.5 Un
|
運行(xing)20年以(yi)上與架(jia)空(kong)線路直接(jie)(jie)連接(jie)(jie)者
|
1.5 Un
|
運行20年以上不與架(jia)空線路直接連接者(zhe)
|
(1.3~1.5)Un
|
十五、設(she)備成(cheng)套性:
變頻電(dian)源(yuan) 1臺
勵磁變壓器(qi) 1臺
電抗(kang)器(qi) 4臺
電容(rong)分壓器(qi) 1臺
附(fu)件及測試線(xian) 1套
支架 15KV 1只
均壓罩 200KV 2只
絕緣底(di)板 2塊
一(yi)、產品概述
YDQC系(xi)列(lie)輕型(xing)交直流高(gao)(gao)(gao)壓試(shi)驗(yan)變壓器是(shi)在同類產(chan)(chan)品(pin)YDJ(G)型(xing)高(gao)(gao)(gao)壓試(shi)驗(yan)變壓器的基(ji)礎上(shang),按(an)試(shi)驗(yan)變壓器國家標準ZBK41006—89要求,經改進后生產(chan)(chan)的一種新型(xing)產(chan)(chan)品(pin),本系(xi)列(lie)產(chan)(chan)品(pin)具(ju)有(you)體積小(xiao)、重量輕、結構(gou)緊(jin)湊、功能齊全、使(shi)用(yong)方便等特點。實用(yong)于電(dian)力、工礦、科研(yan)等部門,對各種高(gao)(gao)(gao)壓電(dian)氣設備、電(dian)氣元件、絕緣材料(liao)進行(xing)工頻耐壓試(shi)驗(yan)和直流泄漏試(shi)驗(yan),是(shi)高(gao)(gao)(gao)壓試(shi)驗(yan)中必不可少的儀器。
二(er)、產品結構
YDQC系(xi)列輕型(xing)高壓(ya)試驗變壓(ya)器(qi)(qi)鐵(tie)芯(xin)(xin)為單框式。線圈(quan)采用同芯(xin)(xin)圓筒多層塔式結構,初(chu)級低壓(ya)繞(rao)組(zu)繞(rao)在鐵(tie)芯(xin)(xin)上(shang),次級高壓(ya)繞(rao)組(zu)繞(rao)在低壓(ya)繞(rao)組(zu)外側,這種同軸布置減少了(le)繞(rao)組(zu)間的(de)藕合(he)損耗(hao)。高壓(ya)硅堆(dui)用特殊工(gong)藝(yi)封(feng)裝在套管內(nei),產品的(de)外殼制成與器(qi)(qi)芯(xin)(xin)配(pei)合(he)較佳的(de)八(ba)角(jiao)形(xing)結構,整體外型(xing)美觀大方。其內(nei)外部結構見圖1。
1-均壓(ya)球(qiu);2-硅堆短路桿(gan);3-高(gao)(gao)(gao)壓(ya)套管;4-油閥;5-殼(ke)體;6、7-調整電壓(ya)輸入a、x端(duan)子(zi)(zi);8、9-儀表(biao)(biao)測(ce)量E、F端(duan)子(zi)(zi);10-高(gao)(gao)(gao)壓(ya)尾(wei)X端(duan)子(zi)(zi);11-變(bian)壓(ya)器外殼(ke)接地端(duan);12-高(gao)(gao)(gao)壓(ya)輸出A端(duan)子(zi)(zi);13-高(gao)(gao)(gao)壓(ya)整流硅堆;14-內部均壓(ya)環;15-變(bian)壓(ya)器鐵芯;16-初級低(di)壓(ya)繞組(zu);17-測(ce)量儀表(biao)(biao)繞組(zu);18-二(er)次(ci)級高(gao)(gao)(gao)壓(ya)繞組(zu);19-變(bian)壓(ya)器油。
三、工作原理
YDQC系列輕型高(gao)壓(ya)(ya)(ya)試(shi)驗(yan)變(bian)(bian)壓(ya)(ya)(ya)器(qi)為單相變(bian)(bian)壓(ya)(ya)(ya)器(qi),聯(lian)結組(zu)標號II。單臺高(gao)壓(ya)(ya)(ya)試(shi)驗(yan)變(bian)(bian)壓(ya)(ya)(ya)器(qi)的(de)工(gong)作(zuo)過(guo)程,用交流220V(10KVA以上為380V)電(dian)(dian)(dian)壓(ya)(ya)(ya)接(jie)入電(dian)(dian)(dian)源(yuan)控制箱(臺),經電(dian)(dian)(dian)源(yuan)控制箱(臺)內自藕調壓(ya)(ya)(ya)器(qi)(50KVA以上調壓(ya)(ya)(ya)器(qi)外附)調節0~200V(10KVA以上0~400V)電(dian)(dian)(dian)壓(ya)(ya)(ya)至試(shi)驗(yan)變(bian)(bian)壓(ya)(ya)(ya)器(qi)的(de)初級(ji)繞(rao)組(zu),根據電(dian)(dian)(dian)磁感(gan)應原理,在(zai)試(shi)驗(yan)變(bian)(bian)壓(ya)(ya)(ya)器(qi)高(gao)壓(ya)(ya)(ya)繞(rao)組(zu)可獲(huo)得試(shi)驗(yan)所(suo)需的(de)高(gao)電(dian)(dian)(dian)壓(ya)(ya)(ya)。其工(gong)作(zuo)原理圖見(jian)圖2所(suo)示。
1、單臺YDQC高壓試驗變壓器(qi)工(gong)作(zuo)原(yuan)理示意(yi)圖
在(zai)試驗(yan)變壓(ya)(ya)器中:a、x為低壓(ya)(ya)輸(shu)(shu)入端;A、X 為高(gao)壓(ya)(ya)輸(shu)(shu)出(chu)端;E、F為儀表測量端。
2、單臺交直流兩用型高壓試驗變壓器工作原理見圖3。圖中所示:高壓套管內裝有高壓硅堆,串接在高壓回路中作高壓整流,以獲得直流高電壓。當用一短路桿將高壓硅堆短接時,可獲得交流高電壓,其狀態為交流輸出;反之在抽出短路桿時,其狀態為直流輸出。
3、三臺高壓試驗變壓器串激獲得更高電壓原理見圖4,串激高壓試驗變壓器有很大的優越性,因為整個試驗裝置由多個單臺串激式試驗變壓器組成,單臺試驗變壓器有著體積小、重量輕、便于運輸的特點,它既可以串接成高出幾倍的單臺試驗變壓器輸出電壓組合使用,又可以分開單獨使用。整套試驗裝置投資小、經濟實惠。圖3所示:在三臺串激式試驗變壓器串激使用中,單臺試驗變壓器B1、B2、B3的輸出電壓都是U,**、二級的試驗變壓器內部都有一個激磁繞組,分別為A1、C1 和A2、C2。當控制電壓加在第**試驗變壓器B1的初級繞組a1、x1上,激磁繞組A1、C1給予試驗變壓器B2初級繞組供電,**級試驗變壓器B2的激磁繞組A2、C2給試驗變壓器B3的初級繞組供電。由于第**試驗變壓器B1的高壓尾及殼體接地,**、三級的試驗變壓器B2和B3對地有絕緣支架的隔離,這樣試驗變壓器B1、B2、B3對地輸出電壓分別為1U、2U、3U。
B1、B2、B3- 串(chuan)激式高壓變(bian)壓器;1U、2U、3U-各(ge)級(ji)對地電壓;
PV- 高(gao)壓(ya)示值表(KV); ZJ1、ZJ2-絕緣(yuan)支架。
四、使用方法及(ji)注意事(shi)項
1、YDQC高壓(ya)(ya)試(shi)驗(yan)(yan)變壓(ya)(ya)器(qi)做(zuo)工頻(pin)耐壓(ya)(ya)試(shi)驗(yan)(yan)使用接線(xian)方法見(jian)圖5。做(zuo)工頻(pin)耐壓(ya)(ya)試(shi)驗(yan)(yan)前,先(xian)根(gen)據試(shi)驗(yan)(yan)變壓(ya)(ya)器(qi)的(de)額定容(rong)量(liang)選擇(ze)好限流(liu)電(dian)(dian)阻(zu),(水電(dian)(dian)阻(zu))的(de)阻(zu)值(zhi),再根(gen)據被試(shi)品(pin)需(xu)加的(de)高壓(ya)(ya)電(dian)(dian)壓(ya)(ya)值(zhi)調整好放電(dian)(dian)球(qiu)隙的(de)球(qiu)間距,為(wei)了(le)提高對被試(shi)品(pin)施加電(dian)(dian)壓(ya)(ya)的(de)測量(liang)精度,應(ying)在高壓(ya)(ya)側接入FRC阻(zu)容(rong)分(fen)壓(ya)(ya)器(qi)來(lai)測量(liang)電(dian)(dian)壓(ya)(ya)。
R1、R2- 限流電(dian)阻; Qx- 放電(dian)球隙(xi); Zx- 被試品;
FRC- 阻容分壓器; V- 分壓器高壓表。
按照圖4、結合圖2所進行的工頻耐壓試驗接好工作線路,試驗變壓器的高壓繞阻的X端(高壓尾)、儀表測量繞組的F端、試驗變壓器的外殼以及電源控制箱(臺)的外殼必須可靠接地。
用三臺試驗變壓器串激做工頻耐壓試驗時、**、三級試驗變壓器的初級繞組X端,儀表測量繞組的F端,以及高壓繞組的X端(高壓尾)均接本級試驗變壓器的外殼,**、三級試驗變壓器的主體必須放置在絕緣支架上。除第**以外、**、三級試驗變壓器的主體不要接地線。其接線方式見圖3所示。
接電源前,電源控制箱(臺)的調壓器必須調到零位。接通電源后,綠色指示燈亮,按一下啟動按鈕,紅色指示燈亮,表示試驗變壓器已接通控制電源,開始升壓。
從零位開始按順時針方向勻速旋轉調壓器手輪升壓。(升壓方式有:快速升壓法,即20S逐級升壓法,慢速升壓法,即60S逐級升壓法,極慢速升壓法供選用)電壓從零開始按選定的升壓速度升到您所需額定試驗電壓的75%后,再以每秒2%額定試驗電壓的速度升到您所需試驗電壓,并密切注意測量儀表的指示以及被試品的情況,被試品施加電壓的時間到后。應在數秒內勻速將調壓器返回,高壓降至1/3試驗電壓以下,按一下停止按鈕,高壓、低壓輸出停止,然后切斷電源線,試驗完畢。
工頻(pin)耐壓試驗(yan)操作過程注意(yi)事項
1、試驗人員應做好責任分工,設定好試驗現場的**距離,仔細檢查好被試品及試驗變壓器的接地情況,并設有專人監護**及觀察被試品狀態工作。
2、被試品主要部位應**干凈,保持**干燥,以免損壞被試品和帶來試驗數值的誤差。
3、對大型設備的試驗,一般都應先進行試驗變壓器的空升試驗,即不接試品時升壓至試驗電壓,以便校對好儀表的指示精度,調整好放電球隙的球間距。
4、做耐壓試驗時升壓速度不能過快,并防止突然加壓,例如調壓器不在零位的突然合閘,也不能突然斷電,一般應在調壓器降至零位時分閘。
5、在升壓或耐壓試驗過程中,如發現下列不正常情況,1 電壓、電流表指針擺動很大,2 被試品發出不正常響聲,3 發現絕緣有燒焦或冒煙現象,應立即降壓,切斷電源,停止試驗并查明原因。
6、使用本產品做高壓試驗時,除熟悉本說明書外,還必須嚴格執行國家有關標準和操作規程。
2、YDQ交直流(liu)(liu)(liu)(liu)兩(liang)用(yong)高(gao)壓(ya)試(shi)(shi)(shi)驗(yan)變壓(ya)器(qi)做(zuo)直流(liu)(liu)(liu)(liu)耐(nai)壓(ya)和(he)泄(xie)(xie)漏(lou)試(shi)(shi)(shi)驗(yan)使用(yong)接線方法見圖(tu)5。由于是交直流(liu)(liu)(liu)(liu)兩(liang)用(yong)高(gao)壓(ya)試(shi)(shi)(shi)驗(yan)變壓(ya)器(qi),應把高(gao)壓(ya)硅(gui)堆(dui)短(duan)路(lu)桿(gan)從(cong)套管中抽(chou)出,使試(shi)(shi)(shi)驗(yan)變壓(ya)器(qi)為直流(liu)(liu)(liu)(liu)輸出狀(zhuang)態。做(zuo)直流(liu)(liu)(liu)(liu)泄(xie)(xie)漏(lou)試(shi)(shi)(shi)驗(yan)前(qian),先(xian)根據泄(xie)(xie)漏(lou)試(shi)(shi)(shi)驗(yan)中輸出端斷路(lu)電(dian)(dian)(dian)流(liu)(liu)(liu)(liu)不(bu)超(chao)過(guo)高(gao)壓(ya)硅(gui)堆(dui)的*大整流(liu)(liu)(liu)(liu)為宜(yi),選擇好限流(liu)(liu)(liu)(liu)電(dian)(dian)(dian)阻(zu)(zu)(水電(dian)(dian)(dian)阻(zu)(zu))的阻(zu)(zu)值,再(zai)根據被試(shi)(shi)(shi)品對直流(liu)(liu)(liu)(liu)高(gao)壓(ya)波形的要求(qiu)選擇好高(gao)壓(ya)濾波電(dian)(dian)(dian)容(rong)的電(dian)(dian)(dian)容(rong)值。為了提高(gao)對被試(shi)(shi)(shi)品施加電(dian)(dian)(dian)壓(ya)的測(ce)量(liang)精度,應在高(gao)壓(ya)側接入FRC阻(zu)(zu)容(rong)分壓(ya)器(qi)來(lai)測(ce)量(liang)電(dian)(dian)(dian)壓(ya)。
R- 限流電(dian)阻; C- 高壓濾波電(dian)容; Zx- 被試品; G- 硅堆短路桿;
FRC- 阻容分壓器;V- 分壓器高壓表;uA- 微安表;D- 高壓整流硅堆。
按照圖5、結合圖3所進行的直流泄漏試驗接好工作線路。試驗變壓器的高壓繞組的X端(高壓尾)、儀表測量繞組的F 端、試驗變壓器的外殼以及電源控制箱(臺)的外殼必須可靠接地。
接電(dian)源(yuan)(yuan)(yuan)前、電(dian)源(yuan)(yuan)(yuan)控制箱(臺)的調(diao)壓器必(bi)須調(diao)到零(ling)位。接通電(dian)源(yuan)(yuan)(yuan)后,綠色(se)指(zhi)示燈(deng)亮,按(an)一下啟動按(an)鈕,紅(hong)色(se)指(zhi)示燈(deng)亮,表示試驗(yan)變壓器已接通控制電(dian)源(yuan)(yuan)(yuan),開(kai)始升壓。
從(cong)零位開(kai)始(shi)按(an)(an)順時針方(fang)向勻速(su)旋(xuan)轉調壓(ya)(ya)(ya)(ya)器手輪(lun)升(sheng)(sheng)壓(ya)(ya)(ya)(ya)。(升(sheng)(sheng)壓(ya)(ya)(ya)(ya)方(fang)式有:快速(su)升(sheng)(sheng)壓(ya)(ya)(ya)(ya)法(fa)即(ji)20S逐(zhu)級升(sheng)(sheng)壓(ya)(ya)(ya)(ya)法(fa);慢速(su)升(sheng)(sheng)壓(ya)(ya)(ya)(ya)法(fa),即(ji)60S逐(zhu)級升(sheng)(sheng)壓(ya)(ya)(ya)(ya)法(fa);級慢速(su)升(sheng)(sheng)壓(ya)(ya)(ya)(ya)法(fa)供(gong)選用(yong))電壓(ya)(ya)(ya)(ya)從(cong)零開(kai)始(shi)按(an)(an)選定(ding)的(de)升(sheng)(sheng)壓(ya)(ya)(ya)(ya)速(su)度升(sheng)(sheng)到(dao)您所需額定(ding)試(shi)驗電壓(ya)(ya)(ya)(ya)或額定(ding)直流(liu)電流(liu)下的(de)參考電壓(ya)(ya)(ya)(ya)。試(shi)驗中應(ying)(ying)嚴密注意(yi)直流(liu)高壓(ya)(ya)(ya)(ya)表、泄漏(lou)電流(liu)表指示(shi)以及(ji)被(bei)試(shi)品的(de)情況。試(shi)驗完(wan)畢后(hou)(hou),應(ying)(ying)訊速(su)均勻將高壓(ya)(ya)(ya)(ya)降至(zhi)零位,按(an)(an)一下停止按(an)(an)鈕,高壓(ya)(ya)(ya)(ya)、低壓(ya)(ya)(ya)(ya)輸出停止,然后(hou)(hou)切斷電源。此時應(ying)(ying)用(yong)直流(liu)高壓(ya)(ya)(ya)(ya)放(fang)**給被(bei)試(shi)品及(ji)試(shi)驗裝置本身充分放(fang)電。
直流泄漏試驗操(cao)作過程注意(yi)事項
(1)試驗人員應做好責任分工,設定好試驗現場的**距離,仔細檢查好被試品及試驗變壓器的接地情況,并設有專人監護**及觀察被試品狀態工作。
(2)被試品做試驗前,應拆除所有對外連線,并充分放電,主要部位應**干凈,保持**干燥,以免損壞被試品及帶來試驗數值的誤差。
(3)對于大容量試品(電容器、超長電纜等)試驗時應緩慢升壓,防止被試品的充電電流過大而燒壞微安表,必要時應分級加壓分別讀取各電壓下微安表的穩定讀數。
(4)試驗過程中,應嚴密監視被試品、微安表及試驗裝置等,一旦發生閃爍、擊穿等現象應立即降壓,切斷電源,并查明原因。
五(wu)、配(pei)套選購產(chan)品(pin)
下列產品僅供選擇,購買時需另行計價。
1.KZX系列電源控制箱 容量:1KVA-5KVA、輸入電壓:220V
2.KZT系列電源控制臺 容量:10KVA~300KVA輸入電壓:220V或380V
3.數字微安表:SWB-II
4.高壓濾波電容: 0.01MF、40 ~ 100KV
5.高壓直流放**: FBR— 70、140、210KV
6.放電球隙: Q—50、100、150、200、250、500
7.標準試油杯: 400ml
8.折疊式手推車: 150、300型
9.絕緣支架: 50、100、200、300、400KV
10.阻容分壓器: FRC —50、100、150、200KV
11.高壓硅堆: 2DL—150、300、450KV
12.水 電 阻: 50、100
六、主(zhu)要試(shi)驗設備的選擇
1、試驗變壓器
其高壓側額定電壓應不小于被試品的*高試驗電壓,額定電流不小于被試品的*大電容電流。被試品的電容電流和試驗變壓器所需容量計算式為:
被試品(pin)電(dian)容量(liang)Cx可由交流電(dian)橋測出。常用的被試品(pin)電(dian)容量(liang)按表1選取。
幾種常用被試品的電容量(pF) 表1
2、調壓(ya)設備
(1)自藕調壓器。其調壓范圍廣、功率損耗小、波形畸變小、選擇這種調壓方式為*好。自藕調壓器的容量按0.75 ~ 1倍的試驗變壓器的容量選擇,適用于容量為100KVA以下的試驗變壓器的調壓。
(2)感應調壓器。其調壓范圍大,波形畸形小、但結構復雜、價格較貴,當試驗變壓器的容量較大時(如100KVA以上)使用。
3、限流電阻
限流電阻的作用是,當被試品擊穿時,限制斷路電流,從而保護試驗變壓器,防止故障的擴大。其數值以*高試驗電壓為準,按0.5 ~ 1 Ω / V(有效值)選擇,限流電阻可用水電阻。注意水不能充滿玻璃管,應留有余地,以防爆裂。
4、放電球隙
放電球隙的布置方式有垂直和水平兩種,球隙間距S和球的直徑D的關系應保護在0.05D ≤S ≤0.5D范圍內,球隙上的水電阻阻值一般按0.1 ~ 1Ω/V選取,設置放電球隙的目的是為了對重要的被試品起保護作用,可以將由于誤操作或被試品擊穿引起的過電壓限制在允許的范圍內。
七、試驗變壓器技術指示(shi)
型號
|
容(rong)量(liang)
|
高壓(ya)電壓(ya)
|
高壓電流
|
低壓(ya)輸入
|
變(bian)比
|
溫(wen)升℃
|
(KVA)
|
(KV)
|
(mA)
|
電壓(ya)(V)
|
電流(liu)(A)
|
高(gao)/儀(yi)
|
30分鐘
|
YDQC-1.5/50
|
1.5
|
50
|
30
|
200
|
7.5
|
500
|
10
|
YDQC-3/50
|
3
|
50
|
60
|
200
|
15
|
500
|
10
|
YDQC-5/50
|
5
|
50
|
100
|
200
|
25
|
500
|
10
|
YDQC-10/50
|
10
|
50
|
200
|
200
|
50
|
500
|
10
|
YDQC-15/50
|
15
|
50
|
300
|
200
|
75
|
500
|
10
|
YDQC-20/50
|
20
|
50
|
400
|
380
|
53
|
500
|
10
|
YDQC-30/50
|
30
|
50
|
600
|
380
|
79
|
500
|
10
|
YDQC-50/50
|
50
|
50
|
1000
|
380
|
12
|
500
|
10
|
YDQC-5/100
|
5
|
100
|
50
|
200
|
25
|
1000
|
10
|
YDQC-10/100
|
10
|
100
|
100
|
200
|
50
|
1000
|
10
|
YDQC-20/100
|
20
|
100
|
200
|
400
|
50
|
1000
|
10
|
YDQC-30/100
|
30
|
100
|
300
|
400
|
75
|
1000
|
10
|
YDQC-50/100
|
50
|
100
|
500
|
400
|
125
|
1000
|
10
|
YDQC-20/150
|
20
|
150
|
133
|
400
|
50
|
1500
|
10
|
YDQC-30/150
|
30
|
150
|
200
|
400
|
75
|
1500
|
10
|
YDQC-50/150
|
50
|
150
|
333
|
400
|
125
|
1500
|
10
|
YDQC-100/150
|
100
|
150
|
667
|
400
|
250
|
1500
|
10
|
YDQC-50/200
|
50
|
200
|
250
|
400
|
125
|
2000
|
10
|
YDQC-100/200
|
100
|
200
|
500
|
400
|
250
|
2000
|
10
|
YDQC-150/200
|
150
|
200
|
750
|
400
|
375
|
2000
|
10
|
YDQC-200/200
|
200
|
200
|
1000
|
400
|
500
|
2000
|
10
|
YDQC-300/200
|
300
|
200
|
1500
|
400
|
600
|
2000
|
10
|
YDQC-50/300
|
50
|
300
|
170
|
400
|
125
|
3000
|
10
|
YDQC-100/300
|
100
|
300
|
333
|
400
|
250
|
3000
|
10
|
YDQC-150/300
|
150
|
300
|
500
|
400
|
375
|
3000
|
10
|
YDQC-200/300
|
200
|
300
|
667
|
400
|
500
|
3000
|
10
|
YDQC-300/300
|
300
|
300
|
3000
|
500
|
600
|
3000
|
10
|
1、使用環境條件
環境溫度不高于+40℃、不低于—20℃;空氣相對濕度不大于90%;海拔高度不超過2000米;
2、工作電壓
電源控制箱(臺)輸入電壓為工頻220V或380V、相對誤差不超過±10%;(具體使用電壓根據用戶所定試驗變壓器規格選取)
八、隨貨文件
YDQC 系列試驗變壓器產品說明書 1份
產品出廠試驗報告 1份
產品合格證 1份
裝箱單 1份
一、概(gai)述
YDQ系(xi)列高壓(ya)(ya)(ya)(ya)試(shi)驗變壓(ya)(ya)(ya)(ya)器(qi)是根據《試(shi)驗變壓(ya)(ya)(ya)(ya)器(qi)》標(biao)準,在油浸式試(shi)驗變壓(ya)(ya)(ya)(ya)器(qi)的(de)(de)(de)基礎上而設計(ji)生產(chan)的(de)(de)(de)。SF6氣(qi)體(ti)具有良(liang)好的(de)(de)(de)電氣(qi)絕(jue)緣(yuan)(yuan)(yuan)性(xing)能(neng)(neng)及優(you)異的(de)(de)(de)滅弧(hu)性(xing)能(neng)(neng),其耐壓(ya)(ya)(ya)(ya)強度為同一壓(ya)(ya)(ya)(ya)力(li)下(xia)氮氣(qi)的(de)(de)(de)2.5倍,擊(ji)穿電壓(ya)(ya)(ya)(ya)的(de)(de)(de)空氣(qi)的(de)(de)(de)2.5倍。在0.25MPa下(xia)與油的(de)(de)(de)擊(ji)穿電壓(ya)(ya)(ya)(ya)相等(deng),在0.45MPa壓(ya)(ya)(ya)(ya)力(li)下(xia)是油的(de)(de)(de)擊(ji)穿電壓(ya)(ya)(ya)(ya)的(de)(de)(de)2倍,是一種(zhong)優(you)于油的(de)(de)(de)新一代超(chao)高壓(ya)(ya)(ya)(ya)絕(jue)緣(yuan)(yuan)(yuan)介質材料。該產(chan)品技術要求(qiu)完全符(fu)合《ZBK-41006-89》標(biao)準,它是油浸式輕型試(shi)驗變壓(ya)(ya)(ya)(ya)器(qi)的(de)(de)(de)換代產(chan)品。該產(chan)品具有體(ti)積小(xiao)、重(zhong)量輕、不受氣(qi)候(hou)變化影響、電暈(yun)小(xiao)、現場搬(ban)運無需靜止可(ke)使(shi)用,使(shi)用壽(shou)命長、免維修等(deng)特點。適(shi)用于電力(li)系(xi)統、工礦企業、科(ke)研部門等(deng)對各種(zhong)高壓(ya)(ya)(ya)(ya)電氣(qi)設備、電氣(qi)元件、絕(jue)緣(yuan)(yuan)(yuan)材料進行工頻或直流(liu)高壓(ya)(ya)(ya)(ya)下(xia)的(de)(de)(de)絕(jue)緣(yuan)(yuan)(yuan)強度試(shi)驗。
二、產品結構(gou)
YDQ系列高(gao)壓試驗變(bian)壓器采用(yong)單框(kuang)芯式鐵芯結構(gou),初(chu)級繞(rao)組(zu)繞(rao)在鐵芯上(shang),高(gao)壓繞(rao)組(zu)在外,這種同軸(zhou)布置減(jian)少了漏(lou)磁通(tong),因而增大了繞(rao)組(zu)間的耦合(he)。產品的外殼為圓(yuan)柱灌式容器結構(gou),能耐受0.8MPa以上(shang)壓力。其(qi)結構(gou)見圖1:
三、工作原理
YDQ系列(lie)高(gao)壓(ya)(ya)(ya)試(shi)驗(yan)變壓(ya)(ya)(ya)器(qi)(qi)為(wei)(wei)單相變壓(ya)(ya)(ya)器(qi)(qi),聯結(jie)組標號Ⅰ.Ⅰ. 用工頻220V(10kVA以上為(wei)(wei)380V)電源(yuan)接入 (為(wei)(wei)本(ben)公司生產的試(shi)驗(yan)變壓(ya)(ya)(ya)器(qi)(qi)配(pei)套專用設(she)備,詳細資料請見其具(ju)體使用說明書)系列(lie)操(cao)作(zuo)箱(臺),經操(cao)作(zuo)箱內自偶調壓(ya)(ya)(ya)器(qi)(qi)(50kVA以上調壓(ya)(ya)(ya)器(qi)(qi)外附)調節(jie)至0~200V(或0~400V)電壓(ya)(ya)(ya)輸出至YDQ試(shi)驗(yan)變壓(ya)(ya)(ya)器(qi)(qi)的初級繞組,根據(ju)電磁感應原理,在試(shi)驗(yan)變壓(ya)(ya)(ya)器(qi)(qi)高(gao)壓(ya)(ya)(ya)繞組可獲得試(shi)驗(yan)所需(xu)的高(gao)電壓(ya)(ya)(ya)。
單臺YDQ系列交(jiao)直(zhi)流高壓(ya)(ya)試(shi)驗變壓(ya)(ya)器的(de)工作(zuo)(zuo)原理圖見(jian)圖3,圖中(zhong)高壓(ya)(ya)套管中(zhong)裝有高壓(ya)(ya)硅堆,串接(jie)在高壓(ya)(ya)回路中(zhong)作(zuo)(zuo)半波整流,以(yi)獲得直(zhi)流高電壓(ya)(ya)。當用一短(duan)路桿將高壓(ya)(ya)硅堆短(duan)接(jie)時,可獲得工頻高電壓(ya)(ya),作(zuo)(zuo)為(wei)交(jiao)流輸出狀態(tai);取消短(duan)路桿時,作(zuo)(zuo)為(wei)直(zhi)流輸出狀態(tai)。
圖中:D—短路桿(gan) VD—高壓硅堆
試驗變壓(ya)器高壓(ya)套(tao)管(guan)中的高壓(ya)硅堆未畫出,其(qi)原(yuan)理與(yu)上(shang)圖(tu)相同。
三(san)臺(tai)(tai)(tai)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)串(chuan)級(ji)(ji)獲得更高(gao)(gao)電(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)的(de)(de)接(jie)線原(yuan)理見圖4。串(chuan)級(ji)(ji)高(gao)(gao)壓(ya)(ya)(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)有很大的(de)(de)優越(yue)性,因為(wei)整個(ge)試(shi)(shi)驗(yan)(yan)(yan)裝(zhuang)置由(you)幾(ji)(ji)(ji)臺(tai)(tai)(tai)單臺(tai)(tai)(tai)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)組(zu)成(cheng)(cheng),單臺(tai)(tai)(tai)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)容量小、電(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)低、重(zhong)量輕,便于運輸和(he)安裝(zhuang)。它既(ji)然可串(chuan)接(jie)成(cheng)(cheng)高(gao)(gao)出(chu)(chu)幾(ji)(ji)(ji)倍的(de)(de)單臺(tai)(tai)(tai)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)輸出(chu)(chu)電(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)組(zu)合(he)使(shi)用(yong),又可分開成(cheng)(cheng)幾(ji)(ji)(ji)套單臺(tai)(tai)(tai)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)單獨使(shi)用(yong)。整套裝(zhuang)置投資(zi)小,經濟實惠。圖5中(zhong),在第**和(he)**級(ji)(ji)的(de)(de)每個(ge)單元(yuan)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)中(zhong)都有一(yi)個(ge)勵(li)磁繞組(zu)A1、C1和(he)A2、C2。在三(san)臺(tai)(tai)(tai)串(chuan)級(ji)(ji)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)基(ji)本(ben)原(yuan)理中(zhong),低壓(ya)(ya)(ya)(ya)(ya)(ya)電(dian)源加在試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)Ⅰ的(de)(de)初(chu)級(ji)(ji)繞組(zu)a1x1上,單臺(tai)(tai)(tai)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)Ⅰ、Ⅱ、Ⅲ的(de)(de)輸出(chu)(chu)電(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)都是V。勵(li)磁繞組(zu)A1、C1給**級(ji)(ji)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)Ⅱ的(de)(de)初(chu)級(ji)(ji)繞組(zu)供電(dian);**級(ji)(ji)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)Ⅱ的(de)(de)勵(li)磁繞組(zu)A2、C2給第三(san)級(ji)(ji)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)Ⅲ的(de)(de)初(chu)級(ji)(ji)繞組(zu)供電(dian)。**級(ji)(ji)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)Ⅱ和(he)第三(san)級(ji)(ji)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)Ⅲ的(de)(de)箱(xiang)體分別處在對地(di)為(wei)1V和(he)2V的(de)(de)高(gao)(gao)電(dian)位上,所以箱(xiang)體對地(di)是絕緣(yuan)的(de)(de),試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)Ⅰ的(de)(de)箱(xiang)體是接(jie)地(di)的(de)(de)。這(zhe)樣第**、**級(ji)(ji)、第三(san)級(ji)(ji)試(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)對地(di)的(de)(de)額(e)定輸出(chu)(chu)電(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)分別為(wei)1V、2V、3V;其額(e)定容量分別為(wei)3P、2P、1P。
YDQ系列高壓(ya)(ya)試(shi)驗變壓(ya)(ya)器做被試(shi)品(pin)的(de)工頻耐(nai)壓(ya)(ya)試(shi)驗使用接線原(yuan)理(li)圖見圖5。
圖中(zhong):R1—限流電阻 FRC—阻容分(fen)壓器 RF—球間(jian)隙(xi)保護電阻 G—球間(jian)隙(xi) CX—被試(shi)品
注:高壓(ya)尾必須(xu)可靠接地(di)
工(gong)頻耐壓(ya)(ya)試驗(yan)(yan)(yan)中限(xian)流(liu)電(dian)(dian)阻(zu)R1應根據試驗(yan)(yan)(yan)變壓(ya)(ya)器(qi)的(de)額定容量來選(xuan)擇(ze)。如高(gao)壓(ya)(ya)側額定輸出(chu)電(dian)(dian)流(liu)在100~300mA時(shi),可取0.5~1Ω/V(試驗(yan)(yan)(yan)電(dian)(dian)壓(ya)(ya));高(gao)壓(ya)(ya)側額定輸出(chu)電(dian)(dian)流(liu)為(wei)1A以(yi)上時(shi),可取1Ω/V(試驗(yan)(yan)(yan)電(dian)(dian)壓(ya)(ya))。常用水(shui)電(dian)(dian)阻(zu)作為(wei)限(xian)流(liu)電(dian)(dian)阻(zu),管子長度可按150kV/m考慮,管子粗細(xi)應具有足夠的(de)熱容量(水(shui)阻(zu)液配(pei)制(zhi)方法:用蒸餾水(shui)加入適量硫酸銅配(pei)制(zhi)成(cheng)各種不同(tong)的(de)阻(zu)值)。
球(qiu)間(jian)隙及保護(hu)電(dian)(dian)(dian)阻:當電(dian)(dian)(dian)壓超過球(qiu)間(jian)隙整定值時(一般取試驗電(dian)(dian)(dian)壓的110%~120%),球(qiu)間(jian)隙放電(dian)(dian)(dian),對被試品(pin)起到(dao)保護(hu)作(zuo)用。球(qiu)間(jian)隙保護(hu)電(dian)(dian)(dian)阻可按1Ω/V(試驗電(dian)(dian)(dian)壓)選取。
在工(gong)頻耐壓(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)中,低(di)電(dian)壓(ya)(ya)(ya)(ya)側(ce)測(ce)量電(dian)壓(ya)(ya)(ya)(ya)(儀表電(dian)壓(ya)(ya)(ya)(ya))不是非常準確的,其(qi)原因是由于(yu)(yu)試(shi)(shi)驗(yan)變壓(ya)(ya)(ya)(ya)器存在著漏抗(kang),在這個(ge)漏抗(kang)上(shang)(shang)必然(ran)存在著壓(ya)(ya)(ya)(ya)降(jiang)或容(rong)(rong)升(sheng),使試(shi)(shi)品上(shang)(shang)的電(dian)壓(ya)(ya)(ya)(ya)低(di)于(yu)(yu)或高(gao)于(yu)(yu)低(di)壓(ya)(ya)(ya)(ya)側(ce)測(ce)量電(dian)壓(ya)(ya)(ya)(ya)表上(shang)(shang)反映出來的電(dian)壓(ya)(ya)(ya)(ya)。工(gong)頻耐壓(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)時(shi),被試(shi)(shi)品上(shang)(shang)的電(dian)壓(ya)(ya)(ya)(ya)高(gao)于(yu)(yu)試(shi)(shi)驗(yan)變壓(ya)(ya)(ya)(ya)器的輸出電(dian)壓(ya)(ya)(ya)(ya),也就(jiu)是所謂容(rong)(rong)升(sheng)現象。感應耐壓(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)時(shi),試(shi)(shi)驗(yan)變壓(ya)(ya)(ya)(ya)器的漏抗(kang)必然(ran)存在著壓(ya)(ya)(ya)(ya)降(jiang)。為了準確測(ce)量被試(shi)(shi)品上(shang)(shang)所施(shi)加的電(dian)壓(ya)(ya)(ya)(ya),因此常在高(gao)壓(ya)(ya)(ya)(ya)側(ce)接入FRC阻容(rong)(rong)分壓(ya)(ya)(ya)(ya)器來測(ce)量電(dian)壓(ya)(ya)(ya)(ya)(見(jian)圖5)。
工頻耐壓試驗(yan)操作注意事項(xiang)
1)試驗人(ren)(ren)員應做(zuo)好分工,明確相互間聯(lian)系(xi)方法。并有專門人(ren)(ren)監護現場(chang)**及(ji)觀(guan)察(cha)試品狀態。
2)被試(shi)品應先清掃干凈,并**干燥,以免損壞被試(shi)品和試(shi)驗(yan)帶來的誤差(cha)。
3)對于大型試(shi)(shi)驗(yan),一般都應先進行空升(sheng)試(shi)(shi)驗(yan)。即不接試(shi)(shi)品時升(sheng)壓至(zhi)試(shi)(shi)驗(yan)電壓,校對各種(zhong)表計,調整球間隙(xi)。
4)升壓速度不能(neng)(neng)太快,并必(bi)須防止突(tu)然(ran)加壓。例如調(diao)壓器不在(zai)(zai)零位時突(tu)然(ran)合(he)閘。也不能(neng)(neng)突(tu)然(ran)切斷(duan)電(dian)源(yuan),一般應在(zai)(zai)調(diao)壓器降(jiang)至零位時拉(la)閘。
5)當電壓升至試驗(yan)電壓時(shi),開始計(ji)時(shi),到1min后(hou),迅速降壓到1/3試驗(yan)電壓以下時(shi),才能拉(la)開電源。
6)在(zai)升壓(ya)或耐(nai)壓(ya)試驗過程中,如發現(xian)下列不(bu)正常(chang)情況(kuang)時(shi),應立即(ji)降壓(ya),切(qie)斷(duan)電(dian)源(yuan)。停止試驗并(bing)查(cha)明原(yuan)因:①電(dian)壓(ya)表指針(zhen)擺動很大;②發現(xian)絕緣燒焦或冒煙;③被試品內(nei)有不(bu)正常(chang)的聲音(yin)。
7)耐壓試驗(yan)前后應測量絕緣電阻,檢查絕緣情況。
試(shi)驗(yan)變壓(ya)器在(zai)做被試(shi)品的(de)直流耐壓(ya)或泄露試(shi)驗(yan)時接(jie)線原理圖(tu)如圖(tu)6。
注:此試驗應先抽出(chu)短(duan)路桿“D”,圖6中所示。
圖(tu)中:VD—高(gao)壓硅(gui)堆 R1—限(xian)流(liu)電(dian)阻(zu) C1—高(gao)壓濾波電(dian)容 FRC—阻(zu)容分壓器 CX—被試品 μA—帶保護微安表
泄露試驗(yan)中限流(liu)電(dian)阻R1選(xuan)擇在額(e)定輸出電(dian)壓時(shi),輸出端短路電(dian)流(liu)不超過高壓硅堆(dui)(dui)的*大(da)整(zheng)流(liu)。如電(dian)壓硅堆(dui)(dui)的*大(da)整(zheng)流(liu)電(dian)流(liu)為(wei)100mA時(shi)用于60kV的試驗(yan)裝置中,限流(liu)電(dian)阻按(an)R1=60/0.1=600kΩ選(xuan)擇。限流(liu)電(dian)阻還應(ying)具有足(zu)夠的容量(liang)和沿面放電(dian)距離。
高壓濾波(bo)電(dian)容C1一般選(xuan)擇在0.01~0.1μF,當(dang)被試品(pin)的電(dian)容量很大時,C1可省(sheng)略不用。
泄(xie)露試驗的操作(zuo)及注意事項
1)試(shi)驗前(qian)應先檢查(cha)被試(shi)品是否(fou)停電(dian),接地放電(dian),一切對外連線是否(fou)擦干凈。要嚴防將試(shi)驗電(dian)壓加(jia)到有人工作的(de)部位上去(qu)。
2)接好試(shi)驗裝(zhuang)置(zhi)的(de)(de)接線后,應復(fu)查無誤后才可加壓。應特別(bie)注意檢查高壓設備(bei)及(ji)引線與(yu)(yu)地(di)(di)、與(yu)(yu)操作人(ren)員(yuan)的(de)(de)**距(ju)離,被試(shi)品(pin)的(de)(de)外(wai)殼是否(fou)可靠(kao)接地(di)(di),要按**規程中所規定的(de)(de)內容進行試(shi)驗。
3)對于大電容量設備應緩慢升壓,防止被(bei)試(shi)品(pin)的充電電流(liu)燒壞微(wei)安表。必(bi)要時應分級加壓,分別讀取各級電壓下微(wei)安表的穩定讀數。
4)試(shi)驗(yan)過程(cheng)中(zhong),應密(mi)切監視被試(shi)品、試(shi)驗(yan)裝置、微安表,一旦發生擊(ji)穿、閃爍等異(yi)常現象(xiang)應立即降壓(ya),切斷電(dian)源,并(bing)查明原因,詳細(xi)記(ji)錄。
5)試(shi)驗(yan)完畢,降壓(ya),切(qie)斷電(dian)源后(hou)應將被試(shi)品(pin)及試(shi)驗(yan)裝(zhuang)置本身充(chong)分放電(dian)。
四、注意事項
1、按照您所進行的(de)試(shi)驗(yan)接(jie)好工作線路(lu)。試(shi)驗(yan)變壓(ya)器的(de)外殼以(yi)及(ji)操(cao)作系(xi)統的(de)外殼必須可靠接(jie)地(di)。試(shi)驗(yan)變壓(ya)器高壓(ya)繞組的(de)X端(高壓(ya)尾(wei))以(yi)及(ji)測量繞組的(de)F端必須可靠接(jie)地(di)。
2、做(zuo)串級(ji)試驗(yan)(yan)時,**級(ji)、第三(san)級(ji)試驗(yan)(yan)變(bian)壓器(qi)的低壓繞組(zu)的X端,測量繞組(zu)的F端以及高壓繞組(zu)的X端(高壓尾)均(jun)接本級(ji)試驗(yan)(yan)變(bian)壓器(qi)的外殼。**級(ji)、第三(san)級(ji)試驗(yan)(yan)變(bian)壓器(qi)的外殼必(bi)須(xu)通過絕緣支架接地。
3、接通(tong)(tong)電(dian)源前,操作系統的調壓(ya)器必須調到零位后方(fang)可接通(tong)(tong)電(dian)源,合閘,開始升(sheng)壓(ya)。
4、從零開(kai)(kai)始均勻旋(xuan)轉調壓(ya)(ya)器手輪升(sheng)壓(ya)(ya)。升(sheng)壓(ya)(ya)方(fang)法(fa)有:快速(su)(su)升(sheng)壓(ya)(ya)法(fa),即20s逐級升(sheng)壓(ya)(ya)法(fa);慢速(su)(su)升(sheng)壓(ya)(ya)法(fa),即60s逐級升(sheng)壓(ya)(ya)法(fa);極(ji)慢速(su)(su)升(sheng)壓(ya)(ya)法(fa)供選用(yong)。電壓(ya)(ya)從零開(kai)(kai)始按一定(ding)的升(sheng)壓(ya)(ya)方(fang)式(shi)和速(su)(su)度上(shang)升(sheng)到您所需的額定(ding)試驗電壓(ya)(ya)的75%后(hou),在(zai)以(yi)(yi)每秒2%額定(ding)試驗電壓(ya)(ya)的速(su)(su)度升(sheng)到您所需的額定(ding)電壓(ya)(ya),并(bing)密切注意測量儀(yi)表(biao)的指(zhi)示以(yi)(yi)及被試品的情(qing)況。升(sheng)壓(ya)(ya)過(guo)程中(zhong)(zhong)或(huo)試驗過(guo)程中(zhong)(zhong)如發(fa)現測量儀(yi)表(biao)的指(zhi)示及被試品情(qing)況異常,應立即降壓(ya)(ya),切斷電源,查明情(qing)況。
5、試驗完畢后,應(ying)在數秒(miao)內(nei)勻速的將調壓器返回至零位,然(ran)后切斷電源。
6、本(ben)產品不得超(chao)過額定參(can)數使用。除試驗必須外,決不允許全電(dian)壓通電(dian)或斷電(dian)。
7、 再升(sheng)壓(ya)或耐壓(ya)試(shi)驗(yan)過(guo)程中,如發現以下不正常情況時,應立即降壓(ya),切斷電(dian)源,停止(zhi)試(shi)驗(yan)并查明原因。
⑴電壓表(biao)指針擺(bai)動(或數字跳(tiao)動)很大
⑵電流表(biao)直線上升
被(bei)試(shi)品內有不正常的聲音(yin)
8、圖1中第9項系壓力閥及壓力表,為長期關閉(bi)狀態。每6個月(yue)開閥一次,以(yi)檢查SF6壓力,應不小于0.2MPa(檢查壓力后立即關閉(bi)閥門),低于0.2MPa時應加SF6氣體(ti),以(yi)增加氣絕緣(yuan)。
9、耐壓實驗前后應(ying)測量被(bei)試設備的絕緣電阻,檢查(cha)絕緣情況。
10、當試驗變壓器長(chang)期不使(shi)用時,應放置于通風、干(gan)燥(zao)、無(wu)陽光直射的地(di)方。
11、該產(chan)品不允許在高于45℃的溫度(du)下長期存放、使用(yong)、放氣。
12、運輸搬運途中不(bu)得(de)重(zhong)力沖擊。
13、產品緊固件及壓力(li)閥、壓力(li)表(biao)不得擅(shan)自(zi)松動。
14、使用本(ben)產品(pin)做高壓(ya)試驗時,出熟(shu)悉本(ben)說明書外,還必(bi)須(xu)嚴格執行國家有關標準和(he)操作規程。可(ke)參照GB311-83《高壓(ya)輸變設備的絕緣配合,高壓(ya)試驗技術(shu)》;《電氣設備預防性試驗規程》等。
五、試驗(yan)變壓器的容量選擇
標稱試驗變壓(ya)器容量Pn的(de)確定公式:Pn=kVn 2ωCt×10-9
式中:
Pn——標稱試(shi)驗變壓器(qi)容量(kVA)
Vn——試驗變壓器的額定(ding)輸出高壓的有效值(zhi)(kV)
k ——**系數。k≥1,標稱電(dian)壓Vn≥1MV時(shi),k=2;標稱電(dian)壓較低時(shi),k值可取(qu)高(gao)一些。
Ct——被試品的(de)電容量(liang)(pF)
ω——角頻(pin)率,ω=2πf,f——試(shi)驗電源(yuan)的頻(pin)率
被試設(she)備的(de)電容(rong)量(liang)Ct可由交流電橋測(ce)出(chu)。Ct的(de)變化很大,
可由設(she)備的類型而定。
典型數據如下:
簡單的棒式或懸式絕緣子(zi) 幾十微法
簡單的分級(ji)套管 100~1000pF
電壓(ya)互感器 200 ~ 500pF
電力(li)變壓器(qi) < 1000kVA~1000pF
> 1000kVA 1000~10000pF
高壓電(dian)力電(dian)纜和油浸(jin)紙(zhi)絕(jue)緣 250~300pF/m
氣體(ti)絕(jue)緣(yuan) ~60pF/m
封閉(bi)變電站,SF6氣體絕緣 100~10000Pf;
對于不同的(de)試驗電壓Vn,選擇(ze)不同的(de)(適當的(de))**系數k。
以下列(lie)出不(bu)同的(de)Vn所選用(yong)的(de)k值供參考(kao)。
Vn =50~100kV k = 4
Vn =150~300kV k = 3
Vn > 300kV k = 2
一、概述(shu)
工頻耐(nai)壓試驗是(shi)鑒定電力設備(bei)絕緣強度的(de)*嚴格(ge)、*有效和*直接(jie)的(de)方法。它(ta)能(neng)(neng)檢查出那些(xie)危險性(xing)較大的(de)集中缺陷,對(dui)判斷電力設備(bei)能(neng)(neng)否繼續參加運行具有決(jue)定性(xing)作用,是(shi)保證設備(bei)絕緣水(shui)平(ping)、避(bi)免發生絕緣事故(gu)的(de)重要手段。
本裝置是根(gen)據國家*新電力行(xing)業(ye)標準而設計的、性能先進的耐(nai)壓(ya)試(shi)驗設備,用于對各種電器產(chan)品(pin)、電氣元(yuan)件、絕緣材(cai)料等進行(xing)規(gui)定電壓(ya)下的絕緣強度試(shi)驗,以考核(he)產(chan)品(pin)的絕緣水平(ping),發現被試(shi)品(pin)的絕緣缺陷,衡量過電壓(ya)的能力。
二、產品特點
監視功能(neng):高壓電壓 低壓電流 零位指(zhi)示 電源指(zhi)示 工作(zuo)指(zhi)示 計時指(zhi)示
保護(hu)功(gong)能:過流(liu)保護(hu)、零位(wei)啟(qi)動保護(hu)、聲(sheng)光語言報警提醒
采用新型時間(jian)繼電器(qi),計時范圍更(geng)廣(guang)(1S~99H)
采(cai)用(yong)新型電流繼電器,更(geng)**、更(geng)可靠,確(que)保人身(shen)及(ji)設備**。
試驗變壓(ya)器高(gao)壓(ya)線圈為圓筒多(duo)層塔式(shi),由上(shang)等(deng)聚酯漆包線及高(gao)耐(nai)壓(ya)值(zhi)絕緣(yuan)材料繞制而成。
試驗變壓器(5kVA以上)裝有(you)可移動的鐵輪。具(ju)有(you)重量輕、體積小、移動方便、性能優越等特(te)點。
三、設備組成
1、選型配置
標準配置
|
□ 分體式
|
操作部分(fen):
□箱(xiang)式(不(bu)大于5kVA) / □臺式
容量: kVA(小于200kVA)
輸入:□AC220V / □AC380V
|
試驗(yan)變壓(ya)器:
□交(jiao)流 / □交(jiao)直流
□油變(bian) / □干變(bian) / □氣變(bian)
容量(liang): kVA(小于200kVA)
輸出:AC kV(小于300kVA)
|
□ 一體式(shi)
|
□箱(xiang)式(shi)(不大于(yu)20kV) / □臺式(shi)(不大于(yu)30kV)
容量: kVA(小于300kVA)
輸入:□AC220V / □AC380V 輸出:AC kV(不大于(yu)30kV)
|
客(ke)戶選(xuan)配
|
□標(biao)準(zhun)高壓分壓器(qi)
|
□保(bao)護球隙
|
□直流微安(an)表(biao)
|
□放(fang)**
|
□保護水(shui)阻(zu)
|
□高壓(ya)濾(lv)波(bo)電容(rong)
|
其(qi)它(ta):
|
2、對(dui)應實(shi)物
四、技術指標
1、使用(yong)條件(jian):
(1)工作場所(suo)應無嚴重影響(xiang)絕緣的氣體(ti)、蒸汽、化學性塵(chen)埃及其它爆炸性和腐(fu)蝕性介(jie)質。
(2)環境(jing)溫度 -20~+50℃
(3)環境濕度(du) ≤85% RH(無凝結水)
2、控制箱(xiang)(臺)參數(shu):(常規參數(shu)見(jian)下表)
規格
|
容量(liang)
|
輸 入 電 源
|
輸 出(chu) 電 壓
|
重量(liang)(kg)
|
相數
|
(V)
|
(A)
|
(V)
|
(A)
|
2/220
|
2
|
1
|
220
|
10
|
0-250
|
8
|
14
|
3/220
|
3
|
1
|
220
|
15
|
0-250
|
12
|
16
|
5/220
|
5
|
1
|
220
|
25
|
0-250
|
20
|
18
|
10/220
|
10
|
1
|
220
|
50
|
0-250
|
40
|
80
|
15/380
|
15
|
2
|
380
|
37.5
|
0-430
|
34.8
|
90
|
20/380
|
20
|
2
|
380
|
50
|
0-430
|
46.5
|
100
|
25/380
|
25
|
2
|
380
|
62.5
|
0-430
|
58.1
|
120
|
30/380
|
30
|
2
|
380
|
75
|
0-430
|
69.7
|
140
|
50/380
|
50
|
2
|
380
|
125
|
0-430
|
116.2
|
160
|
100/380
|
100
|
2
|
380
|
250
|
0-430
|
232.5
|
250
|
說明:如(ru)有特殊(shu)參(can)數(shu)要(yao)求(qiu),可按用戶的技術參(can)數(shu)進行設計制作。
3、試驗變壓器參(can)數:(常規參(can)數見下表(biao))
規格
|
容量(liang)
kVA
|
低(di)壓側
|
高(gao)壓側(ce)
|
高壓(ya)側(交直(zhi)流變壓(ya)器)
|
測量(liang)變比
|
60分(fen)鐘溫升(sheng)℃
|
阻抗電壓%
|
空載(zai)電(dian)流
%
|
質量
kg
|
電壓
V
|
電流
A
|
交流輸出
|
直流輸(shu)出
|
電壓kV
|
電(dian)流
|
電壓kV
|
電流
|
1.5/50
|
1.5
|
200
|
7.5
|
50
|
30
|
70
|
21.4
|
500
|
50
|
10
|
<4
|
19.5
|
3/50
|
3
|
200
|
15
|
50
|
60
|
70
|
42.9
|
500
|
50
|
10
|
<4
|
27
|
5/50
|
5
|
200
|
25
|
50
|
100
|
70
|
71.4
|
500
|
50
|
10
|
<4
|
52
|
10/50
|
10
|
200
|
50
|
50
|
200
|
70
|
142.9
|
500
|
50
|
10
|
<4
|
80
|
15/50
|
15
|
400
|
37.5
|
50
|
300
|
70
|
214.3
|
500
|
50
|
8
|
<4
|
120
|
20/50
|
20
|
400
|
50
|
50
|
400
|
70
|
285.7
|
500
|
50
|
8
|
<4
|
140
|
30/50
|
30
|
400
|
75
|
50
|
600
|
70
|
428.6
|
500
|
50
|
8
|
<4
|
155
|
50/50
|
50
|
400
|
125
|
50
|
1000
|
70
|
714.3
|
500
|
50
|
8
|
<4
|
184
|
10/100
|
10
|
200
|
50
|
100
|
100
|
140
|
71.4
|
1000
|
50
|
10
|
<4
|
135
|
15/100
|
15
|
400
|
37.5
|
100
|
150
|
140
|
107.1
|
1000
|
50
|
8
|
<4
|
150
|
20/100
|
20
|
400
|
50
|
100
|
200
|
140
|
142.9
|
1000
|
50
|
8
|
<4
|
215
|
30/100
|
30
|
400
|
75
|
100
|
300
|
140
|
214.3
|
1000
|
50
|
8
|
<4
|
250
|
50/100
|
50
|
400
|
125
|
100
|
500
|
140
|
357.1
|
1000
|
50
|
8
|
<4
|
290
|
10/150
|
10
|
200
|
50
|
100
|
66.7
|
140
|
47.6
|
1500
|
50
|
10
|
<4
|
180
|
15/150
|
15
|
400
|
37.5
|
150
|
100
|
210
|
71.4
|
1500
|
50
|
8
|
<4
|
200
|
20/150
|
30
|
400
|
50
|
150
|
133.3
|
210
|
95.2
|
1500
|
50
|
8
|
<4
|
220
|
30/150
|
30
|
400
|
75
|
150
|
200
|
210
|
142.9
|
1500
|
50
|
8
|
<4
|
280
|
50/150
|
50
|
400
|
125
|
150
|
333.3
|
210
|
238.1
|
1500
|
50
|
8
|
<4
|
340
|
說明(ming):如有特殊參數(shu)要求(qiu),可按用戶(hu)的技術參數(shu)進行設計(ji)制作。
上表的重量(liang)以油浸式(shi)試驗變(bian)壓(ya)(ya)器(qi)為例,干式(shi)試驗變(bian)壓(ya)(ya)器(qi)和充(chong)氣式(shi)試驗變(bian)壓(ya)(ya)器(qi)稍有不同(tong)。
五(wu)、接線及工(gong)作原理
1、調壓部分接線及原理(li)
調壓(ya)(ya)部分(fen)由控制部分(fen)和(he)試驗變壓(ya)(ya)器(qi)組(zu)成。控制部分(fen)是由接觸式調壓(ya)(ya)器(qi)及其(qi)控制、保護、測量、信號(hao)電路(lu)組(zu)成。試驗變壓(ya)(ya)器(qi)由低壓(ya)(ya)繞(rao)(rao)組(zu)、高壓(ya)(ya)繞(rao)(rao)組(zu)、儀表繞(rao)(rao)組(zu)三(san)部分(fen)組(zu)成。
試(shi)驗(yan)變(bian)(bian)(bian)(bian)(bian)壓(ya)器(qi)為交直(zhi)流(liu)兩用時,試(shi)驗(yan)變(bian)(bian)(bian)(bian)(bian)壓(ya)器(qi)配置了高(gao)壓(ya)硅(gui)堆(油變(bian)(bian)(bian)(bian)(bian)、氣變(bian)(bian)(bian)(bian)(bian)為內(nei)置,干變(bian)(bian)(bian)(bian)(bian)為外置),高(gao)壓(ya)可輸出交流(liu)和直(zhi)流(liu)。輸出交流(liu)時,要(yao)求接入短路桿(油變(bian)(bian)(bian)(bian)(bian)、氣變(bian)(bian)(bian)(bian)(bian))或(huo)去掉外置硅(gui)堆(干變(bian)(bian)(bian)(bian)(bian));輸出直(zhi)流(liu)時,要(yao)求擰出短路桿(油變(bian)(bian)(bian)(bian)(bian)、氣變(bian)(bian)(bian)(bian)(bian))或(huo)加(jia)上外置硅(gui)堆(干變(bian)(bian)(bian)(bian)(bian))
通過接入工頻電(dian)源,調節調壓器,以(yi)獲得所需要的試(shi)驗高壓電(dian)壓值(zhi)。其工作原(yuan)理(li)見圖1:
2、試驗部(bu)分接線(xian)及原理
做耐壓試驗(yan)時,控制(zhi)部分(fen)、變壓器(qi)的(de)接地端及高(gao)壓尾必須(xu)可靠(kao)接地。有條件(jian)的(de)情況下,做工頻(pin)耐壓試驗(yan)請加(jia)上限流電阻、標準高(gao)壓分(fen)壓器(qi)、球隙保護電阻及保護球隙,如圖3。
做(zuo)直(zhi)(zhi)流(liu)耐壓(ya)試驗請(qing)(qing)另外加(jia)上(shang)微(wei)安表(biao),微(wei)安表(biao)必須接(jie)在(zai)(zai)(zai)硅(gui)堆(dui)(dui)和被(bei)試器之間,油變(bian)(bian)或氣變(bian)(bian)一般擰(ning)在(zai)(zai)(zai)高(gao)壓(ya)頭上(shang)面(mian)(要(yao)求擰(ning)出短路桿),干(gan)變(bian)(bian)擰(ning)在(zai)(zai)(zai)外置硅(gui)堆(dui)(dui)上(shang)面(mian);為了更準確(que)顯示高(gao)壓(ya)直(zhi)(zhi)流(liu)泄(xie)漏電流(liu),請(qing)(qing)將分壓(ya)器的(de)高(gao)壓(ya)線接(jie)在(zai)(zai)(zai)微(wei)安表(biao)和硅(gui)堆(dui)(dui)之間,(油變(bian)(bian)、氣變(bian)(bian))如圖4,(干(gan)變(bian)(bian))如圖5。
耐壓(ya)(ya)試(shi)(shi)驗中限(xian)流電(dian)阻(zu)R1應根據試(shi)(shi)驗變壓(ya)(ya)器(qi)的額(e)定容量來選擇。如(ru)高壓(ya)(ya)側額(e)定輸(shu)出(chu)電(dian)流在100~300mA時,可取(qu)0.5~1Ω/V(試(shi)(shi)驗電(dian)壓(ya)(ya));高壓(ya)(ya)側額(e)定輸(shu)出(chu)電(dian)流為1A以上時,可取(qu)1Ω/V(試(shi)(shi)驗電(dian)壓(ya)(ya))。常用(yong)水(shui)電(dian)阻(zu)作為限(xian)流電(dian)阻(zu),管子長(chang)度可按150kV/m考(kao)慮,管子粗(cu)細應具有(you)足夠的熱容量(水(shui)阻(zu)液配制方法:用(yong)蒸餾(liu)水(shui)加入適量硫酸(suan)銅配制成各種不同(tong)的阻(zu)值)。
球間隙(xi)及保(bao)護(hu)(hu)電(dian)(dian)阻(zu):當電(dian)(dian)壓(ya)(ya)(ya)超過(guo)球間隙(xi)整定值時(shi)(一(yi)般取試(shi)(shi)驗電(dian)(dian)壓(ya)(ya)(ya)的110%~120%),球間隙(xi)放電(dian)(dian),對被試(shi)(shi)品起(qi)到保(bao)護(hu)(hu)作用。球間隙(xi)保(bao)護(hu)(hu)電(dian)(dian)阻(zu)可按(an)1Ω/V(試(shi)(shi)驗電(dian)(dian)壓(ya)(ya)(ya))選取。
在(zai)工(gong)頻耐壓(ya)(ya)(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)(yan)(yan)中,低電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)側測量電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(儀表電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya))不(bu)是非常準(zhun)(zhun)確的(de)(de)(de),其原因是由于(yu)(yu)試(shi)(shi)驗(yan)(yan)(yan)變(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器存在(zai)著(zhu)漏抗,在(zai)這個漏抗上(shang)必(bi)然(ran)存在(zai)著(zhu)壓(ya)(ya)(ya)(ya)(ya)(ya)降或容(rong)升,使試(shi)(shi)品上(shang)的(de)(de)(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)低于(yu)(yu)或高(gao)于(yu)(yu)低壓(ya)(ya)(ya)(ya)(ya)(ya)側測量電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)表上(shang)反映出來(lai)的(de)(de)(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)。工(gong)頻耐壓(ya)(ya)(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)(yan)(yan)時,被(bei)試(shi)(shi)品上(shang)的(de)(de)(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)高(gao)于(yu)(yu)試(shi)(shi)驗(yan)(yan)(yan)變(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器的(de)(de)(de)輸出電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya),也就是所謂(wei)容(rong)升現象。感應耐壓(ya)(ya)(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)(yan)(yan)時,試(shi)(shi)驗(yan)(yan)(yan)變(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)器的(de)(de)(de)漏抗必(bi)然(ran)存在(zai)著(zhu)壓(ya)(ya)(ya)(ya)(ya)(ya)降。為了準(zhun)(zhun)確測量被(bei)試(shi)(shi)品上(shang)所施加的(de)(de)(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya),因此(ci)常在(zai)高(gao)壓(ya)(ya)(ya)(ya)(ya)(ya)側接入(ru)標準(zhun)(zhun)高(gao)壓(ya)(ya)(ya)(ya)(ya)(ya)分壓(ya)(ya)(ya)(ya)(ya)(ya)器來(lai)測量電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)。
五(wu)、面板(ban)結構說明
1、操作(zuo)箱面板(ban)
控制箱為箱式鋁合(he)金(jin)結(jie)構,面板采(cai)用(yong)拉絲(si)鋁合(he)金(jin)工藝(yi),所有(you)電器元(yuan)(yuan)件(jian)均裝在骨架上,便于安裝和維(wei)修。面板元(yuan)(yuan)件(jian)布(bu)置如(ru)下:
2、操作臺面板
操作臺為(wei)臺式結構(gou),殼體(ti)為(wei)冷扎鋼(gang)板(ban)結構(gou),面板(ban)采用鋁合金拉絲工藝,面板(ban)元件布置如下:
六、操作指南
本裝(zhuang)置在操作之前應根據(ju)不同被試(shi)(shi)品的容(rong)量(liang)、電(dian)(dian)(dian)壓(ya)等級,先計算好*大工作電(dian)(dian)(dian)流,并調整電(dian)(dian)(dian)流保護器。其試(shi)(shi)驗(yan)接(jie)(jie)線(xian)應參考本說(shuo)明書中(zhong)圖(tu)(tu)1、圖(tu)(tu)2、圖(tu)(tu)3、圖(tu)(tu)4、圖(tu)(tu)5,必須(xu)可靠(kao)接(jie)(jie)地。
1、操作要點
(1)試(shi)(shi)驗(yan)前,應(ying)了解(jie)被試(shi)(shi)品的(de)試(shi)(shi)驗(yan)電壓(ya)(ya),同(tong)時了解(jie)被試(shi)(shi)品的(de)其他試(shi)(shi)驗(yan)項目及以前的(de)試(shi)(shi)驗(yan)結果。若被試(shi)(shi)品有缺(que)陷或異常(chang),應(ying)在消除后再進行耐壓(ya)(ya)試(shi)(shi)驗(yan)。
(2)試(shi)驗現場(chang)應圍好(hao)遮攔或(huo)圍繩,掛好(hao)標(biao)示牌,并派專人監護。
(3)試(shi)驗前,被(bei)試(shi)品(pin)表面應擦拭干凈,將被(bei)試(shi)品(pin)的(de)外殼和非(fei)被(bei)試(shi)繞組可靠接地。被(bei)試(shi)品(pin)為新(xin)沖油設備時(shi)(shi)(shi),應按《規程》規定使油靜(jing)止(zhi)一定時(shi)(shi)(shi)間再升壓,對110kV及以下的(de)充油電(dian)(dian)力(li)設備,在注滿油后靜(jing)置時(shi)(shi)(shi)間應不(bu)少(shao)于(yu)24小時(shi)(shi)(shi),對220kV及330kV的(de)充油電(dian)(dian)力(li)設備,靜(jing)置時(shi)(shi)(shi)間應不(bu)少(shao)于(yu)48小時(shi)(shi)(shi)。
(4)接好試驗接線后(hou)(hou),應(ying)由有經(jing)驗的人員檢查,確認(ren)無(wu)誤(wu)后(hou)(hou)方(fang)可升(sheng)壓。
(5)升(sheng)壓前,首先檢查調(diao)(diao)壓器(qi)是(shi)否在零(ling)(ling)位。調(diao)(diao)壓器(qi)在零(ling)(ling)位方(fang)可升(sheng)壓。
(6)升(sheng)壓(ya)(ya)過程中不(bu)(bu)僅要(yao)監視(shi)電(dian)(dian)壓(ya)(ya)表的(de)變化,還(huan)應監視(shi)電(dian)(dian)流表的(de)變化,以(yi)及被(bei)試品電(dian)(dian)流的(de)變化。升(sheng)壓(ya)(ya)時(shi)(shi)要(yao)均(jun)勻升(sheng)壓(ya)(ya),不(bu)(bu)能太快。升(sheng)至規定試驗電(dian)(dian)壓(ya)(ya)時(shi)(shi),開(kai)始計算時(shi)(shi)間,時(shi)(shi)間到(dao)后,緩慢均(jun)勻降下電(dian)(dian)壓(ya)(ya)。絕不(bu)(bu)允許不(bu)(bu)降壓(ya)(ya)就(jiu)先跳開(kai)電(dian)(dian)源開(kai)關(guan)。
(7)試驗中(zhong)發(fa)現表(biao)針(zhen)擺動或被(bei)試品有異常聲響、冒煙等應立即降下電壓,拉開電源,在高壓側掛上接(jie)地(di)線后,再查明原因。
(8)耐壓試驗前后均應測(ce)量被試品的(de)絕(jue)緣電阻。
2、操作步驟(zou)
(1) 按(an)試(shi)驗要求將控制部分、試(shi)驗變(bian)壓器(qi)、被試(shi)品正確接好線,必須可靠(kao)接地,請參考圖(tu)1、圖(tu)2、圖(tu)3、圖(tu)4、圖(tu)5。
(2) 根據(ju)試驗的要求,整定“時(shi)間繼電(dian)器(qi)”及“過流繼電(dian)器(qi)”。
A 時間繼電器設置(zhi):
T1,T2,T3,T4設(she)置0~9任意數字(zi),T可設(she)置為H(小時),M(分鐘),S(秒)。
根(gen)據試(shi)驗要求,在1S~99H內可以(yi)任意設(she)置定(ding)時時間。
B 過流繼電器設(she)置:
過流動作(zuo)設(she)定值=過流繼電(dian)器刻度盤讀數×測量(liang)變(bian)比×K,其中K為電(dian)流倍(bei)率(lv)/切除開(kai)關的狀態(tai)值,分別為X1,X2,OFF,電(dian)流倍(bei)率(lv)/切除開(kai)關處于×1,×2位置時,K值分別為1、2,切換為OFF擋時,K值為+∞。(注(zhu):不要使用OFF檔,因為會(hui)使變(bian)壓(ya)器失去(qu)過流保護功(gong)能而導致設(she)備(bei)損壞。測量(liang)變(bian)比為電(dian)流互(hu)感器的變(bian)比,沒有電(dian)流互(hu)感器時為1)。
(3) 接入電源,此時(shi),“電源燈(deng)”亮,表示(shi)外部電源已引(yin)入。如“零(ling)(ling)位(wei)燈(deng)”亮,表示(shi)調(diao)壓(ya)器在零(ling)(ling)位(wei)。如“零(ling)(ling)位(wei)燈(deng)”不亮,應逆(ni)時(shi)針(zhen)旋轉調(diao)節調(diao)壓(ya)器手柄至“零(ling)(ling)位(wei)燈(deng)”亮,表示(shi)可進(jin)行調(diao)壓(ya)操作。
(4)按“啟動按鈕”。此時,“送(song)電燈”,“電源(yuan)燈”和“零位(wei)燈”亮;進入(ru)送(song)電狀態(tai)。
(5)以2kV/S勻(yun)速順時(shi)(shi)針旋(xuan)轉調壓(ya)器手柄至被試(shi)(shi)品規定的耐壓(ya)值,并密切(qie)(qie)注(zhu)(zhu)視電(dian)流(liu)(liu)表(直(zhi)流(liu)(liu)耐壓(ya)試(shi)(shi)驗(yan)時(shi)(shi),同時(shi)(shi)密切(qie)(qie)注(zhu)(zhu)視直(zhi)流(liu)(liu)微安表)。此(ci)時(shi)(shi),“電(dian)源燈(deng)”,“工作(zuo)燈(deng)”亮(liang);“零位燈(deng)”滅(mie)。
(6)根據試(shi)驗啟動“計(ji)時按鈕”,計(ji)時開始(shi),并注意被(bei)試(shi)品的情況。
(7)當耐壓計(ji)時(shi)到時(shi),操作臺自動聲光報警。應立(li)即(ji)逆(ni)時(shi)針旋轉調壓器(qi)手柄至零(ling)位(wei),按下停止按鈕和解除計(ji)時(shi)按鈕自鎖狀態。此(ci)時(shi)“電源燈”, “零(ling)位(wei)燈”亮,“工(gong)作燈”滅。試驗即(ji)告完(wan)畢
(8)拔掉電源,拆除接線,試(shi)驗結束(shu)。
(9)在升壓(ya)或(huo)耐壓(ya)過程中,如發生短路(lu)、閃絡、擊穿過流時(shi),過流繼電器(qi)動(dong)作,切斷主回路(lu)。此(ci)時(shi)應將調壓(ya)器(qi)逆時(shi)針旋(xuan)轉至零位(wei),切斷電源,并(bing)查明原因,并(bing)作詳細記錄(lu)。
(10)試(shi)驗完畢(bi),降壓,切斷電源后應(ying)用放**將(jiang)被試(shi)品及試(shi)驗裝置本身充分(fen)放電。
七(qi)、產品維護
1、開箱驗收時(shi),應檢(jian)查主(zhu)控回路接(jie)線(xian)是(shi)否(fou)松動,調壓器電刷是(shi)否(fou)接(jie)觸(chu)良好;
2、長期(qi)不(bu)用(yong)時,使(shi)用(yong)前應用(yong)500V兆歐表測量(liang)絕(jue)緣電阻(zu),其阻(zu)值不(bu)低于0.5MΩ;
3、電源電壓(ya)應符合控制箱(臺)銘牌上的輸(shu)入(ru)電壓(ya)值;
4、本裝(zhuang)置設(she)有過電(dian)流(liu)保護,出廠已調(diao)整為額定(ding)電(dian)流(liu)的50%。用于(yu)小(xiao)負載時,應根據被試品(pin)的額定(ding)容量電(dian)流(liu)重新設(she)定(ding);
5、使用(yong)完畢后,應關(guan)好(hao)控(kong)制箱(xiang)(臺)門,以保(bao)持控(kong)制箱(xiang)(臺)內部(bu)清潔。
八、注(zhu)意事項
1、按照(zhao)您所(suo)進行的試(shi)驗接好工作線路。試(shi)驗變(bian)壓(ya)器的外(wai)殼以(yi)及(ji)操作系統的外(wai)殼必須(xu)(xu)可靠接地(di)。試(shi)驗變(bian)壓(ya)器的高(gao)壓(ya)繞組(zu)的X端(duan)(高(gao)壓(ya)尾(wei))以(yi)及(ji)測量繞組(zu)的F端(duan)必須(xu)(xu)可靠接地(di)。
2、做(zuo)串(chuan)級(ji)(ji)試驗時,**級(ji)(ji)、第(di)三級(ji)(ji)試驗變(bian)壓(ya)(ya)器的低壓(ya)(ya)繞(rao)組成X端(duan),測量繞(rao)組的F端(duan)以及高壓(ya)(ya)繞(rao)組的X端(duan)(高壓(ya)(ya)端(duan))均接本級(ji)(ji)試驗變(bian)壓(ya)(ya)器具外殼(ke)。**級(ji)(ji)、第(di)三級(ji)(ji)試驗變(bian)壓(ya)(ya)器的外殼(ke)必(bi)須通過絕緣支(zhi)架接地。
3、接通電源前,操(cao)作系統(tong)的調(diao)壓(ya)(ya)器必須調(diao)到(dao)零(ling)位后方可接通電源,合(he)閘,開始升(sheng)壓(ya)(ya)。從零(ling)開始勻速旋轉調(diao)壓(ya)(ya)器手輪(lun)升(sheng)壓(ya)(ya)。升(sheng)壓(ya)(ya)方式有:快速升(sheng)壓(ya)(ya)法(fa)(fa)(fa),即20s逐級升(sheng)壓(ya)(ya)法(fa)(fa)(fa);慢速升(sheng)壓(ya)(ya)法(fa)(fa)(fa),即60s逐級升(sheng)壓(ya)(ya)法(fa)(fa)(fa);極(ji)慢速升(sheng)壓(ya)(ya)法(fa)(fa)(fa)供選用。電壓(ya)(ya)從零(ling)開始按一定(ding)(ding)的升(sheng)壓(ya)(ya)方式和速度上升(sheng)到(dao)您(nin)所(suo)需的額定(ding)(ding)試(shi)(shi)驗電壓(ya)(ya)的75%后,再(zai)以每秒2%額定(ding)(ding)試(shi)(shi)驗電壓(ya)(ya)的速度升(sheng)到(dao)您(nin)所(suo)需的試(shi)(shi)驗電壓(ya)(ya),并密切注意測(ce)量(liang)儀表的及被(bei)試(shi)(shi)品的情況。升(sheng)壓(ya)(ya)過程(cheng)中(zhong)或試(shi)(shi)驗過程(cheng)中(zhong)如發(fa)現測(ce)量(liang)儀表的指示及被(bei)試(shi)(shi)品情況異(yi)常,應(ying)立即降壓(ya)(ya),切斷電源,查明情況。
4、試驗完(wan)畢后(hou),應在數秒內勻速的(de)將調壓器返(fan)回至零(ling)位,然(ran)后(hou)切斷電源。本產(chan)品不得超(chao)過額(e)定參數使用(yong)。
5、使用(yong)本(ben)(ben)產品(pin)做(zuo)高壓試驗(yan)時,除熟悉本(ben)(ben)說明書外(wai),還必須嚴格執行國(guo)家有關(guan)標準和(he)操作(zuo)規(gui)程(cheng)(cheng)。可(ke)參(can)照(zhao)GB311.1 – 97《高壓輸變設備的絕緣配合,高壓試驗(yan)技術》;《電氣設備預防性試驗(yan)規(gui)程(cheng)(cheng)》等
一、概述
智能耐(nai)壓(ya)試(shi)驗裝置是根據國(guo)家*新(xin)電(dian)(dian)力行業標準而設計的(de)、性能先進(jin)的(de)智能型耐(nai)壓(ya)試(shi)驗設備,用(yong)于(yu)對各種(zhong)電(dian)(dian)器產品(pin)、電(dian)(dian)氣元件、絕(jue)緣(yuan)材(cai)料等進(jin)行規定(ding)電(dian)(dian)壓(ya)下(xia)的(de)絕(jue)緣(yuan)強度(du)試(shi)驗,以考核產品(pin)的(de)絕(jue)緣(yuan)水平,發現(xian)被(bei)試(shi)品(pin)的(de)絕(jue)緣(yuan)缺陷,衡量(liang)過電(dian)(dian)壓(ya)的(de)能力。廣泛應用(yong)于(yu)電(dian)(dian)工(gong)制造部門、電(dian)(dian)力運行部門、科(ke)研單位和高等院校。
二、產(chan)品特點
1. 320×240液晶顯示器、高速熱敏打(da)印(yin)機(ji)。
2. 高(gao)壓(ya)(ya)電(dian)壓(ya)(ya)、高(gao)壓(ya)(ya)電(dian)流、低(di)壓(ya)(ya)電(dian)壓(ya)(ya)、低(di)壓(ya)(ya)電(dian)流4路測量方式,高(gao)精度傳(chuan)感器和高(gao)性能14位AD采集芯片(pian)。
3. 人機對話全鍵(jian)盤(pan)操作方式,智能化(hua)工作全過程,任選自動方式和手動方式。
4. 實時顯示(shi)(shi)高(gao)壓(ya)(ya)電壓(ya)(ya)、高(gao)壓(ya)(ya)電流(liu)、低壓(ya)(ya)電壓(ya)(ya)、低壓(ya)(ya)電流(liu),時間(jian)及耐(nai)壓(ya)(ya)結果,顯示(shi)(shi)直觀明了(le)。
5. 完善的過壓(ya)(ya)、過流(liu)保護,任意(yi)設定輸出電(dian)壓(ya)(ya)、高壓(ya)(ya)電(dian)流(liu)上(shang)限、低壓(ya)(ya)電(dian)流(liu)上(shang)限和計時時間(jian)。
6. 具(ju)有回零(ling)檢測功能,回零(ling)確定后才可進(jin)行試驗,**可靠。
7. 具有絕(jue)緣電阻測試(shi)功能,直(zhi)接反映(ying)被試(shi)品(pin)絕(jue)緣強度(du)。
8. 逼(bi)近式調壓(ya)(ya)(ya)算(suan)法,到達(da)設定電壓(ya)(ya)(ya)后自動(dong)(dong)耐壓(ya)(ya)(ya)計(ji)時(shi),計(ji)時(shi)結束后自動(dong)(dong)降壓(ya)(ya)(ya)回零。
9. 超過設定(ding)高壓(ya)電(dian)流或低壓(ya)電(dian)流時(shi)自動切斷電(dian)壓(ya)輸出,降壓(ya)回零,并(bing)發生聲(sheng)光報警。
10. 精(jing)良(liang)的軟硬(ying)件(jian)抗干擾設(she)計,多種抗干擾手段(duan),適應(ying)惡劣電磁環(huan)境。
11. 自動(dong)錯誤診斷(duan),易于發現和解(jie)決問題。
12. 可(ke)選配無線遙(yao)控控制功能、遠(yuan)程通信、門聯鎖警(jing)鈴、外接分壓器校驗接口等。
三(san)、設備組成
1、選型配置
標(biao)準配置
|
□ 分體式
|
操(cao)作部分:
□箱式(不(bu)大于5kVA) / □臺式
容量(liang): kVA(小于200kVA)
輸入:□AC220V / □AC380V
|
試驗(yan)變壓器:
□交(jiao)(jiao)流(liu) / □交(jiao)(jiao)直流(liu)
□油變(bian) / □干變(bian) / □氣變(bian)
容量: kVA(小于(yu)200kVA)
輸出:AC kV(小于300kVA)
|
□ 一體(ti)式
|
□箱式(shi)(不大于20kV) / □臺式(shi)(不大于30kV)
容量: kVA(小于300kVA)
輸入(ru):□AC220V / □AC380V 輸出:AC kV(不(bu)大于30kV)
|
客戶選配
|
□標準高(gao)壓分壓器
|
□保護(hu)球隙
|
□直(zhi)流微安表(biao)
|
□放(fang)**
|
□保(bao)護水阻
|
□高(gao)壓(ya)濾波電容
|
其(qi)它:
|
2、對應實物
四、技術(shu)指標
1、使用條件:
(1)工(gong)作(zuo)場所應無嚴重影(ying)響絕緣的氣體、蒸汽、化學性(xing)塵(chen)埃及其(qi)它爆炸性(xing)和腐蝕性(xing)介質。
(2)環境溫度(du) -20~+50℃
(3)環境濕(shi)度 ≤85% RH(無凝結水)
2、控制(zhi)箱(臺)參(can)數:(常(chang)規參(can)數見下表)
(1)計時范(fan)圍:0-999S
(3)電(dian)壓(ya)精度(du) ≤1.5% ±1個(ge)字(F.S)
(4)電(dian)流精(jing)度 ≤1.5% ±1個字(zi)(F.S)
規格(ge)
|
容量
|
輸 入 電 源
|
輸 出 電(dian) 壓
|
重量(liang)(kg)
|
相數
|
(V)
|
(A)
|
(V)
|
(A)
|
2/220
|
2
|
1
|
220
|
10
|
0-250
|
8
|
14
|
3/220
|
3
|
1
|
220
|
15
|
0-250
|
12
|
16
|
5/220
|
5
|
1
|
220
|
25
|
0-250
|
20
|
18
|
10/220
|
10
|
1
|
220
|
50
|
0-250
|
40
|
80
|
15/380
|
15
|
2
|
380
|
37.5
|
0-430
|
34.8
|
90
|
20/380
|
20
|
2
|
380
|
50
|
0-430
|
46.5
|
100
|
25/380
|
25
|
2
|
380
|
62.5
|
0-430
|
58.1
|
120
|
30/380
|
30
|
2
|
380
|
75
|
0-430
|
69.7
|
140
|
50/380
|
50
|
2
|
380
|
125
|
0-430
|
116.2
|
160
|
100/380
|
100
|
2
|
380
|
250
|
0-430
|
232.5
|
250
|
說明(ming):如有特殊參數(shu)要求,可按(an)用戶的技術參數(shu)進行設計制(zhi)作。
3、試驗變壓器參數:(常規(gui)參數見下(xia)表)
規格
|
容(rong)量
kVA
|
低壓(ya)側
|
高(gao)壓側
|
高壓(ya)(ya)側(交(jiao)直流變壓(ya)(ya)器(qi))
|
測量變(bian)比(bi)
|
60分鐘溫(wen)升(sheng)℃
|
阻抗電壓%
|
空載電流
%
|
質量
kg
|
電壓
V
|
電流
A
|
交流輸出
|
直流輸(shu)出
|
電(dian)壓(ya)kV
|
電(dian)流
|
電壓kV
|
電流(liu)
|
1.5/50
|
1.5
|
200
|
7.5
|
50
|
30
|
70
|
21.4
|
500
|
50
|
10
|
<4
|
19.5
|
3/50
|
3
|
200
|
15
|
50
|
60
|
70
|
42.9
|
500
|
50
|
10
|
<4
|
27
|
5/50
|
5
|
200
|
25
|
50
|
100
|
70
|
71.4
|
500
|
50
|
10
|
<4
|
52
|
10/50
|
10
|
200
|
50
|
50
|
200
|
70
|
142.9
|
500
|
50
|
10
|
<4
|
80
|
15/50
|
15
|
400
|
37.5
|
50
|
300
|
70
|
214.3
|
500
|
50
|
8
|
<4
|
120
|
20/50
|
20
|
400
|
50
|
50
|
400
|
70
|
285.7
|
500
|
50
|
8
|
<4
|
140
|
30/50
|
30
|
400
|
75
|
50
|
600
|
70
|
428.6
|
500
|
50
|
8
|
<4
|
155
|
50/50
|
50
|
400
|
125
|
50
|
1000
|
70
|
714.3
|
500
|
50
|
8
|
<4
|
184
|
10/100
|
10
|
200
|
50
|
100
|
100
|
140
|
71.4
|
1000
|
50
|
10
|
<4
|
135
|
15/100
|
15
|
400
|
37.5
|
100
|
150
|
140
|
107.1
|
1000
|
50
|
8
|
<4
|
150
|
20/100
|
20
|
400
|
50
|
100
|
200
|
140
|
142.9
|
1000
|
50
|
8
|
<4
|
215
|
30/100
|
30
|
400
|
75
|
100
|
300
|
140
|
214.3
|
1000
|
50
|
8
|
<4
|
250
|
50/100
|
50
|
400
|
125
|
100
|
500
|
140
|
357.1
|
1000
|
50
|
8
|
<4
|
290
|
10/150
|
10
|
200
|
50
|
100
|
66.7
|
140
|
47.6
|
1500
|
50
|
10
|
<4
|
180
|
15/150
|
15
|
400
|
37.5
|
150
|
100
|
210
|
71.4
|
1500
|
50
|
8
|
<4
|
200
|
20/150
|
30
|
400
|
50
|
150
|
133.3
|
210
|
95.2
|
1500
|
50
|
8
|
<4
|
220
|
30/150
|
30
|
400
|
75
|
150
|
200
|
210
|
142.9
|
1500
|
50
|
8
|
<4
|
280
|
50/150
|
50
|
400
|
125
|
150
|
333.3
|
210
|
238.1
|
1500
|
50
|
8
|
<4
|
340
|
說(shuo)明(ming):如有特(te)殊參數(shu)要求,可按用戶的技術參數(shu)進行設計制作(zuo)。
上表的重量以油浸(jin)式(shi)試(shi)驗(yan)變壓器(qi)為(wei)例,干式(shi)試(shi)驗(yan)變壓器(qi)和充氣式(shi)試(shi)驗(yan)變壓器(qi)稍有不(bu)同。
五、接線(xian)及工(gong)作原理
1、調壓部(bu)分接線及原理
調壓(ya)部分(fen)(fen)由(you)(you)控(kong)制(zhi)部分(fen)(fen)和試(shi)驗(yan)(yan)變壓(ya)器組成。控(kong)制(zhi)部分(fen)(fen)是(shi)由(you)(you)接(jie)觸式調壓(ya)器、單(dan)片機(ji)控(kong)制(zhi)系(xi)統、液(ye)晶、打印機(ji)、信號測量(liang)、電路保護組成。試(shi)驗(yan)(yan)變壓(ya)器由(you)(you)低壓(ya)繞(rao)組、高(gao)壓(ya)繞(rao)組、儀(yi)表(biao)繞(rao)組三部分(fen)(fen)組成。
試驗變(bian)(bian)壓(ya)(ya)(ya)器為交(jiao)直(zhi)流(liu)(liu)兩用時,試驗變(bian)(bian)壓(ya)(ya)(ya)器配(pei)置(zhi)了高(gao)壓(ya)(ya)(ya)硅堆(油變(bian)(bian)、氣變(bian)(bian)為內(nei)置(zhi),干變(bian)(bian)為外置(zhi)),高(gao)壓(ya)(ya)(ya)可輸(shu)出交(jiao)流(liu)(liu)和直(zhi)流(liu)(liu)。輸(shu)出交(jiao)流(liu)(liu)時,要(yao)求(qiu)接入(ru)短(duan)路桿(gan)(gan)(油變(bian)(bian)、氣變(bian)(bian))或去掉外置(zhi)硅堆(干變(bian)(bian));輸(shu)出直(zhi)流(liu)(liu)時,要(yao)求(qiu)擰出短(duan)路桿(gan)(gan)(油變(bian)(bian)、氣變(bian)(bian))或加(jia)上(shang)外置(zhi)硅堆(干變(bian)(bian))
通過接(jie)入工頻電源,調(diao)節調(diao)壓器,以獲得所(suo)需要的試驗高壓電壓值(zhi)。其工作原理見(jian)圖1:
2、試驗部分接(jie)線及原理
做耐壓(ya)(ya)試(shi)驗(yan)(yan)時(shi),控制部(bu)分、變壓(ya)(ya)器的接地(di)端及高壓(ya)(ya)尾(wei)必須可(ke)靠接地(di)。有條件的情(qing)況下,做工頻耐壓(ya)(ya)試(shi)驗(yan)(yan)請加上限流電阻、標準高壓(ya)(ya)分壓(ya)(ya)器、球隙保(bao)護(hu)電阻及保(bao)護(hu)球隙,如圖3。
做直流(liu)(liu)耐(nai)壓試驗請另外加上微(wei)安(an)表,微(wei)安(an)表必須接在硅(gui)堆和(he)被(bei)試器(qi)之(zhi)間,油變(bian)(bian)或氣變(bian)(bian)一般擰(ning)(ning)在高壓頭(tou)上面(mian)(要求擰(ning)(ning)出(chu)短路桿),干變(bian)(bian)擰(ning)(ning)在外置硅(gui)堆上面(mian);為了更準確顯(xian)示高壓直流(liu)(liu)泄漏(lou)電流(liu)(liu),請將(jiang)分壓器(qi)的高壓線接在微(wei)安(an)表和(he)硅(gui)堆之(zhi)間,(油變(bian)(bian)、氣變(bian)(bian))如圖4,(干變(bian)(bian))如圖5。
耐壓(ya)(ya)試(shi)驗(yan)中限流(liu)電(dian)阻(zu)R1應(ying)根據試(shi)驗(yan)變壓(ya)(ya)器(qi)的額定容量來選擇。如高壓(ya)(ya)側額定輸(shu)出電(dian)流(liu)在100~300mA時(shi),可取(qu)(qu)0.5~1Ω/V(試(shi)驗(yan)電(dian)壓(ya)(ya));高壓(ya)(ya)側額定輸(shu)出電(dian)流(liu)為(wei)1A以上時(shi),可取(qu)(qu)1Ω/V(試(shi)驗(yan)電(dian)壓(ya)(ya))。常(chang)用(yong)水電(dian)阻(zu)作(zuo)為(wei)限流(liu)電(dian)阻(zu),管(guan)子(zi)長度可按150kV/m考慮,管(guan)子(zi)粗細應(ying)具有足夠的熱容量(水阻(zu)液配(pei)制方(fang)法:用(yong)蒸餾水加入適量硫酸銅(tong)配(pei)制成各(ge)種不(bu)同的阻(zu)值)。
球(qiu)間(jian)隙及保護(hu)電(dian)阻(zu):當電(dian)壓超過球(qiu)間(jian)隙整(zheng)定值(zhi)時(一(yi)般取試(shi)驗電(dian)壓的110%~120%),球(qiu)間(jian)隙放電(dian),對被試(shi)品起到保護(hu)作用。球(qiu)間(jian)隙保護(hu)電(dian)阻(zu)可按1Ω/V(試(shi)驗電(dian)壓)選取。
在工(gong)頻(pin)耐(nai)(nai)壓(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)(yan)中,低(di)電(dian)壓(ya)(ya)(ya)(ya)側(ce)測量(liang)電(dian)壓(ya)(ya)(ya)(ya)(儀表電(dian)壓(ya)(ya)(ya)(ya))不是(shi)(shi)非常(chang)準確的(de),其原因是(shi)(shi)由于試(shi)(shi)驗(yan)(yan)變壓(ya)(ya)(ya)(ya)器(qi)(qi)存(cun)在著(zhu)漏(lou)抗(kang),在這個漏(lou)抗(kang)上必然存(cun)在著(zhu)壓(ya)(ya)(ya)(ya)降或容升,使試(shi)(shi)品(pin)(pin)(pin)上的(de)電(dian)壓(ya)(ya)(ya)(ya)低(di)于或高(gao)于低(di)壓(ya)(ya)(ya)(ya)側(ce)測量(liang)電(dian)壓(ya)(ya)(ya)(ya)表上反映出(chu)來的(de)電(dian)壓(ya)(ya)(ya)(ya)。工(gong)頻(pin)耐(nai)(nai)壓(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)(yan)時,被(bei)試(shi)(shi)品(pin)(pin)(pin)上的(de)電(dian)壓(ya)(ya)(ya)(ya)高(gao)于試(shi)(shi)驗(yan)(yan)變壓(ya)(ya)(ya)(ya)器(qi)(qi)的(de)輸出(chu)電(dian)壓(ya)(ya)(ya)(ya),也就是(shi)(shi)所謂(wei)容升現象(xiang)。感應耐(nai)(nai)壓(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)(yan)時,試(shi)(shi)驗(yan)(yan)變壓(ya)(ya)(ya)(ya)器(qi)(qi)的(de)漏(lou)抗(kang)必然存(cun)在著(zhu)壓(ya)(ya)(ya)(ya)降。為了準確測量(liang)被(bei)試(shi)(shi)品(pin)(pin)(pin)上所施加的(de)電(dian)壓(ya)(ya)(ya)(ya),因此常(chang)在高(gao)壓(ya)(ya)(ya)(ya)側(ce)接入標準高(gao)壓(ya)(ya)(ya)(ya)分壓(ya)(ya)(ya)(ya)器(qi)(qi)來測量(liang)電(dian)壓(ya)(ya)(ya)(ya)。
六、操(cao)作要點
1、試驗(yan)前,應了解被(bei)(bei)試品(pin)的試驗(yan)電(dian)壓,同(tong)時了解被(bei)(bei)試品(pin)的其他(ta)試驗(yan)項(xiang)目(mu)及以前的試驗(yan)結(jie)果。若被(bei)(bei)試品(pin)有缺陷或異常,應在消除后再進(jin)行耐(nai)壓試驗(yan)。
2、試驗現(xian)場應圍好遮(zhe)攔或圍繩,掛好標示牌,并派(pai)專人監(jian)護。
3、試(shi)驗前,被試(shi)品表(biao)面應(ying)(ying)擦拭干(gan)凈(jing),將被試(shi)品的(de)外殼(ke)和非被試(shi)繞組可靠接地。被試(shi)品為新沖油(you)(you)設備時(shi),應(ying)(ying)按《規(gui)程》規(gui)定使油(you)(you)靜止一定時(shi)間再升壓,對110kV及以下(xia)的(de)充油(you)(you)電力設備,在注(zhu)滿油(you)(you)后靜置時(shi)間應(ying)(ying)不少(shao)于(yu)24小時(shi),對220kV及330kV的(de)充油(you)(you)電力設備,靜置時(shi)間應(ying)(ying)不少(shao)于(yu)48小時(shi)。
4、接好(hao)試驗接線后,應由有經驗的人員檢查,確認無誤后方可升壓。
5、升壓(ya)前,首先(xian)檢查調(diao)壓(ya)器(qi)是否在(zai)零位。調(diao)壓(ya)器(qi)在(zai)零位方可升壓(ya)。
6、升(sheng)(sheng)壓過程中不(bu)僅(jin)要監視(shi)電(dian)(dian)壓的變化(hua),還應監視(shi)電(dian)(dian)流(liu)的變化(hua),以及被試品泄漏(lou)電(dian)(dian)流(liu)的變化(hua)。升(sheng)(sheng)壓時要均(jun)勻升(sheng)(sheng)壓,不(bu)能太快。升(sheng)(sheng)至規定試驗(yan)電(dian)(dian)壓時,開(kai)始計時,時間到(dao)后,緩慢均(jun)勻降下電(dian)(dian)壓。絕不(bu)允許不(bu)降壓就先跳開(kai)電(dian)(dian)源(yuan)開(kai)關。
7、試驗中發(fa)現被試品(pin)有異常聲(sheng)響、冒(mao)煙等應(ying)立即降(jiang)下電壓(ya),拉開電源,在高壓(ya)側(ce)掛上接地線后(hou),再(zai)查明原因(yin)。耐壓(ya)試驗前后(hou)均應(ying)測量被試品(pin)的絕(jue)緣電阻。
七、面板功(gong)能說(shuo)明
打印機(ji):打印機(ji)是熱敏打印機(ji),當試(shi)驗完(wan)成后按(an)鍵盤上的“打印”按(an)鈕打印試(shi)驗結果。
RS232:RS232是與計算機相連(lian)的串口(kou)(kou)通信(xin)接口(kou)(kou),是用戶選配接口(kou)(kou),本裝置沒有配置這個接口(kou)(kou)。
LCD對比度(du):因為液晶(jing)顯示屏在溫度(du)和(he)光線有所不同時稍有些變化,可以(yi)通過LCD對比度(du)調(diao)節背光到(dao)適(shi)合亮度(du)。
液晶: 320x240像素(su)點陣(zhen)白色(se)背光液晶,在強(qiang)光和陰暗環境下(xia)都十(shi)分清楚。
指示燈(deng):由啟動燈(deng)、零位燈(deng)、指示燈(deng)三(san)個燈(deng)組成,啟動燈(deng)和(he)警示燈(deng)是高(gao)亮七彩燈(deng)。
操作提示:有一些簡短的提示語句和安裝(zhuang)接線圖。
緊(jin)急(ji)開關:在(zai)(zai)緊(jin)急(ji)情況下按此開關,即(ji)可以切斷(duan)變壓(ya)器電(dian)源(yuan),也可以切斷(duan)工作電(dian)源(yuan)。(箱式安(an)裝在(zai)(zai)面板上(shang),臺式安(an)裝在(zai)(zai)柜體上(shang))
鍵盤:由上、下(xia)、左、右、設置、打印、確(que)定、取消8個鍵組成(cheng),是(shi)用(yong)戶和設備交互(hu)的終(zhong)端(duan)。
電(dian)源(yuan)開關(guan):工作電(dian)源(yuan),帶通電(dian)指示燈(deng)。
八、軟件使用說明
按試(shi)驗要求將控制部(bu)分、試(shi)驗變壓器、被(bei)試(shi)品正確接(jie)好線,必須可靠接(jie)地,請參考圖(tu)1、圖(tu)2、圖(tu)3、圖(tu)4、圖(tu)5。
1、開機使用
開機處于“歡迎(ying)界(jie)面”,如圖7:
根(gen)據鍵盤的示圖8,按上↑、下↓、左(zuo)←,右(you)→可以切換“自動(dong)(dong)耐壓試(shi)(shi)驗(yan)”或“手動(dong)(dong)耐壓試(shi)(shi)驗(yan)”,在“自動(dong)(dong)試(shi)(shi)驗(yan)”或“手動(dong)(dong)試(shi)(shi)驗(yan)”里面選擇(ze)“交流試(shi)(shi)驗(yan)方式”或“直流試(shi)(shi)驗(yan)方式”。如圖9
說明:
(1)當配置的是交直(zhi)流(liu)(liu)(liu)兩用(yong)(yong)控(kong)制部分時(shi),使用(yong)(yong)直(zhi)流(liu)(liu)(liu)輸(shu)出時(shi)軟件(jian)操作請(qing)進入直(zhi)流(liu)(liu)(liu)試(shi)驗方(fang)式(shi),交流(liu)(liu)(liu)輸(shu)出時(shi)軟件(jian)操作請(qing)進入交流(liu)(liu)(liu)試(shi)驗方(fang)式(shi),如果選擇錯誤(wu)會導致儀器顯示電壓會和輸(shu)出實際(ji)電壓不一致。
(2)當配置(zhi)的(de)是交直流兩(liang)用變壓器時(shi),使用直流時(shi)請將變壓器的(de)短路桿取出,當使用交流時(shi)請將短路桿插入擰緊。
(3)如(ru)果配(pei)置的是交流控制部分(fen)時,軟件界面里就沒有交直流試驗方式(如(ru)圖9)的選擇項。
選中試驗方式后,按確定可以進入主(zhu)界面,如圖10:
動態顯示區(qu):一直處于采集信號,并顯示高壓電壓、高壓電流(liu)、低(di)壓電壓、低(di)壓電流(liu)。
結果(guo)顯示區:如果(guo)試驗(yan)沒有被擊穿時,顯示平均高(gao)壓(ya)(ya)電(dian)(dian)(dian)壓(ya)(ya),平均高(gao)壓(ya)(ya)電(dian)(dian)(dian)流,平均低壓(ya)(ya)電(dian)(dian)(dian)壓(ya)(ya),平均低壓(ya)(ya)電(dian)(dian)(dian)流,絕緣(yuan)電(dian)(dian)(dian)阻;否之,顯示峰(feng)值(zhi)電(dian)(dian)(dian)壓(ya)(ya),峰(feng)值(zhi)電(dian)(dian)(dian)流,低壓(ya)(ya)電(dian)(dian)(dian)壓(ya)(ya),低壓(ya)(ya)電(dian)(dian)(dian)流。
設置數據(ju)區:設置試驗中需要的(de)參(can)數數據(ju)輸出(chu)電(dian)壓為(wei)(wei)在自(zi)動(dong)方式下的(de)升壓目(mu)標耐(nai)壓值(zhi)耐(nai)壓時(shi)間為(wei)(wei)耐(nai)壓過(guo)(guo)程的(de)時(shi)間長度電(dian)流(liu)(liu)上限為(wei)(wei)高壓電(dian)流(liu)(liu)峰值(zhi)的(de)上限,高壓電(dian)流(liu)(liu)超過(guo)(guo)電(dian)流(liu)(liu)上限將(jiang)認(ren)為(wei)(wei)擊穿過(guo)(guo)流(liu)(liu)保(bao)護為(wei)(wei)低壓電(dian)流(liu)(liu)峰值(zhi)的(de)上限,低壓電(dian)流(liu)(liu)超過(guo)(guo)過(guo)(guo)流(liu)(liu)保(bao)護將(jiang)認(ren)為(wei)(wei)擊穿
信(xin)息顯(xian)示區:顯(xian)示試驗過(guo)程中(zhong)的試驗狀態(tai)和提(ti)示信(xin)息。
試驗(yan)操作(zuo)區:選擇設置、試驗(yan)、回零命令。
2、設置(zhi)參數
在主界(jie)面上,選中“設置”,然(ran)后按確定后進入設置界(jie)面,如圖11:
按(an)左←,右→時(shi)切(qie)換(huan)光標(biao)(biao)移動位(wei)置(zhi),按(an)上↑、下↓時(shi)更改(gai)光標(biao)(biao)位(wei)置(zhi)數據的(de)值(zhi)。光標(biao)(biao)位(wei)置(zhi)和設置(zhi)的(de)數值(zhi)全部可以自動循環(huan),前且在使用時(shi)有默認的(de)標(biao)(biao)準值(zhi)。如(ru)果所有的(de)參數都(dou)設置(zhi)完成(cheng),按(an)取消退出設置(zhi)回到主(zhu)界面開始狀態。
3、手(shou)動試驗
零位檢查—當選中“試驗”后(hou),按確定就進入(ru)提示試驗狀態。如果調壓器不在零位,將提示“試驗前(qian)請先回零”,退出(chu)試驗并且切換到回零命令。
試(shi)驗(yan)過程—回零確(que)認(ren)后,可(ke)以進行試(shi)驗(yan)。選中“試(shi)驗(yan)”后按確(que)定,接觸器合閘,這時(shi)輸出電壓幾乎為0,如圖12:
按(an)上↑,高壓(ya)(ya)電(dian)壓(ya)(ya)將(jiang)不斷(duan)升壓(ya)(ya),松開就(jiu)停(ting)止升壓(ya)(ya),如果到(dao)上限就(jiu)提示滿量程;
按下↓,高壓(ya)(ya)電(dian)壓(ya)(ya)將不斷降(jiang)壓(ya)(ya),松開就(jiu)停止降(jiang)壓(ya)(ya),如(ru)果(guo)到下限就(jiu)提示已(yi)回零(ling);
按計時←,計時開始工作,到(dao)耐壓時間計時結束完成試驗;
按(an)取消→,取消試驗(yan)過程;
在升壓(ya)過(guo)(guo)(guo)程(cheng)(cheng)中,如果(guo)高壓(ya)電(dian)(dian)(dian)流(liu)(liu)峰(feng)值(zhi)(zhi)超過(guo)(guo)(guo)“電(dian)(dian)(dian)流(liu)(liu)上限(xian)(xian)”值(zhi)(zhi)或低壓(ya)電(dian)(dian)(dian)流(liu)(liu)峰(feng)值(zhi)(zhi)超過(guo)(guo)(guo)“過(guo)(guo)(guo)流(liu)(liu)保護(hu)”值(zhi)(zhi)將(jiang)認(ren)為被(bei)試(shi)(shi)(shi)品(pin)被(bei)擊穿(chuan),接觸器(qi)立刻(ke)分閘(zha)并顯(xian)示(shi)試(shi)(shi)(shi)驗(yan)(yan)結(jie)(jie)果(guo),包括峰(feng)值(zhi)(zhi)電(dian)(dian)(dian)壓(ya)、峰(feng)值(zhi)(zhi)電(dian)(dian)(dian)流(liu)(liu)、低壓(ya)電(dian)(dian)(dian)流(liu)(liu)等,調壓(ya)器(qi)開始回(hui)零(ling),回(hui)零(ling)完成試(shi)(shi)(shi)驗(yan)(yan)結(jie)(jie)束。如果(guo)在耐壓(ya)過(guo)(guo)(guo)程(cheng)(cheng)中,高壓(ya)電(dian)(dian)(dian)流(liu)(liu)和低壓(ya)電(dian)(dian)(dian)流(liu)(liu)峰(feng)值(zhi)(zhi)沒(mei)有超設置(zhi)上限(xian)(xian)值(zhi)(zhi),認(ren)為被(bei)試(shi)(shi)(shi)品(pin)未擊穿(chuan),結(jie)(jie)果(guo)顯(xian)示(shi)區就(jiu)顯(xian)示(shi)耐壓(ya)電(dian)(dian)(dian)壓(ya)、高壓(ya)電(dian)(dian)(dian)流(liu)(liu)、低壓(ya)電(dian)(dian)(dian)流(liu)(liu)、絕緣電(dian)(dian)(dian)阻等,調壓(ya)器(qi)開始回(hui)零(ling),回(hui)零(ling)完成后接觸器(qi)分閘(zha)試(shi)(shi)(shi)驗(yan)(yan)結(jie)(jie)束。
4、自動試驗
自動(dong)試驗(yan)和手(shou)動(dong)試驗(yan)的試驗(yan)過程類似,首(shou)先也進行(xing)回零檢(jian)查,確認后進入(ru)如(ru)下界面,如(ru)圖13:
按(an)上方(fang)法切換到“開始”確(que)定后(hou)進(jin)行試驗(yan),與手動試驗(yan)不同之(zhi)處就是(shi)升壓過程將自動升壓到“輸(shu)出(chu)電壓”值,然后(hou)進(jin)行計時。
升(sheng)壓(ya)過程為(wei)逼近方式,首先(xian)升(sheng)到到接(jie)近目標值(zhi)(zhi),然后(hou)再進行微調,保(bao)證高壓(ya)電壓(ya)值(zhi)(zhi)幾乎為(wei)輸出電壓(ya)值(zhi)(zhi)。
5、功能選擇
按鍵盤上的“設置(zhi)”就進入功能(neng)界(jie)面,如圖(tu)14:
進入功(gong)能界面后,可以(yi)選擇“時(shi)鐘設置”、“注意事項(xiang)”等界面。
時鐘(zhong)(zhong)設置(zhi):設置(zhi)時鐘(zhong)(zhong)的時間,為打(da)印報表(biao)提(ti)供時間依(yi)據(ju)。
注意事(shi)項:為(wei)用戶提供一(yi)些操作規范和**注意事(shi)項。
6、打(da)印
按(an)鍵盤“打印(yin)”按(an)鍵可以打印(yin)試驗(yan)果,在(zai)此不贅(zhui)述。
七、產品維(wei)護(hu)
1、開箱驗(yan)收時,應檢查主(zhu)控回路接(jie)線是否松動,調(diao)壓器電刷是否接(jie)觸良好。
2.、長期不用(yong)時,使用(yong)前應(ying)用(yong)500V兆歐表測(ce)量絕(jue)緣電(dian)阻(zu),其阻(zu)值不低于0.5MΩ。
3、電(dian)源電(dian)壓應(ying)符合(he)控(kong)制箱(xiang)(臺)說(shuo)明書上(shang)的輸入電(dian)壓值(zhi)要求。
4、本控制箱(臺)設有(you)過電(dian)流(liu)保護,出廠已(yi)調整為額定電(dian)流(liu)的50%。用于小負載時,應根(gen)據被試品的額定容(rong)量(liang)電(dian)流(liu)重新設定;
5、使用完(wan)畢后,應(ying)關(guan)好(hao)控制(zhi)箱(臺)門蓋,以保持內部清(qing)潔。
八(ba)、注(zhu)意事項
1、按照您(nin)所進行(xing)的(de)(de)試(shi)驗接好工作線路。試(shi)驗變壓(ya)器的(de)(de)外殼以及操作系統的(de)(de)外殼必須(xu)可靠接地。試(shi)驗變壓(ya)器的(de)(de)測量繞組(zu)的(de)(de)F端(duan)和(he)外殼必須(xu)可靠接地。
2、做串級(ji)試驗(yan)時,**級(ji)、第(di)三級(ji)試驗(yan)變(bian)壓(ya)器(qi)的(de)低壓(ya)繞組成X端(duan),測量(liang)繞組的(de)F端(duan)以及高(gao)壓(ya)繞組的(de)X端(duan)(高(gao)壓(ya)端(duan))均接本級(ji)試驗(yan)變(bian)壓(ya)器(qi)具(ju)外殼。**級(ji)、第(di)三級(ji)試驗(yan)變(bian)壓(ya)器(qi)的(de)外殼必須通過(guo)絕緣支架(jia)接地。
接通電(dian)源前,控制箱(臺)的調壓器必須調到(dao)零位后(hou)方(fang)可接通電(dian)源,合閘(zha),開始升壓。
3、從零開始勻(yun)速(su)旋轉(zhuan)調(diao)壓(ya)(ya)(ya)(ya)器(qi)手輪(lun)升(sheng)壓(ya)(ya)(ya)(ya)。升(sheng)壓(ya)(ya)(ya)(ya)方式有:快(kuai)速(su)升(sheng)壓(ya)(ya)(ya)(ya)法(fa)(fa),即20s逐級升(sheng)壓(ya)(ya)(ya)(ya)法(fa)(fa);慢速(su)升(sheng)壓(ya)(ya)(ya)(ya)法(fa)(fa),即60s逐級升(sheng)壓(ya)(ya)(ya)(ya)法(fa)(fa);極(ji)慢速(su)升(sheng)壓(ya)(ya)(ya)(ya)法(fa)(fa)供選用(yong)。電壓(ya)(ya)(ya)(ya)從零開始按(an)一定的(de)升(sheng)壓(ya)(ya)(ya)(ya)方式和速(su)度上升(sheng)到您(nin)所需的(de)額定試(shi)驗電壓(ya)(ya)(ya)(ya)的(de)75%后,再(zai)以每秒2%額定試(shi)驗電壓(ya)(ya)(ya)(ya)的(de)速(su)度升(sheng)到您(nin)所需的(de)試(shi)驗電壓(ya)(ya)(ya)(ya),并密切(qie)注意測量(liang)儀表(biao)的(de)及(ji)被(bei)(bei)試(shi)品的(de)情況。升(sheng)壓(ya)(ya)(ya)(ya)過程(cheng)(cheng)中(zhong)或(huo)試(shi)驗過程(cheng)(cheng)中(zhong)如(ru)發現測量(liang)儀表(biao)的(de)指示及(ji)被(bei)(bei)試(shi)品情況異常,應立即降壓(ya)(ya)(ya)(ya),切(qie)斷(duan)電源,查明情況。
4、試(shi)驗(yan)完(wan)畢后(hou),應在等調壓器(qi)返回至零位,然(ran)后(hou)切斷(duan)電源(yuan)。
5、本產(chan)品不得超(chao)過(guo)額定參(can)數使用(yong)。
6、使用本(ben)產品做高(gao)(gao)壓試(shi)(shi)驗(yan)(yan)時,除(chu)熟悉本(ben)說(shuo)明書外,還必(bi)須嚴格(ge)執(zhi)行國家(jia)有關標準和操作規程。可參照GB311.1 – 97《高(gao)(gao)壓輸(shu)變設備的絕緣配合(he),高(gao)(gao)壓試(shi)(shi)驗(yan)(yan)技術》;《電氣設備預防(fang)性試(shi)(shi)驗(yan)(yan)規程》等(deng)。
7、控制箱(xiang)(臺)應與試(shi)驗(yan)變壓(ya)器(qi)(qi)配(pei)套使(shi)(shi)用(yong),控制箱(xiang)(臺)的(de)(de)使(shi)(shi)用(yong)方法,請詳細參閱控制器(qi)(qi)的(de)(de)使(shi)(shi)用(yong)說(shuo)明書。