一、WBYD2000串聯諧振設備基本原理
耐(nai)壓(ya)試(shi)驗是(shi)利用電(dian)抗器的(de)電(dian)感(gan)與被(bei)試(shi)品電(dian)容組成LC串聯回(hui)路(lu),調節變頻電(dian)源輸出的(de)電(dian)壓(ya)頻率,在(zai)被(bei)試(shi)品上獲得高電(dian)壓(ya),是(shi)當前高電(dian)壓(ya)試(shi)驗的(de)一種新方法,深(shen)受專家好(hao)評(ping),在(zai)國內外已經得到(dao)廣泛的(de)使用。
根據諧振(zhen)原理,我們知道當電(dian)抗器L的感抗值(zhi)(zhi)Xl與回(hui)路中的容抗值(zhi)(zhi)Xc相等時(shi),回(hui)路達到諧振(zhen)狀態(tai),此時(shi)回(hui)路中僅回(hui)路電(dian)阻R消(xiao)耗有功功率(lv),而無功功率(lv)則在(zai)電(dian)抗器與試(shi)(shi)品電(dian)容之間來回(hui)振(zhen)蕩,從而在(zai)試(shi)(shi)品上產(chan)生高壓。
二、WBYD2000串聯諧振設備系統構成
全套試驗(yan)系統(tong)(tong)由調頻電(dian)源主機、電(dian)抗器、分壓器、激勵變(bian)壓器和補償電(dian)容器(可選器件)組成,接入被試品后組成一個(ge)諧振(zhen)系統(tong)(tong)進行(xing)交流耐壓實(shi)驗(yan)。
主機: 就是一臺幅值和頻率可(ke)調的正弦(xian)波交流調頻電源,給諧振回路提(ti)供激勵(li)源,同(tong)時提(ti)供電壓(ya)顯示、電流顯示、計(ji)時、保護(hu)、報(bao)警等功能。
電(dian)抗(kang)器:就是一個大電(dian)感(gan)線圈,與被試品(pin)(相當于(yu)電(dian)容)構成回路,可配置電(dian)抗(kang)器多節電(dian)抗(kang)器,使用(yong)時通過不(bu)(bu)同(tong)的(de)串(chuan)聯(lian)、并(bing)聯(lian)組合、實現不(bu)(bu)同(tong)的(de)電(dian)感(gan)量以適用(yong)不(bu)(bu)同(tong)的(de)試驗條件。
分壓器:內(nei)部通過電(dian)容器分壓,從試品上(shang)高電(dian)壓分得低電(dian)壓供主機測量、控制使用。
勵磁變壓(ya)器(qi):隔離主(zhu)機(ji)電(dian)(dian)源與諧振回路電(dian)(dian)源,并升(sheng)高主(zhu)機(ji)的輸出電(dian)(dian)壓(ya)。
補(bu)償(chang)(chang)(chang)電(dian)(dian)(dian)容(rong)(rong)器(qi):當試(shi)品(pin)(pin)電(dian)(dian)(dian)容(rong)(rong)量很小(xiao)時,如果要實現系統諧振可(ke)能(neng)要求的(de)電(dian)(dian)(dian)源頻率超出試(shi)驗標準的(de)規定,可(ke)在試(shi)品(pin)(pin)上并聯一個補(bu)償(chang)(chang)(chang)電(dian)(dian)(dian)容(rong)(rong),以實現試(shi)驗要求,稱此電(dian)(dian)(dian)容(rong)(rong)器(qi)為補(bu)償(chang)(chang)(chang)電(dian)(dian)(dian)容(rong)(rong)器(qi)。
三、WBYD2000串聯諧振設備主要技術性能
功(gong)率(lv)電(dian)源電(dian)壓:AC380V±10%、50Hz;
儀器電源(yuan):220V±10%、50Hz;
諧振輸出容量:200kVA;
儀(yi)器額定電壓:0~200kV;
輸(shu)出頻率范圍:30~300Hz;
輸(shu)出(chu)電壓波(bo)形(xing):正(zheng)弦波(bo),波(bo)形(xing)畸(ji)變率(lv)<0.5%;
頻率調節靈敏度:0.1Hz,不穩定度≤0.05%;
系統噪聲:≤60db;
9、系統測(ce)量精度:<1級;
10.輸出電(dian)壓不穩(wen)定:<0.5%;
11.保護響應時(shi)間:1us;
12.電感非線性(xing)度:≤0.05%;;
13.滿功率輸出(chu)下,連續(xu)工作時(shi)間為60min
14.環境溫(wen)度(du):-15℃~+50℃;
15.相(xiang)對濕度:≤90%RH;
16.海拔(ba)高(gao)度:≤2000米。
四、WBYD2000串聯諧振設備面板及部件名稱
五、WBYD2000串聯諧振設備操作步驟
1、正確連線,檢(jian)查(cha)無誤后方可送電。
必要時工作(zuo)電(dian)源的(de)跳過現場漏電(dian)保安器(qi),以(yi)免不(bu)必要的(de)跳閘(zha)。
2、打開電(dian)源開關,主機開始工作,液(ye)晶屏(ping)顯示版權頁(ye)(ye),該頁(ye)(ye)標明本(ben)裝置的軟件版本(ben)號。
觸按確(que)認鍵,進(jin)入系統菜(cai)(cai)單(dan),該主菜(cai)(cai)單(dan)下有(you):試驗(yan)方案(an)、開(kai)始試驗(yan)、試驗(yan)幫助(zhu)、系統設置(zhi)、實用(yong)工具和試驗(yan)記錄等六(liu)個(ge)子菜(cai)(cai)單(dan)項。
3、 系統(tong)設(she)置(zhi)菜(cai)單(dan)(dan)下有電抗(kang)器(qi)電感、日期(qi)時(shi)間設(she)置(zhi)和(he)采(cai)樣(yang)系數設(she)置(zhi)等三個子菜(cai)單(dan)(dan)項。按(an)(an)上下鍵,上下移動(dong)光標系統(tong)參數設(she)置(zhi)菜(cai)單(dan)(dan)項,觸按(an)(an)確定鈕后(hou),進入系統(tong)參數設(she)置(zhi)菜(cai)單(dan)(dan),可以分別設(she)定電抗(kang)器(qi)的電感—H、-年-月-日、-時(shi)-分-秒(miao)和(he)電壓和(he)電流的采(cai)樣(yang)系數也就(jiu)是采(cai)樣(yang)倍率,設(she)定完(wan)成后(hou),觸按(an)(an)返還鍵返回上**菜(cai)單(dan)(dan)。
電(dian)抗(kang)器電(dian)感量的設定(ding):按(an)確(que)定(ding)鍵選擇到(dao)此項,按(an)左右鍵移動(dong)光(guang)標需要改變的數位,按(an)上(shang)下鍵改變數值(zhi),達(da)到(dao)所要達(da)到(dao)的數值(zhi)按(an)確(que)定(ding)鍵確(que)認。
日(ri)期時間的設定(ding):按(an)(an)確(que)定(ding)鍵選擇到此項,按(an)(an)左右鍵移動(dong)光標(biao)需要(yao)改變的數位,按(an)(an)上下(xia)鍵改變數值,按(an)(an)照所要(yao)設置的年月(yue)日(ri)時間數值按(an)(an)確(que)定(ding)鍵確(que)認。
采樣(yang)系(xi)數的(de)設(she)(she)定(ding)(ding)(ding)(ding):按確定(ding)(ding)(ding)(ding)鍵(jian)選擇到高壓/電(dian)流采樣(yang)系(xi)數項(xiang),此(ci)項(xiang)為電(dian)壓或電(dian)流采樣(yang)倍(bei)率的(de)設(she)(she)定(ding)(ding)(ding)(ding)。一般出廠前(qian)設(she)(she)定(ding)(ding)(ding)(ding)好了(le)。如需修改,要(yao)輸入密碼。(密碼廠家與設(she)(she)備(bei)一起提供一般設(she)(she)定(ding)(ding)(ding)(ding)為:188888)
警告:系統默認上一次電(dian)(dian)抗(kang)(kang)器電(dian)(dian)感、日期(qi)時間和采(cai)(cai)樣系數設(she)定(ding)(ding)值。如果需(xu)改變要重新設(she)定(ding)(ding)。電(dian)(dian)抗(kang)(kang)器電(dian)(dian)感量設(she)定(ding)(ding)值與實(shi)際使用的(de)電(dian)(dian)抗(kang)(kang)器電(dian)(dian)感量不(bu)對(dui),會導致試驗報告中的(de)被試品電(dian)(dian)容(rong)量不(bu)準(zhun)。其他并不(bu)會影響。采(cai)(cai)樣系數設(she)置不(bu)正確,會導致顯示電(dian)(dian)壓電(dian)(dian)流(liu)不(bu)準(zhun)將很有可能會對(dui)被試品或(huo)試驗設(she)備(bei)造(zao)成損(sun)壞。
4、試(shi)驗方案菜(cai)單下有預置(zhi)保護電流、找頻(pin)(pin)起始頻(pin)(pin)率(lv)(lv)(lv)、找頻(pin)(pin)結(jie)束頻(pin)(pin)率(lv)(lv)(lv)、預定(ding)起始功率(lv)(lv)(lv)四個子(zi)菜(cai)單項,分別設(she)定(ding)本次試(shi)驗的保護電流、找頻(pin)(pin)起始頻(pin)(pin)率(lv)(lv)(lv)、找頻(pin)(pin)結(jie)束頻(pin)(pin)率(lv)(lv)(lv)、輸(shu)出起始功率(lv)(lv)(lv),全(quan)部(bu)設(she)定(ding)完成后,觸按返還(huan)鍵(jian)進入預置(zhi)試(shi)驗電壓和預置(zhi)試(shi)驗時間設(she)置(zhi)菜(cai)單。
可(ke)以(yi)分3段時(shi)間(jian)設置試驗電壓(ya)和試驗時(shi)間(jian), 實際試驗時(shi),若設定(ding)為自(zi)動試驗, 裝置將按設定(ding)的3段電壓(ya)及時(shi)間(jian),按順序分別(bie)加(jia)壓(ya), 全部完成(cheng)后自(zi)動退出.
如果**段電壓(ya)設為0, 或時間設為0, 那么執行完**段試驗電壓(ya)加壓(ya)后退(tui)出試驗, 只(zhi)加壓(ya)**段設定的(de)電壓(ya).
如果第(di)(di)三段電壓設為0, 或時間設為0, 不執行第(di)(di)三段加壓.
試驗(yan)(yan)方(fang)案設(she)置(zhi)的(de)設(she)定(ding)(ding):在試驗(yan)(yan)電壓項中(zhong),按確定(ding)(ding)單鈕,移動左右光標到需要改變的(de)數(shu)位,按上下單鈕以改變當前(qian)數(shu)位的(de)數(shu)值大(da)小,觸按返回鈕完(wan)(wan)成當前(qian)數(shu)位的(de)數(shu)值設(she)定(ding)(ding),依(yi)次選擇下一項數(shu)值的(de)設(she)定(ding)(ding),直(zhi)至分別完(wan)(wan)成試驗(yan)(yan)時間、起始頻(pin)率、起始功率的(de)設(she)置(zhi),方(fang)可完(wan)(wan)成本次試驗(yan)(yan)的(de)試驗(yan)(yan)方(fang)案設(she)置(zhi)的(de)設(she)定(ding)(ding)。
出廠(chang)默認值(zhi):試驗電(dian)(dian)壓(ya) 20kV、加壓(ya)時間 2min、激勵(li)強(qiang)度 2%、輸出電(dian)(dian)流20A、頻率范圍(wei)30-300Hz。
5、實(shi)用工具(ju)菜單(dan)下(xia)有
頻率計算:在實驗前(qian)可對諧振頻率進(jin)行(xing)計算。只需輸入具體參(can)與試(shi)驗的電感、電容值并(bing)按確定鍵(jian)試(shi)驗頻率即直(zhi)接(jie)生成。
6、開始(shi)試驗菜(cai)單(dan)(dan)下有自動(dong)試驗模(mo)式(shi)(shi)和(he)手動(dong)試驗模(mo)式(shi)(shi)兩種子菜(cai)單(dan)(dan)可供選擇。
按確認鍵進入所選試(shi)驗步驟.
自動試(shi)驗(yan)模(mo)式的(de)操作:選中自動試(shi)驗(yan)模(mo)式后,觸(chu)按菜(cai)(cai)單(dan)鈕進入正(zheng)在自動尋找(zhao)諧(xie)振(zhen)(zhen)點菜(cai)(cai)單(dan)項,裝(zhuang)置在設(she)定的(de)頻(pin)率(lv)范(fan)圍內自動尋找(zhao)諧(xie)振(zhen)(zhen)點(如果被試(shi)品電容C和電抗器電感L的(de)實際諧(xie)振(zhen)(zhen)頻(pin)率(lv)不(bu)在設(she)定的(de)頻(pin)率(lv)范(fan)圍內,將找(zhao)不(bu)到諧(xie)振(zhen)(zhen)點,此時根據(ju)需要調整頻(pin)率(lv)范(fan)圍或調整被試(shi)品回(hui)路的(de)LC參數)。當找(zhao)到諧(xie)振(zhen)(zhen)點時,會有(you)聲(sheng)音(yin)提(ti)示。
找到諧振(zhen)點后(hou),裝(zhuang)置(zhi)自(zi)動進入正(zheng)在自(zi)動升壓(ya)菜單(dan)項,當升到試驗電(dian)壓(ya)設定的電(dian)壓(ya)時(shi),裝(zhuang)置(zhi)停止加壓(ya)。
當裝置升到(dao)試(shi)(shi)(shi)驗(yan)(yan)電(dian)壓(ya)(ya)設(she)定的電(dian)壓(ya)(ya)時,設(she)備(bei)(bei)停(ting)止加(jia)(jia)壓(ya)(ya),自動(dong)進入正在加(jia)(jia)壓(ya)(ya)試(shi)(shi)(shi)驗(yan)(yan)菜(cai)單項(xiang)(xiang),并自動(dong)記(ji)錄(lu)試(shi)(shi)(shi)驗(yan)(yan)的加(jia)(jia)壓(ya)(ya)時間(jian),當加(jia)(jia)壓(ya)(ya)時間(jian)到(dao)達設(she)定時間(jian)時,設(she)備(bei)(bei)逐步降(jiang)壓(ya)(ya)退(tui)出試(shi)(shi)(shi)驗(yan)(yan),完成本次試(shi)(shi)(shi)驗(yan)(yan),進入試(shi)(shi)(shi)驗(yan)(yan)結束菜(cai)單項(xiang)(xiang)。并可選擇保存試(shi)(shi)(shi)驗(yan)(yan)數據或打(da)印試(shi)(shi)(shi)驗(yan)(yan)數據。
試驗時間的一(yi)行顯(xian)示末端(duan),會顯(xian)示[一(yi)段]或(huo)[二(er)段]或(huo)[三段]字(zi)樣,表示當前(qian)正在進行的加壓(ya)試驗是(shi)預置(zhi)的一(yi)段,二(er)段或(huo)三段.
手動(dong)試(shi)(shi)驗模式的(de)(de)操(cao)作:選中手動(dong)試(shi)(shi)驗模式后觸按確定鈕(niu),進(jin)入(ru)正在試(shi)(shi)驗菜單項(xiang);手動(dong)按調(diao)(diao)頻(pin)(pin)鈕(niu),對應的(de)(de)光標隨(sui)之改(gai)變到輸出(chu)頻(pin)(pin)率(lv)(lv)項(xiang),可以(yi)通(tong)過(guo)上(shang)下左右鍵改(gai)變頻(pin)(pin)率(lv)(lv)大小使其(qi)試(shi)(shi)驗電壓(ya)逐(zhu)步升(sheng)(sheng)高,當升(sheng)(sheng)到*高電壓(ya)時,繼續向上(shang)或向下調(diao)(diao)整頻(pin)(pin)率(lv)(lv)按鈕(niu),直至試(shi)(shi)驗電壓(ya)開始下降(jiang);這時反調(diao)(diao)頻(pin)(pin)率(lv)(lv),試(shi)(shi)驗電壓(ya)又逐(zhu)步回升(sheng)(sheng),上(shang)下回調(diao)(diao)頻(pin)(pin)率(lv)(lv),從頻(pin)(pin)率(lv)(lv)的(de)(de)高位到低(di)位逐(zhu)位調(diao)(diao)整*高電壓(ya)值時的(de)(de)頻(pin)(pin)率(lv)(lv)就(jiu)是當前的(de)(de)諧(xie)振頻(pin)(pin)率(lv)(lv)。
找(zhao)到諧振點后,手(shou)動按電(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)鈕,光(guang)標(biao)到了輸出功(gong)率(lv),隨之按上下鍵增(zeng)加(jia)輸出功(gong)率(lv),試(shi)驗(yan)(yan)電(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)也逐(zhu)步(bu)升(sheng)高,當升(sheng)到試(shi)驗(yan)(yan)電(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)設(she)定電(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)值時,裝置停止加(jia)壓(ya)(ya)(ya)(ya)(ya)(ya),并(bing)有屏幕顯示提示和聲音(yin)提示;自動進入正在(zai)加(jia)壓(ya)(ya)(ya)(ya)(ya)(ya)試(shi)驗(yan)(yan)菜單(dan)項,并(bing)自動記錄試(shi)驗(yan)(yan)的加(jia)壓(ya)(ya)(ya)(ya)(ya)(ya)時間,當到達加(jia)壓(ya)(ya)(ya)(ya)(ya)(ya)時間設(she)定時間時,設(she)備逐(zhu)步(bu)降壓(ya)(ya)(ya)(ya)(ya)(ya)退出試(shi)驗(yan)(yan),完成本次試(shi)驗(yan)(yan),進入試(shi)驗(yan)(yan)結束菜單(dan)項。
注(zhu)意:在(zai)調(diao)(diao)(diao)節(jie)頻率(lv)調(diao)(diao)(diao)整(zheng)鈕(niu)(niu)的(de)(de)過程(cheng)中,觸按(an)左(zuo)右鈕(niu)(niu),可以(yi)改變(bian)頻率(lv)調(diao)(diao)(diao)節(jie)的(de)(de)速(su)度(du)實(shi)現(xian)粗細調(diao)(diao)(diao)的(de)(de)切(qie)換(huan)。在(zai)調(diao)(diao)(diao)節(jie)電(dian)壓調(diao)(diao)(diao)整(zheng)鈕(niu)(niu)的(de)(de)過程(cheng)中,向下觸按(an)左(zuo)右鈕(niu)(niu),可以(yi)改變(bian)電(dian)壓的(de)(de)升(sheng)降的(de)(de)速(su)度(du)實(shi)現(xian)粗細調(diao)(diao)(diao)的(de)(de)切(qie)換(huan)。觸按(an)調(diao)(diao)(diao)頻、調(diao)(diao)(diao)壓鈕(niu)(niu),實(shi)現(xian)調(diao)(diao)(diao)頻與調(diao)(diao)(diao)壓間的(de)(de)切(qie)換(huan)。
7、進入(ru)試驗記錄(lu)查詢菜單項,查詢以往和當前試驗數(shu)據。選(xuan)擇(ze)上下鍵翻看前一組數(shu)據后一組數(shu)據;選(xuan)擇(ze)左右鍵可選(xuan)擇(ze)打印(yin)或刪(shan)除當前頁的(de)內容。
125/456為試驗數據(ju)庫指(zhi)針,分子是試驗數據(ju)的在數據(ju)庫的順序(xu)數,分母是當前的數據(ju)總數,*多可儲存999組試驗數據(ju)。
8、裝置和試(shi)驗狀態菜單(dan)提示(shi):設(she)(she)(she)備的(de)使用和升壓和耐(nai)壓試(shi)驗過(guo)程中,如(ru)果出現影響試(shi)驗設(she)(she)(she)備、被試(shi)驗設(she)(she)(she)備以及操(cao)作人(ren)的(de)**情況,設(she)(she)(she)備可能出現自動保護轉臺(tai),并在屏幕有相應(ying)的(de)提示(shi)。
不能諧振:如果諧振點(dian)(dian)不在諧振頻(pin)率設置(zhi)的(de)范圍內;系統連線不正確等現(xian)象,裝置(zhi)將找(zhao)不到諧振點(dian)(dian),這時裝置(zhi)和試驗狀(zhuang)態菜(cai)單中的(de)不能諧振項(xiang)被反白(bai)并(bing)閃爍。
輸(shu)(shu)(shu)出保(bao)(bao)護(hu):如果裝置的(de)電源輸(shu)(shu)(shu)出電流大(da)于輸(shu)(shu)(shu)出保(bao)(bao)護(hu)設定的(de)電流值,裝置自動保(bao)(bao)護(hu),這時裝置和試驗狀態菜單中的(de)輸(shu)(shu)(shu)出保(bao)(bao)護(hu)項被反(fan)白(bai)并閃爍。
試(shi)驗中(zhong)止(zhi):如果在(zai)試(shi)驗升壓(ya)或加壓(ya)過程出(chu)現(xian)閃絡現(xian)象,裝置自動保護,這時裝置和試(shi)驗狀態(tai)菜單中(zhong)的輸出(chu)保護項被反白并閃爍。
9、試驗幫助內容包括五大(da)項分別(bie)為(wei):1.版本信(xin)息(xi)2.接線示意3.使用說明(ming)4.常見問題(ti)5.參(can)考資料(liao).如常見問題(ti)FAQ分五幅畫(hua)面顯示、各種(zhong)被試品電(dian)(dian)力電(dian)(dian)纜、變(bian)壓器、發電(dian)(dian)機(ji)電(dian)(dian)容參(can)數的查詢:
接線示意圖:
10、設備(bei)出(chu)廠(chang)(chang)(chang)參(can)數設置是生產(chan)廠(chang)(chang)(chang)家的出(chu)廠(chang)(chang)(chang)設置參(can)術和(he)校驗(yan)參(can)數,不適當的設置和(he)修改(gai)會(hui)影(ying)響設備(bei)性能和(he)高壓試驗(yan)的**性,未經廠(chang)(chang)(chang)家授(shou)權密(mi)碼,無(wu)法修改(gai)。
警告:正常試驗(yan)狀態下,按返回鍵(jian)即可中止(zhi)試驗(yan)。中止(zhi)或結束試驗(yan)后,應分離刀閘(zha)切(qie)斷電源。在升(sheng)壓(ya)或加壓(ya)過程中,非緊急情況(kuang),不(bu)要按下急停鍵(jian)。
六、本(ben)說明書的(de)專屬名詞的(de)定義(yi)
自動(dong)試驗:高(gao)壓試驗全過程(cheng)由主機(ji)按程(cheng)序和(he)預置參數自動(dong)完成(cheng)。
自動(dong)調諧:調諧由主(zhu)機按程序(xu)自動(dong)完成,升壓手動(dong)完成。
手動試(shi)驗:尋找諧振點和升壓均為(wei)手動,通過面板旋鈕完(wan)成。
系統參(can)數設置是(shi)指對設備部件參(can)數的設置。
試(shi)驗參數(shu)(shu)設(she)置是指對試(shi)驗過程參數(shu)(shu)的設(she)置。
試(shi)驗模式選(xuan)擇是(shi)指對試(shi)驗模式的選(xuan)擇。
試(shi)驗結果查詢是指(zhi)對試(shi)驗數據的查詢。
分(fen)壓器(qi)變比(bi)是指對(dui)分(fen)壓器(qi)的分(fen)壓比(bi)設置。
電(dian)抗器(qi)電(dian)感是指對電(dian)抗器(qi)電(dian)抗值的設置。
激勵變(bian)(bian)變(bian)(bian)比是指對勵磁變(bian)(bian)壓器的變(bian)(bian)比設(she)置。
設置電(dian)壓是(shi)高壓試驗時的保護電(dian)壓設置。
試(shi)驗電(dian)壓(ya)(ya)是高壓(ya)(ya)試(shi)驗時的試(shi)驗電(dian)壓(ya)(ya)。
加壓時(shi)間是施加試驗電壓的時(shi)間。
激勵強度是指主機(ji)電源輸出(chu)的大(da)小(xiao)。
輸出(chu)電(dian)流(liu)是主機電(dian)源的輸出(chu)電(dian)流(liu)。
頻率范圍是試驗的頻率范圍。
自動試驗模式(shi)是(shi)指試驗過程全部自動完成。
自動(dong)調(diao)諧模(mo)式是指自動(dong)尋找諧振點(dian)后,手動(dong)加壓完(wan)成試(shi)驗。
手(shou)動試驗模式(shi)全(quan)部由人(ren)工完成試驗過程。
未接(jie)地線(xian)主(zhu)機電源為接(jie)地。
不能(neng)諧(xie)振未(wei)能(neng)找到諧(xie)振點。
輸出(chu)保護主(zhu)機(ji)電源輸出(chu)電流大于整(zheng)定電流。
試驗中(zhong)止指在升壓或加壓過(guo)程裝置自動(dong)保護。
設(she)備(bei)出廠參(can)(can)數設(she)置是廠家對設(she)備(bei)有關參(can)(can)數的設(she)置。
確(que)認鍵:確(que)認當前操(cao)作。
返回鍵:返回上**菜(cai)單。
七、變頻(pin)電(dian)源技術參數:
1.額定輸出(chu)容量:15kvA;
2.儀器電源:220v±10% 50Hz;
功率電源:380v±10% 50Hz;
3.額定輸入電流:39.5A;
4.額定輸(shu)出電(dian)(dian)壓:0-340v可調、單相、輸(shu)出電(dian)(dian)壓不穩定度(du)0.05%;
5.額定輸出(chu)電(dian)流:44A;
6.頻(pin)率調節范圍:25~320Hz;
7.額定(ding)容量下連續(xu)運(yun)行為(wei)規定(ding)工作時間下*高溫升≤60K;
8.顯示以下參數:
a.經變頻(pin)輸出的(de)頻(pin)率、電(dian)壓、電(dian)流;
b.過壓(ya)(ya)保(bao)護(hu)電壓(ya)(ya)值,并可任(ren)意整定,當成套裝置(zhi)的輸出(chu)電壓(ya)(ya)值達到保(bao)護(hu)整定時,可自動切除成套裝置(zhi);
c.過(guo)流(liu)保護:當調(diao)頻電源的(de)輸出電流(liu)達到保護整定值時(shi),可(ke)自動切(qie)除成套裝置;
d.擊穿保護:當高壓側發生對地閃絡(luo)時,可(ke)自動切除成(cheng)套(tao)裝(zhuang)置,裝(zhuang)置帶有隔離裝(zhuang)置,可(ke)確保設備和人身不受(shou)損害;
e.具有全(quan)電(dian)壓(ya)輸出保護,在調壓(ya)過程(cheng)中(zhong),一旦調壓(ya)失(shi)控,調頻電(dian)源立即(ji)閉鎖(suo);
9.可(ke)實現以下操(cao)作:
a.頻率的調節,上(shang)升和下降頻率調節分粗調和細調兩(liang)種,并可自動尋找(zhao)試驗諧振點(dian),保證諧振頻率在整(zheng)個試驗過程(cheng)中不發(fa)生漂(piao)移(yi);
b.帶有設(she)(she)(she)置(zhi)電壓(ya)、設(she)(she)(she)置(zhi)時(shi)間(jian),電壓(ya)自動上升(sheng)到設(she)(she)(she)置(zhi)值(zhi)而停止并自動計時(shi);
c.帶有(you)各(ge)種(zhong)保護功能(neng)的整定按鈕(niu),可在面板上對各(ge)種(zhong)保護值進行整定;
d.帶有手動(dong)試驗功(gong)能和自(zi)動(dong)試驗功(gong)能;
e.帶(dai)有試驗(yan)數(shu)據打印功能。
八、勵磁變壓器技術(shu)參數:
1.結構(gou)形式:干(gan)式;
2.額定(ding)容量:15kVA;
3.輸入電壓:0~340V;
4.輸出電(dian)壓:四組并聯(lian)3.75KV;四組串聯(lian)15KV;二串二并7.5KV;
5.輸出(chu)電流:四組并(bing)(bing)聯4A;四組串聯1A;二(er)串二(er)并(bing)(bing)2A;
6.工作(zuo)頻率范圍:30~300Hz;
勵(li)磁變壓器的接線端子,如圖(tu)所示:
1.輸(shu)出端(duan)尾—與接地(di)端(duan)連接。
2.輸出端頭—與電抗(kang)器連接。
3.接地(di)端—與變(bian)頻電源、分壓器及(ji)被試品共同接地(di)。
4.輸入端—接調頻(pin)電源(yuan)功率輸出端。
九、諧振(zhen)電抗器技術參數:
額定(ding)容量:55KVA;
額定電壓:55kV;
額定(ding)電流:1.5A;
電(dian) 感 量:160H;
品質因(yin)數(shu):Q≥30
采用環氧(yang)干(gan)式。
7.接線端(duan)了如圖所示(shi):
a.高壓側(ce)接(jie)線端子—與被試品高壓端連接(jie)。
b.低壓側接線端子—與(yu)勵磁變輸出端連接。
c.多臺電抗器串(chuan)聯時上(shang)節(jie)的(de)低壓(ya)側與下(xia)節(jie)高壓(ya)側連接(jie)。諧振電抗器采(cai)用多臺串(chuan)聯或并聯的(de)連接(jie)方(fang)式。
8.額定容量下(xia)連續運(yun)行(xing)為規定工(gong)作時(shi)間下(xia),電(dian)抗(kang)器(qi)對空(kong)氣的溫升不大于60K;
9.性能(neng)及特點:電(dian)抗器設計(ji)干式、環(huan)氧(yang)澆鑄,電(dian)抗器可以自由方(fang)便疊裝(zhuang)。環(huan)氧(yang)樹脂絕緣筒外(wai)殼,具(ju)有(you)足夠(gou)的電(dian)氣(qi)、機械強(qiang)度,必要(yao)的散熱(re)能(neng)力以及油(you)熱(re)脹冷(leng)縮(suo)的裕度。外(wai)殼上下蓋板,顏色為(wei)橘紅色。
十、電容分(fen)壓(ya)器(qi)技術參數:
額定(ding)電(dian)壓:200kV;
工作(zuo)頻率:30~300Hz;
分壓比:2000:1;
分壓(ya)比誤差:1%;
電容分(fen)壓器接線端子如圖所示(shi):
高(gao)壓端—與電抗器高(gao)壓側(ce)及被試品高(gao)壓側(ce)相連。
測量插座(zuo)—采用專配的測量電纜與控(kong)制箱背(bei)板(ban)測量輸入端連接。
接地端—采用專配接地線(xian)按接線(xian)圖指示接地。
4.性能及特點(dian):
a.額定電(dian)壓下(xia)可(ke)連(lian)續運行2小時(shi)。
b.在(zai)30~300Hz范圍內,其(qi)精(jing)度和穩定度保持不變。
c.在(zai)20℃溫度下電容分壓器介質損耗值≤0.0025
d.電(dian)容分壓(ya)器(qi)配有(you)支撐底架,具有(you)足夠的(de)穩定性。
e.電壓測量通過專(zhuan)用測試引線引至調頻電源進行測量。
試驗接線圖(tu):
110kv主(zhu)變、GIS試驗接(jie)線
35kv電纜試驗接線圖(tu)
10kv電纜試(shi)驗接線(xian)圖(tu)
十二、設備(bei)保存(cun)和維(wei)護(hu)
1、存(cun)放于干(gan)燥、清潔場地,防止(zhi)雨水(shui)、灰塵進入部(bu)件(jian)內部(bu);
2、如若長期不使用,正常天氣至少2個(ge)月應通電(dian)(dian)一(yi)次(ci)時(shi)間(jian)不少于(yu)半(ban)小(xiao)時(shi),雨季及潮濕(shi)期應每隔一(yi)個(ge)月通電(dian)(dian)一(yi)次(ci),通電(dian)(dian)時(shi)間(jian)半(ban)小(xiao)時(shi),以(yi)驅(qu)除設備內(nei)的潮氣防止電(dian)(dian)子元器件的銹(xiu)蝕(shi),影響正常使用。
3、定期(qi)檢查裝置各(ge)部件(jian),確保各(ge)接(jie)頭緊固無松動;
4、更(geng)換(huan)打印(yin)紙(zhi),機器(qi)采用熱(re)敏打印(yin)紙(zhi)并且是前換(huan)紙(zhi)式當需要換(huan)紙(zhi)時只要按POST鍵鈕打印(yin)紙(zhi)艙門就會打開可以將(jiang)新打印(yin)紙(zhi)裝入(ru);
十三、常(chang)見(jian)故障排除
故障(zhang)現(xian)象
|
發 生 原(yuan) 因(yin)
|
排 除 方 法
|
找(zhao)不(bu)到諧振點(dian)
|
接線(xian)有誤。
輸出開關(guan)未開,;
3、做GIS時PT二次回路未打開;
4、試品Q值太(tai)低;
5、起始激勵功(gong)率太低(di);
6、試(shi)驗(yan)回(hui)路有短路現象(xiang);
7、找(zhao)頻范圍(wei)不對(dui)。
|
退出(chu)試驗狀態,合上輸出(chu)開關(guan),檢查接(jie)線;打開PT二次回(hui)路;
調高起(qi)始功率(lv)(∠30%);
用兆(zhao)歐表測量(liang)試品絕緣
重新設置找(zhao)頻范圍
|
諧振后,電壓升不上去
|
1、試(shi)品Q值太低(di);
2、激勵電壓不夠;
3、電(dian)抗器底部有鐵磁物體(ti);
4、3次諧(xie)波諧(xie)振。
|
檢查(cha)試品;
改變(bian)激勵(li)變(bian)壓器繞組接法,提高勵(li)磁電壓
絕緣筒架高(gao)電抗器或離(li)開鐵磁物體(ti)。
|
主機自動復位
|
供(gong)電(dian)電(dian)源容量不夠;
電源引線過(guo)長或線徑過(guo)小;
接(jie)頭處接(jie)觸**;
供電電壓(ya)波動;
按鍵死接觸。
|
增加供電(dian)(dian)電(dian)(dian)源容量;
換較(jiao)粗(cu)導(dao)線,減小(xiao)導(dao)線長(chang)度;
檢查接頭;
減(jian)小供電(dian)電(dian)壓波動。
|
開機(ji)后線路跳閘
|
線(xian)路漏(lou)電保護器較為敏(min)感;
空氣開關容量不夠。
|
跨過漏電保護器或空(kong)氣開關的接線;
改換較大容量的空氣開關。
|
電壓跌(die)落
|
試品(pin)放電(dian)或擊穿
|
檢查試品(pin)
|
輸出(chu)短(duan)路
|
電流超過本(ben)機限流值(zhi)。
|
檢查接線和(he)試品。
|
試品電壓不準(zhun)
|
分壓(ya)比(bi)設置錯誤或分壓(ya)器(qi)信號(hao)傳輸(shu)有問題(ti)。
|
重設(she)分壓比(bi)或檢查分壓器接線。
|
電壓(ya)閃變
|
試驗電壓劇烈波動,變化率(lv)超過本機限定值。
|
檢查供電電源電壓穩定性或試品參數的變化(hua)。
|
回路(lu)無(wu)電流(liu)
|
|
檢查接線和試(shi)品。
|
未接好(hao)地線
|
|
檢查接(jie)地(di)(di)線(xian)和地(di)(di)樁(zhuang),按說明書要求(qiu)連接(jie)。
|
試品過電壓
|
手動升壓太快或(huo)失(shi)控。
|
改變調(diao)壓(ya)步(bu)距或(huo)改用(yong)自(zi)動(dong)升壓(ya) 。
|
系統不諧振
|
接(jie)線有誤或試品Q值太低。
|
檢查接(jie)線和試品
|
十四、常(chang)用設(she)備資料參考
交聯聚乙(yi)烯(xi)電纜單位長(chang)度電容量(liang)
電纜(lan)導體(ti)截面(mian)積(平方毫米)
|
電 容(rong) (μ/km)
|
YJV、YJLV
|
YJV、YJLV
|
YJV、YJV、YJLV
|
YJV、YJLV
|
YJV、YJLV
|
6/6kV、6/10kV
|
8.7/10kV、8.7/15kV
|
12/35kV
|
21/35kV
|
26/35kV
|
1×35
|
0.212
|
0.173
|
0.152
|
|
|
1×50
|
0.237
|
0.192
|
0.166
|
0.118
|
0.114
|
1×70
|
0.270
|
0.217
|
0.187
|
0.131
|
0.125
|
1×95
|
0.301
|
0.240
|
0.206
|
0.143
|
0.135
|
1×120
|
0.327
|
0.261
|
0.223
|
0.153
|
0.143
|
1×150
|
0.358
|
0.284
|
0.241
|
0.164
|
0.153
|
1×185
|
0.388
|
0.307
|
0.267
|
0.180
|
0.163
|
1×240
|
0.430
|
0.339
|
0.291
|
0.194
|
0.176
|
1×300
|
0.472
|
0.370
|
0.319
|
0.211
|
0.190
|
1×400
|
0.531
|
0.418
|
0.352
|
0.231
|
0.209
|
1×500
|
0.603
|
0.438
|
0.388
|
0.254
|
0.232
|
1×600
|
0.667
|
0.470
|
0.416
|
0.287
|
0.256
|
2、交(jiao)聯聚(ju)乙烯電(dian)纜(lan)單(dan)位長度電(dian)容量
電(dian)纜導體截面積(平方毫米)
|
電(dian) 容 (μF/km)
|
YJV、YJLV
|
YJV、YJLV
|
YJV、YJV、YJLV
|
YJV、YJLV
|
YJV、YJLV
|
6/6kV、6/10kV
|
8.7/10kV、8.7/15kV
|
12/35kV
|
21/35kV
|
26/35kV
|
3×35
|
0.212
|
0.173
|
0.152
|
|
|
3×50
|
0.237
|
0.192
|
0.166
|
0.118
|
0.114
|
3×70
|
0.270
|
0.217
|
0.187
|
0.131
|
0.125
|
3×95
|
0.301
|
0.240
|
0.206
|
0.143
|
0.135
|
3×120
|
0.327
|
0.261
|
0.223
|
0.153
|
0.143
|
3×150
|
0.358
|
0.284
|
0.241
|
0.164
|
0.153
|
3×185
|
0.388
|
0.307
|
0.267
|
0.180
|
0.163
|
3×240
|
0.430
|
0.339
|
0.291
|
0.194
|
0.176
|
3×300
|
0.472
|
0.370
|
0.319
|
0.211
|
0.190
|
3×400
|
0.531
|
0.418
|
0.352
|
0.231
|
0.209
|
3×500
|
0.603
|
0.438
|
0.388
|
0.254
|
0.232
|
3×600
|
0.667
|
0.470
|
0.416
|
0.287
|
0.256
|
3、交聯聚乙烯電(dian)纜(lan)單位長度電(dian)容量
電纜導體截面(mian)積(平(ping)方毫米(mi))
|
電 容 (μF/km)
|
YJV、YJLV
|
YJV、YJLV
|
64/110kV
|
128/220kV
|
3×240
|
0.129
|
|
3×300
|
0.139
|
|
3×400
|
0.156
|
0.118
|
3×500
|
0.169
|
0.124
|
3×630
|
0.188
|
0.138
|
3×800
|
0.214
|
0.155
|
3×1000
|
0.231
|
0.172
|
3×1200
|
0.242
|
0.179
|
3×1400
|
0.259
|
0.190
|
3×1600
|
0.273
|
0.198
|
3×1800
|
0.284
|
0.297
|
3×2000
|
0.296
|
0.215
|
3×2200
|
|
0.221
|
3×2500
|
|
0.232
|
4、60kV級全絕緣變壓(ya)器的(de)電(dian)容(rong)(pF)
類 型
|
變 壓 器(qi) 容 量 kVA
|
630
|
2000
|
3150
|
6300
|
8000
|
1600
|
高壓-地
|
2700
|
4100
|
4600
|
5900
|
7000
|
8200
|
低壓-地(di)
|
4200
|
6600
|
7900
|
10000
|
11000
|
15300
|
對(dui)于表(biao)中(zhong)沒有(you)的產品,可根據表(biao)中(zhong)的上、下容量(liang)(liang)近似地估算。同容量(liang)(liang)的雙繞(rao)組(zu)(zu)變壓器,其(qi)繞(rao)組(zu)(zu)電容要比三繞(rao)組(zu)(zu)產品小。
5、110kV級(ji)中性點(dian)分級(ji)絕緣變壓器的電(dian)容(pF)
類 型
|
變 壓 器 容 量kVA
|
50000
|
31500
|
20000
|
10000
|
5600
|
高壓(ya)-中壓(ya)、低(di)壓(ya)、地
|
14200
|
11400
|
8700
|
6150
|
4200
|
中壓(ya)-高壓(ya)、低壓(ya)、地
|
24800
|
11800
|
13200
|
9600
|
-
|
低壓(ya)(ya)-高壓(ya)(ya)、中壓(ya)(ya)、地
|
19300
|
19300
|
12000
|
9400
|
6800
|
6、220kV級中性點非(fei)全級絕(jue)緣部分變(bian)壓器的電容(rong)(pF)
試(shi) 品 型(xing) 號
|
SEPSL-63000
|
SSPSL-120000
|
SSPSL-240000
|
類 型
|
高壓(ya)-中壓(ya)、低(di)壓(ya)及地
|
12100
|
13500
|
17050
|
中壓(ya)-高(gao)壓(ya)、低壓(ya)及地
|
18500
|
19700
|
23260
|
低壓(ya)(ya)-高壓(ya)(ya)、中壓(ya)(ya)及地
|
18200
|
23600
|
29940
|
試(shi) 品 型 號
|
SFPL-240000
|
SFP-360000
|
SFPSZL-120000
|
類 型
|
高壓(ya)-中(zhong)壓(ya)、低壓(ya)及(ji)地
|
32230
|
33910
|
38020
|
中壓(ya)-高壓(ya)、低壓(ya)及地
|
-
|
-
|
23260
|
低壓(ya)-高壓(ya)、中壓(ya)及(ji)地
|
22470
|
23790
|
22160
|
7、油浸式電(dian)力變壓器交(jiao)流試驗電(dian)壓
額定電壓
(k V)
|
*高工作
電壓(k V)
|
線端交流試驗(yan)電壓值(kV)
|
中性點交流試驗電(dian)壓(ya)值(kV)
|
全部更換(huan)繞組
|
部分(fen)更換繞組或(huo)交接
|
全(quan)部(bu)更換繞(rao)組(zu)
|
部分更換繞組(zu)或交(jiao)接
|
<1
|
≤1
|
3
|
2.5
|
3
|
2.5
|
3
|
3.5
|
18
|
15
|
18
|
15
|
6
|
6.9
|
25
|
21
|
25
|
21
|
10
|
11.5
|
35
|
30
|
35
|
30
|
15
|
17.5
|
45
|
38
|
45
|
38
|
20
|
23.0
|
55
|
47
|
55
|
47
|
35
|
40.5
|
85
|
72
|
85
|
72
|
110
|
126.0
|
200
|
170(195)
|
95
|
80
|
220
|
252.0
|
360
|
306
|
85
|
72
|
395
|
336
|
(200)
|
(170)
|
500
|
550.0
|
630
|
536
|
85
|
72
|
680
|
578
|
140
|
120
|
8、部分型號發電(dian)機(ji)定(ding)子繞組的(de)單相對(dui)地電(dian)容量
類別
|
發(fa) 電 機(ji)
|
型號
|
生產廠家
|
額定容量(MW)
|
額定電壓(kV)
|
相電容(rong)(mF)
|
火
力
發
電
機
|
QFS-125-2
|
上海電機廠
|
125
|
13.8
|
0.08-0.12
|
QFSN-200-2
|
哈爾濱電機廠
|
200
|
15.75
|
0.19-0.21
|
QFQS-200-2
|
東(dong)方電(dian)機廠
|
200
|
15.75
|
0.1928-0.21
|
QFQS-200-2
|
北京重型電機廠
|
200
|
15.75
|
0.18-0.19
|
QFS-300-2
|
上海電機廠
|
300
|
18.0
|
0.16-0.20
|
QFSN-300-2
|
上海電機(ji)廠
|
300
|
18.0
|
0.18-0.20
|
ATB-2
|
美國GE公司
|
352
|
23.0
|
0.268(設(she)計值(zhi))
|
TBB-320-2
|
(前蘇聯)
|
320
|
20.0
|
0.31
|
2-105×234
|
美國西(xi)屋公司
|
600
|
20.0
|
0.2(工(gong)廠試驗(yan)值)
|
50WT23E-138
|
ABB
|
600
|
22.0
|
0.253(設計值(zhi))
|
水 發
力 電(dian)
機
|
|
|
72.5 - 85
|
10.5
|
0.694
|
|
|
300
|
15.75
|
1.7-2.5
|
|
|
400
|
18.0
|
2-2.5
|
9、同步(bu)發電(dian)機定子繞(rao)組交流試驗電(dian)壓(ya)
1
|
全部更(geng)換定子繞(rao)組(zu)并修好后的試驗電壓
|
容量kW或kVA
|
小于(yu)10000
|
10000及以上
|
額(e)定電壓Un (V)
|
36以(yi)上(shang)
|
6000以下
|
6000~18000
|
18000以上
|
試驗電(dian)壓V
|
2Un+1000但*低為1500
|
2.5Un
|
2Un
+3000
|
按專門協議
|
2
|
大修(xiu)前(qian)或局部更(geng)換定(ding)子繞(rao)組并修(xiu)好后(hou)的試(shi)驗電壓(ya)
|
運行(xing)20年及以下者
|
1.5 Un
|
運(yun)行20年以(yi)上與架空線路(lu)直接連接者(zhe)
|
1.5 Un
|
運行20年以上(shang)不與架空線路(lu)直接(jie)連(lian)接(jie)者
|
(1.3~1.5)Un
|
十五(wu)、設備(bei)成套性:
變頻(pin)電源(yuan) 1臺
勵(li)磁變(bian)壓器 1臺
電抗器 4臺
電容分壓器 1臺
附件及測試線(xian) 1套
支架 15KV 1只(zhi)
均壓罩 200KV 2只
絕緣底板(ban) 2塊
一、產品概述(shu)
YDQC系列輕(qing)型(xing)(xing)交直流高(gao)(gao)壓(ya)試(shi)(shi)(shi)驗變(bian)壓(ya)器是在同(tong)類產品YDJ(G)型(xing)(xing)高(gao)(gao)壓(ya)試(shi)(shi)(shi)驗變(bian)壓(ya)器的基礎上,按試(shi)(shi)(shi)驗變(bian)壓(ya)器國家標(biao)準ZBK41006—89要(yao)求,經改(gai)進(jin)后生(sheng)產的一(yi)種新型(xing)(xing)產品,本系列產品具有體積小、重量輕(qing)、結構緊湊、功能齊全、使用方便等特點。實用于電力(li)、工礦、科(ke)研等部門(men),對各種高(gao)(gao)壓(ya)電氣(qi)(qi)設(she)備(bei)、電氣(qi)(qi)元件、絕(jue)緣材料進(jin)行(xing)工頻耐(nai)壓(ya)試(shi)(shi)(shi)驗和直流泄漏試(shi)(shi)(shi)驗,是高(gao)(gao)壓(ya)試(shi)(shi)(shi)驗中必不可少的儀器。
二(er)、產品結構(gou)
YDQC系列輕型高壓(ya)(ya)(ya)試(shi)驗(yan)變(bian)壓(ya)(ya)(ya)器(qi)鐵芯為(wei)單框式(shi)。線圈(quan)采用同芯圓筒多(duo)層塔(ta)式(shi)結(jie)(jie)(jie)構,初級低壓(ya)(ya)(ya)繞(rao)(rao)組(zu)繞(rao)(rao)在(zai)鐵芯上,次級高壓(ya)(ya)(ya)繞(rao)(rao)組(zu)繞(rao)(rao)在(zai)低壓(ya)(ya)(ya)繞(rao)(rao)組(zu)外(wai)側,這種同軸布置(zhi)減少(shao)了繞(rao)(rao)組(zu)間的(de)藕合(he)損耗。高壓(ya)(ya)(ya)硅堆用特殊(shu)工藝封裝在(zai)套管內,產品的(de)外(wai)殼制(zhi)成與器(qi)芯配合(he)較佳的(de)八(ba)角形(xing)結(jie)(jie)(jie)構,整體外(wai)型美觀大方。其內外(wai)部(bu)結(jie)(jie)(jie)構見圖1。
1-均(jun)壓球;2-硅(gui)堆短路桿;3-高(gao)(gao)壓套管(guan);4-油閥(fa);5-殼(ke)體;6、7-調整電(dian)壓輸入(ru)a、x端(duan)(duan)子;8、9-儀(yi)表測量(liang)E、F端(duan)(duan)子;10-高(gao)(gao)壓尾X端(duan)(duan)子;11-變(bian)壓器(qi)外殼(ke)接地端(duan)(duan);12-高(gao)(gao)壓輸出A端(duan)(duan)子;13-高(gao)(gao)壓整流硅(gui)堆;14-內部均(jun)壓環(huan);15-變(bian)壓器(qi)鐵(tie)芯(xin);16-初級(ji)低壓繞組(zu);17-測量(liang)儀(yi)表繞組(zu);18-二次級(ji)高(gao)(gao)壓繞組(zu);19-變(bian)壓器(qi)油。
三、工作原(yuan)理(li)
YDQC系(xi)列輕型高(gao)壓(ya)(ya)試(shi)驗(yan)變壓(ya)(ya)器(qi)(qi)(qi)為(wei)單相變壓(ya)(ya)器(qi)(qi)(qi),聯(lian)結組(zu)標號II。單臺高(gao)壓(ya)(ya)試(shi)驗(yan)變壓(ya)(ya)器(qi)(qi)(qi)的(de)工(gong)作過(guo)程,用交流220V(10KVA以上(shang)為(wei)380V)電壓(ya)(ya)接入電源(yuan)控制(zhi)箱(臺),經電源(yuan)控制(zhi)箱(臺)內自藕調(diao)壓(ya)(ya)器(qi)(qi)(qi)(50KVA以上(shang)調(diao)壓(ya)(ya)器(qi)(qi)(qi)外(wai)附(fu))調(diao)節0~200V(10KVA以上(shang)0~400V)電壓(ya)(ya)至試(shi)驗(yan)變壓(ya)(ya)器(qi)(qi)(qi)的(de)初級繞(rao)(rao)組(zu),根據電磁感應(ying)原理,在試(shi)驗(yan)變壓(ya)(ya)器(qi)(qi)(qi)高(gao)壓(ya)(ya)繞(rao)(rao)組(zu)可獲得試(shi)驗(yan)所需的(de)高(gao)電壓(ya)(ya)。其工(gong)作原理圖見圖2所示。
1、單(dan)臺(tai)YDQC高壓試驗變(bian)壓器工作原理(li)示意圖(tu)
在(zai)試驗變壓(ya)器(qi)中:a、x為(wei)低壓(ya)輸入端(duan);A、X 為(wei)高壓(ya)輸出端(duan);E、F為(wei)儀表測量端(duan)。
2、單臺交直流兩用型高壓試驗變壓器工作原理見圖3。圖中所示:高壓套管內裝有高壓硅堆,串接在高壓回路中作高壓整流,以獲得直流高電壓。當用一短路桿將高壓硅堆短接時,可獲得交流高電壓,其狀態為交流輸出;反之在抽出短路桿時,其狀態為直流輸出。
3、三臺高壓試驗變壓器串激獲得更高電壓原理見圖4,串激高壓試驗變壓器有很大的優越性,因為整個試驗裝置由多個單臺串激式試驗變壓器組成,單臺試驗變壓器有著體積小、重量輕、便于運輸的特點,它既可以串接成高出幾倍的單臺試驗變壓器輸出電壓組合使用,又可以分開單獨使用。整套試驗裝置投資小、經濟實惠。圖3所示:在三臺串激式試驗變壓器串激使用中,單臺試驗變壓器B1、B2、B3的輸出電壓都是U,**、二級的試驗變壓器內部都有一個激磁繞組,分別為A1、C1 和A2、C2。當控制電壓加在第**試驗變壓器B1的初級繞組a1、x1上,激磁繞組A1、C1給予試驗變壓器B2初級繞組供電,**級試驗變壓器B2的激磁繞組A2、C2給試驗變壓器B3的初級繞組供電。由于第**試驗變壓器B1的高壓尾及殼體接地,**、三級的試驗變壓器B2和B3對地有絕緣支架的隔離,這樣試驗變壓器B1、B2、B3對地輸出電壓分別為1U、2U、3U。
B1、B2、B3- 串激式(shi)高壓(ya)變壓(ya)器;1U、2U、3U-各級對地電壓(ya);
PV- 高壓(ya)示值表(KV); ZJ1、ZJ2-絕緣(yuan)支架。
四、使用方法(fa)及注意事項
1、YDQC高(gao)(gao)壓(ya)試(shi)驗(yan)(yan)(yan)變壓(ya)器(qi)做工(gong)頻(pin)耐壓(ya)試(shi)驗(yan)(yan)(yan)使用接(jie)線方法見圖(tu)5。做工(gong)頻(pin)耐壓(ya)試(shi)驗(yan)(yan)(yan)前,先根據試(shi)驗(yan)(yan)(yan)變壓(ya)器(qi)的額(e)定容量(liang)選(xuan)擇好限(xian)流(liu)電(dian)阻(zu)(zu),(水電(dian)阻(zu)(zu))的阻(zu)(zu)值,再根據被試(shi)品需加(jia)的高(gao)(gao)壓(ya)電(dian)壓(ya)值調整好放電(dian)球隙(xi)的球間距(ju),為(wei)了提(ti)高(gao)(gao)對被試(shi)品施加(jia)電(dian)壓(ya)的測量(liang)精度,應(ying)在(zai)高(gao)(gao)壓(ya)側接(jie)入(ru)FRC阻(zu)(zu)容分壓(ya)器(qi)來測量(liang)電(dian)壓(ya)。
R1、R2- 限流電阻(zu); Qx- 放電球隙(xi); Zx- 被試(shi)品(pin);
FRC- 阻容分壓器; V- 分壓器高壓表。
按照圖4、結合圖2所進行的工頻耐壓試驗接好工作線路,試驗變壓器的高壓繞阻的X端(高壓尾)、儀表測量繞組的F端、試驗變壓器的外殼以及電源控制箱(臺)的外殼必須可靠接地。
用三臺試驗變壓器串激做工頻耐壓試驗時、**、三級試驗變壓器的初級繞組X端,儀表測量繞組的F端,以及高壓繞組的X端(高壓尾)均接本級試驗變壓器的外殼,**、三級試驗變壓器的主體必須放置在絕緣支架上。除第**以外、**、三級試驗變壓器的主體不要接地線。其接線方式見圖3所示。
接電源前,電源控制箱(臺)的調壓器必須調到零位。接通電源后,綠色指示燈亮,按一下啟動按鈕,紅色指示燈亮,表示試驗變壓器已接通控制電源,開始升壓。
從零位開始按順時針方向勻速旋轉調壓器手輪升壓。(升壓方式有:快速升壓法,即20S逐級升壓法,慢速升壓法,即60S逐級升壓法,極慢速升壓法供選用)電壓從零開始按選定的升壓速度升到您所需額定試驗電壓的75%后,再以每秒2%額定試驗電壓的速度升到您所需試驗電壓,并密切注意測量儀表的指示以及被試品的情況,被試品施加電壓的時間到后。應在數秒內勻速將調壓器返回,高壓降至1/3試驗電壓以下,按一下停止按鈕,高壓、低壓輸出停止,然后切斷電源線,試驗完畢。
工(gong)頻(pin)耐壓(ya)試驗(yan)操作(zuo)過程(cheng)注(zhu)意事項
1、試驗人員應做好責任分工,設定好試驗現場的**距離,仔細檢查好被試品及試驗變壓器的接地情況,并設有專人監護**及觀察被試品狀態工作。
2、被試品主要部位應**干凈,保持**干燥,以免損壞被試品和帶來試驗數值的誤差。
3、對大型設備的試驗,一般都應先進行試驗變壓器的空升試驗,即不接試品時升壓至試驗電壓,以便校對好儀表的指示精度,調整好放電球隙的球間距。
4、做耐壓試驗時升壓速度不能過快,并防止突然加壓,例如調壓器不在零位的突然合閘,也不能突然斷電,一般應在調壓器降至零位時分閘。
5、在升壓或耐壓試驗過程中,如發現下列不正常情況,1 電壓、電流表指針擺動很大,2 被試品發出不正常響聲,3 發現絕緣有燒焦或冒煙現象,應立即降壓,切斷電源,停止試驗并查明原因。
6、使用本產品做高壓試驗時,除熟悉本說明書外,還必須嚴格執行國家有關標準和操作規程。
2、YDQ交(jiao)直流(liu)兩用高壓(ya)(ya)試(shi)(shi)驗(yan)變壓(ya)(ya)器(qi)做直流(liu)耐壓(ya)(ya)和泄(xie)漏(lou)試(shi)(shi)驗(yan)使(shi)用接線方(fang)法見圖5。由于是(shi)交(jiao)直流(liu)兩用高壓(ya)(ya)試(shi)(shi)驗(yan)變壓(ya)(ya)器(qi),應把高壓(ya)(ya)硅堆(dui)短路桿從套管(guan)中抽出(chu),使(shi)試(shi)(shi)驗(yan)變壓(ya)(ya)器(qi)為(wei)(wei)直流(liu)輸出(chu)狀態(tai)。做直流(liu)泄(xie)漏(lou)試(shi)(shi)驗(yan)前,先根(gen)據(ju)泄(xie)漏(lou)試(shi)(shi)驗(yan)中輸出(chu)端斷路電流(liu)不超(chao)過(guo)高壓(ya)(ya)硅堆(dui)的(de)*大(da)整流(liu)為(wei)(wei)宜,選(xuan)擇好限流(liu)電阻(zu)(水電阻(zu))的(de)阻(zu)值(zhi)(zhi),再根(gen)據(ju)被試(shi)(shi)品對(dui)直流(liu)高壓(ya)(ya)波形的(de)要求(qiu)選(xuan)擇好高壓(ya)(ya)濾波電容的(de)電容值(zhi)(zhi)。為(wei)(wei)了提高對(dui)被試(shi)(shi)品施加(jia)電壓(ya)(ya)的(de)測量精(jing)度(du),應在(zai)高壓(ya)(ya)側接入FRC阻(zu)容分壓(ya)(ya)器(qi)來測量電壓(ya)(ya)。
R- 限流電阻; C- 高壓濾波電容(rong); Zx- 被試品; G- 硅(gui)堆短路桿;
FRC- 阻容分壓器;V- 分壓器高壓表;uA- 微安表;D- 高壓整流硅堆。
按照圖5、結合圖3所進行的直流泄漏試驗接好工作線路。試驗變壓器的高壓繞組的X端(高壓尾)、儀表測量繞組的F 端、試驗變壓器的外殼以及電源控制箱(臺)的外殼必須可靠接地。
接電源(yuan)前、電源(yuan)控制(zhi)箱(臺(tai))的調(diao)壓(ya)器必(bi)須調(diao)到零(ling)位(wei)。接通電源(yuan)后,綠色(se)指示燈(deng)亮(liang),按一下啟動按鈕,紅色(se)指示燈(deng)亮(liang),表(biao)示試驗變壓(ya)器已接通控制(zhi)電源(yuan),開始升(sheng)壓(ya)。
從(cong)零位(wei)(wei)開始按(an)順時針方向勻速(su)(su)旋(xuan)轉調壓(ya)(ya)器手輪升(sheng)壓(ya)(ya)。(升(sheng)壓(ya)(ya)方式(shi)有:快速(su)(su)升(sheng)壓(ya)(ya)法(fa)即20S逐級升(sheng)壓(ya)(ya)法(fa);慢速(su)(su)升(sheng)壓(ya)(ya)法(fa),即60S逐級升(sheng)壓(ya)(ya)法(fa);級慢速(su)(su)升(sheng)壓(ya)(ya)法(fa)供選用(yong))電(dian)壓(ya)(ya)從(cong)零開始按(an)選定(ding)的(de)升(sheng)壓(ya)(ya)速(su)(su)度升(sheng)到您所(suo)需(xu)額定(ding)試(shi)驗電(dian)壓(ya)(ya)或額定(ding)直(zhi)流(liu)(liu)電(dian)流(liu)(liu)下的(de)參考電(dian)壓(ya)(ya)。試(shi)驗中應(ying)嚴(yan)密注意(yi)直(zhi)流(liu)(liu)高(gao)壓(ya)(ya)表(biao)、泄漏電(dian)流(liu)(liu)表(biao)指示以(yi)及被(bei)試(shi)品的(de)情況。試(shi)驗完(wan)畢后,應(ying)訊速(su)(su)均勻將高(gao)壓(ya)(ya)降(jiang)至零位(wei)(wei),按(an)一下停止(zhi)按(an)鈕,高(gao)壓(ya)(ya)、低壓(ya)(ya)輸出(chu)停止(zhi),然后切斷電(dian)源。此時應(ying)用(yong)直(zhi)流(liu)(liu)高(gao)壓(ya)(ya)放**給被(bei)試(shi)品及試(shi)驗裝置本身充(chong)分(fen)放電(dian)。
直(zhi)流泄漏試驗(yan)操作過程注(zhu)意事項(xiang)
(1)試驗人員應做好責任分工,設定好試驗現場的**距離,仔細檢查好被試品及試驗變壓器的接地情況,并設有專人監護**及觀察被試品狀態工作。
(2)被試品做試驗前,應拆除所有對外連線,并充分放電,主要部位應**干凈,保持**干燥,以免損壞被試品及帶來試驗數值的誤差。
(3)對于大容量試品(電容器、超長電纜等)試驗時應緩慢升壓,防止被試品的充電電流過大而燒壞微安表,必要時應分級加壓分別讀取各電壓下微安表的穩定讀數。
(4)試驗過程中,應嚴密監視被試品、微安表及試驗裝置等,一旦發生閃爍、擊穿等現象應立即降壓,切斷電源,并查明原因。
五(wu)、配套選購產品(pin)
下列產品僅供選擇,購買時需另行計價。
1.KZX系列電源控制箱 容量:1KVA-5KVA、輸入電壓:220V
2.KZT系列電源控制臺 容量:10KVA~300KVA輸入電壓:220V或380V
3.數字微安表:SWB-II
4.高壓濾波電容: 0.01MF、40 ~ 100KV
5.高壓直流放**: FBR— 70、140、210KV
6.放電球隙: Q—50、100、150、200、250、500
7.標準試油杯: 400ml
8.折疊式手推車: 150、300型
9.絕緣支架: 50、100、200、300、400KV
10.阻容分壓器: FRC —50、100、150、200KV
11.高壓硅堆: 2DL—150、300、450KV
12.水 電 阻: 50、100
六、主要(yao)試驗設(she)備的選擇
1、試驗變壓器
其高壓側額定電壓應不小于被試品的*高試驗電壓,額定電流不小于被試品的*大電容電流。被試品的電容電流和試驗變壓器所需容量計算式為:
被(bei)試品(pin)電容量Cx可由交流(liu)電橋測出(chu)。常用的被(bei)試品(pin)電容量按表1選取(qu)。
幾種常用被(bei)試(shi)品的電容量(pF) 表1
2、調壓設備
(1)自藕調壓器。其調壓范圍廣、功率損耗小、波形畸變小、選擇這種調壓方式為*好。自藕調壓器的容量按0.75 ~ 1倍的試驗變壓器的容量選擇,適用于容量為100KVA以下的試驗變壓器的調壓。
(2)感應調壓器。其調壓范圍大,波形畸形小、但結構復雜、價格較貴,當試驗變壓器的容量較大時(如100KVA以上)使用。
3、限流電阻
限流電阻的作用是,當被試品擊穿時,限制斷路電流,從而保護試驗變壓器,防止故障的擴大。其數值以*高試驗電壓為準,按0.5 ~ 1 Ω / V(有效值)選擇,限流電阻可用水電阻。注意水不能充滿玻璃管,應留有余地,以防爆裂。
4、放電球隙
放電球隙的布置方式有垂直和水平兩種,球隙間距S和球的直徑D的關系應保護在0.05D ≤S ≤0.5D范圍內,球隙上的水電阻阻值一般按0.1 ~ 1Ω/V選取,設置放電球隙的目的是為了對重要的被試品起保護作用,可以將由于誤操作或被試品擊穿引起的過電壓限制在允許的范圍內。
七、試驗變壓(ya)器技術(shu)指(zhi)示(shi)
型號
|
容(rong)量
|
高壓(ya)電壓(ya)
|
高壓電流
|
低壓輸入
|
變(bian)比
|
溫升℃
|
(KVA)
|
(KV)
|
(mA)
|
電壓(V)
|
電流(A)
|
高(gao)/儀
|
30分鐘
|
YDQC-1.5/50
|
1.5
|
50
|
30
|
200
|
7.5
|
500
|
10
|
YDQC-3/50
|
3
|
50
|
60
|
200
|
15
|
500
|
10
|
YDQC-5/50
|
5
|
50
|
100
|
200
|
25
|
500
|
10
|
YDQC-10/50
|
10
|
50
|
200
|
200
|
50
|
500
|
10
|
YDQC-15/50
|
15
|
50
|
300
|
200
|
75
|
500
|
10
|
YDQC-20/50
|
20
|
50
|
400
|
380
|
53
|
500
|
10
|
YDQC-30/50
|
30
|
50
|
600
|
380
|
79
|
500
|
10
|
YDQC-50/50
|
50
|
50
|
1000
|
380
|
12
|
500
|
10
|
YDQC-5/100
|
5
|
100
|
50
|
200
|
25
|
1000
|
10
|
YDQC-10/100
|
10
|
100
|
100
|
200
|
50
|
1000
|
10
|
YDQC-20/100
|
20
|
100
|
200
|
400
|
50
|
1000
|
10
|
YDQC-30/100
|
30
|
100
|
300
|
400
|
75
|
1000
|
10
|
YDQC-50/100
|
50
|
100
|
500
|
400
|
125
|
1000
|
10
|
YDQC-20/150
|
20
|
150
|
133
|
400
|
50
|
1500
|
10
|
YDQC-30/150
|
30
|
150
|
200
|
400
|
75
|
1500
|
10
|
YDQC-50/150
|
50
|
150
|
333
|
400
|
125
|
1500
|
10
|
YDQC-100/150
|
100
|
150
|
667
|
400
|
250
|
1500
|
10
|
YDQC-50/200
|
50
|
200
|
250
|
400
|
125
|
2000
|
10
|
YDQC-100/200
|
100
|
200
|
500
|
400
|
250
|
2000
|
10
|
YDQC-150/200
|
150
|
200
|
750
|
400
|
375
|
2000
|
10
|
YDQC-200/200
|
200
|
200
|
1000
|
400
|
500
|
2000
|
10
|
YDQC-300/200
|
300
|
200
|
1500
|
400
|
600
|
2000
|
10
|
YDQC-50/300
|
50
|
300
|
170
|
400
|
125
|
3000
|
10
|
YDQC-100/300
|
100
|
300
|
333
|
400
|
250
|
3000
|
10
|
YDQC-150/300
|
150
|
300
|
500
|
400
|
375
|
3000
|
10
|
YDQC-200/300
|
200
|
300
|
667
|
400
|
500
|
3000
|
10
|
YDQC-300/300
|
300
|
300
|
3000
|
500
|
600
|
3000
|
10
|
1、使用環境條件
環境溫度不高于+40℃、不低于—20℃;空氣相對濕度不大于90%;海拔高度不超過2000米;
2、工作電壓
電源控制箱(臺)輸入電壓為工頻220V或380V、相對誤差不超過±10%;(具體使用電壓根據用戶所定試驗變壓器規格選取)
八、隨貨文件
YDQC 系列試驗變壓器產品說明書 1份
產品出廠試驗報告 1份
產品合格證 1份
裝箱單 1份
一(yi)、概述
YDQ系列高(gao)壓(ya)試(shi)驗(yan)變(bian)(bian)(bian)壓(ya)器(qi)是(shi)根據《試(shi)驗(yan)變(bian)(bian)(bian)壓(ya)器(qi)》標(biao)準,在油浸式(shi)(shi)試(shi)驗(yan)變(bian)(bian)(bian)壓(ya)器(qi)的(de)(de)(de)(de)(de)(de)(de)基礎上而設計(ji)生(sheng)產(chan)的(de)(de)(de)(de)(de)(de)(de)。SF6氣(qi)(qi)體(ti)具有良(liang)好的(de)(de)(de)(de)(de)(de)(de)電(dian)(dian)(dian)(dian)氣(qi)(qi)絕(jue)(jue)緣性能及優異(yi)的(de)(de)(de)(de)(de)(de)(de)滅弧性能,其耐壓(ya)強度為同一(yi)壓(ya)力(li)下(xia)氮氣(qi)(qi)的(de)(de)(de)(de)(de)(de)(de)2.5倍,擊穿(chuan)電(dian)(dian)(dian)(dian)壓(ya)的(de)(de)(de)(de)(de)(de)(de)空氣(qi)(qi)的(de)(de)(de)(de)(de)(de)(de)2.5倍。在0.25MPa下(xia)與油的(de)(de)(de)(de)(de)(de)(de)擊穿(chuan)電(dian)(dian)(dian)(dian)壓(ya)相等(deng),在0.45MPa壓(ya)力(li)下(xia)是(shi)油的(de)(de)(de)(de)(de)(de)(de)擊穿(chuan)電(dian)(dian)(dian)(dian)壓(ya)的(de)(de)(de)(de)(de)(de)(de)2倍,是(shi)一(yi)種優于(yu)油的(de)(de)(de)(de)(de)(de)(de)新(xin)一(yi)代(dai)超高(gao)壓(ya)絕(jue)(jue)緣介質材料。該產(chan)品技術(shu)要求完全符合《ZBK-41006-89》標(biao)準,它(ta)是(shi)油浸式(shi)(shi)輕(qing)型試(shi)驗(yan)變(bian)(bian)(bian)壓(ya)器(qi)的(de)(de)(de)(de)(de)(de)(de)換代(dai)產(chan)品。該產(chan)品具有體(ti)積(ji)小、重量輕(qing)、不(bu)受氣(qi)(qi)候(hou)變(bian)(bian)(bian)化影響、電(dian)(dian)(dian)(dian)暈(yun)小、現(xian)場搬運無需(xu)靜止可使用(yong),使用(yong)壽(shou)命長、免(mian)維修等(deng)特點。適用(yong)于(yu)電(dian)(dian)(dian)(dian)力(li)系統、工礦企(qi)業、科研部門(men)等(deng)對各種高(gao)壓(ya)電(dian)(dian)(dian)(dian)氣(qi)(qi)設備、電(dian)(dian)(dian)(dian)氣(qi)(qi)元(yuan)件、絕(jue)(jue)緣材料進行(xing)工頻或直流高(gao)壓(ya)下(xia)的(de)(de)(de)(de)(de)(de)(de)絕(jue)(jue)緣強度試(shi)驗(yan)。
二、產品結構(gou)
YDQ系列高壓(ya)試驗(yan)變壓(ya)器采用單框芯(xin)式鐵芯(xin)結構,初級繞(rao)組(zu)繞(rao)在(zai)鐵芯(xin)上(shang),高壓(ya)繞(rao)組(zu)在(zai)外(wai),這種同(tong)軸布置減少了(le)漏磁通(tong),因(yin)而增大(da)了(le)繞(rao)組(zu)間(jian)的(de)耦(ou)合。產品的(de)外(wai)殼為圓柱灌(guan)式容(rong)器結構,能耐受0.8MPa以上(shang)壓(ya)力。其結構見圖1:
三、工(gong)作(zuo)原理
YDQ系(xi)(xi)列高(gao)(gao)壓(ya)試(shi)(shi)驗(yan)變(bian)(bian)壓(ya)器(qi)為單相變(bian)(bian)壓(ya)器(qi),聯結組標號(hao)Ⅰ.Ⅰ. 用(yong)工(gong)頻220V(10kVA以上(shang)為380V)電源接入 (為本公司生產的(de)試(shi)(shi)驗(yan)變(bian)(bian)壓(ya)器(qi)配套(tao)專用(yong)設備,詳細(xi)資料請(qing)見其具體(ti)使用(yong)說明書(shu))系(xi)(xi)列操作箱(xiang)(臺),經(jing)操作箱(xiang)內自偶調壓(ya)器(qi)(50kVA以上(shang)調壓(ya)器(qi)外附)調節至0~200V(或0~400V)電壓(ya)輸出至YDQ試(shi)(shi)驗(yan)變(bian)(bian)壓(ya)器(qi)的(de)初級繞組,根據電磁感應原理,在試(shi)(shi)驗(yan)變(bian)(bian)壓(ya)器(qi)高(gao)(gao)壓(ya)繞組可獲(huo)得試(shi)(shi)驗(yan)所需的(de)高(gao)(gao)電壓(ya)。
單(dan)臺YDQ系列(lie)交直流高(gao)(gao)壓(ya)(ya)(ya)試驗變壓(ya)(ya)(ya)器的工(gong)作原理圖見圖3,圖中(zhong)高(gao)(gao)壓(ya)(ya)(ya)套管中(zhong)裝有高(gao)(gao)壓(ya)(ya)(ya)硅堆,串(chuan)接在高(gao)(gao)壓(ya)(ya)(ya)回路(lu)中(zhong)作半波整流,以獲(huo)得(de)直流高(gao)(gao)電壓(ya)(ya)(ya)。當用(yong)一短(duan)路(lu)桿(gan)將高(gao)(gao)壓(ya)(ya)(ya)硅堆短(duan)接時,可獲(huo)得(de)工(gong)頻高(gao)(gao)電壓(ya)(ya)(ya),作為交流輸出狀(zhuang)態;取消短(duan)路(lu)桿(gan)時,作為直流輸出狀(zhuang)態。
圖中:D—短路桿 VD—高壓硅堆
試(shi)驗變壓器高(gao)(gao)壓套管中的高(gao)(gao)壓硅堆未畫(hua)出(chu),其(qi)原理與上(shang)圖相同。
三臺(tai)(tai)(tai)(tai)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)串級(ji)(ji)(ji)(ji)獲得更高(gao)電壓(ya)(ya)(ya)(ya)的(de)(de)(de)接(jie)(jie)線原(yuan)理見圖(tu)4。串級(ji)(ji)(ji)(ji)高(gao)壓(ya)(ya)(ya)(ya)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)有很大的(de)(de)(de)優越性,因(yin)為(wei)(wei)整個(ge)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)裝置(zhi)由(you)幾臺(tai)(tai)(tai)(tai)單(dan)(dan)臺(tai)(tai)(tai)(tai)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)組(zu)成(cheng),單(dan)(dan)臺(tai)(tai)(tai)(tai)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)容量小、電壓(ya)(ya)(ya)(ya)低、重(zhong)量輕,便(bian)于運輸(shu)(shu)和(he)安(an)裝。它既然可串接(jie)(jie)成(cheng)高(gao)出幾倍(bei)的(de)(de)(de)單(dan)(dan)臺(tai)(tai)(tai)(tai)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)輸(shu)(shu)出電壓(ya)(ya)(ya)(ya)組(zu)合(he)使用,又可分開成(cheng)幾套單(dan)(dan)臺(tai)(tai)(tai)(tai)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)單(dan)(dan)獨使用。整套裝置(zhi)投資小,經濟實惠。圖(tu)5中,在第**和(he)**級(ji)(ji)(ji)(ji)的(de)(de)(de)每個(ge)單(dan)(dan)元(yuan)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)中都(dou)有一個(ge)勵磁(ci)(ci)繞組(zu)A1、C1和(he)A2、C2。在三臺(tai)(tai)(tai)(tai)串級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)基本原(yuan)理中,低壓(ya)(ya)(ya)(ya)電源加在試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)Ⅰ的(de)(de)(de)初級(ji)(ji)(ji)(ji)繞組(zu)a1x1上,單(dan)(dan)臺(tai)(tai)(tai)(tai)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)Ⅰ、Ⅱ、Ⅲ的(de)(de)(de)輸(shu)(shu)出電壓(ya)(ya)(ya)(ya)都(dou)是V。勵磁(ci)(ci)繞組(zu)A1、C1給**級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)Ⅱ的(de)(de)(de)初級(ji)(ji)(ji)(ji)繞組(zu)供電;**級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)Ⅱ的(de)(de)(de)勵磁(ci)(ci)繞組(zu)A2、C2給第三級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)Ⅲ的(de)(de)(de)初級(ji)(ji)(ji)(ji)繞組(zu)供電。**級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)Ⅱ和(he)第三級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)Ⅲ的(de)(de)(de)箱體分別(bie)處在對地(di)(di)為(wei)(wei)1V和(he)2V的(de)(de)(de)高(gao)電位上,所以箱體對地(di)(di)是絕(jue)緣(yuan)的(de)(de)(de),試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)Ⅰ的(de)(de)(de)箱體是接(jie)(jie)地(di)(di)的(de)(de)(de)。這樣第**、**級(ji)(ji)(ji)(ji)、第三級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)(shi)驗(yan)(yan)(yan)變(bian)(bian)(bian)(bian)(bian)(bian)(bian)(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)(qi)(qi)(qi)(qi)(qi)對地(di)(di)的(de)(de)(de)額(e)定輸(shu)(shu)出電壓(ya)(ya)(ya)(ya)分別(bie)為(wei)(wei)1V、2V、3V;其額(e)定容量分別(bie)為(wei)(wei)3P、2P、1P。
YDQ系列高壓(ya)試(shi)驗變(bian)壓(ya)器做被試(shi)品的工(gong)頻耐壓(ya)試(shi)驗使用接(jie)線原理圖(tu)見圖(tu)5。
圖中:R1—限流(liu)電(dian)阻(zu) FRC—阻(zu)容分壓(ya)器 RF—球間隙保護電(dian)阻(zu) G—球間隙 CX—被試品
注(zhu):高壓尾必須可(ke)靠接地
工(gong)頻(pin)耐壓(ya)試(shi)驗(yan)(yan)中限流電(dian)阻R1應(ying)根據試(shi)驗(yan)(yan)變壓(ya)器的額定(ding)容量來選擇。如高壓(ya)側額定(ding)輸出電(dian)流在100~300mA時(shi),可取0.5~1Ω/V(試(shi)驗(yan)(yan)電(dian)壓(ya));高壓(ya)側額定(ding)輸出電(dian)流為1A以上時(shi),可取1Ω/V(試(shi)驗(yan)(yan)電(dian)壓(ya))。常用水(shui)電(dian)阻作為限流電(dian)阻,管子長度可按150kV/m考慮,管子粗(cu)細應(ying)具(ju)有足夠的熱容量(水(shui)阻液配制(zhi)方法:用蒸(zheng)餾水(shui)加(jia)入適量硫酸銅(tong)配制(zhi)成各種不同的阻值)。
球(qiu)間(jian)隙(xi)(xi)及保(bao)護電阻(zu):當電壓(ya)超過球(qiu)間(jian)隙(xi)(xi)整(zheng)定(ding)值(zhi)時(一般取試驗(yan)電壓(ya)的110%~120%),球(qiu)間(jian)隙(xi)(xi)放(fang)電,對被試品起到保(bao)護作用(yong)。球(qiu)間(jian)隙(xi)(xi)保(bao)護電阻(zu)可按1Ω/V(試驗(yan)電壓(ya))選(xuan)取。
在(zai)(zai)工頻(pin)耐(nai)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)試(shi)(shi)(shi)驗(yan)中,低電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)側測量(liang)(liang)電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)(儀表電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya))不是(shi)(shi)(shi)非常準(zhun)確的(de)(de),其原(yuan)因是(shi)(shi)(shi)由于(yu)試(shi)(shi)(shi)驗(yan)變(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)器(qi)存(cun)在(zai)(zai)著(zhu)(zhu)漏抗,在(zai)(zai)這(zhe)個漏抗上(shang)必(bi)然存(cun)在(zai)(zai)著(zhu)(zhu)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)降(jiang)或(huo)容升(sheng)(sheng),使試(shi)(shi)(shi)品(pin)上(shang)的(de)(de)電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)低于(yu)或(huo)高于(yu)低壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)側測量(liang)(liang)電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)表上(shang)反映出(chu)來的(de)(de)電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)。工頻(pin)耐(nai)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)試(shi)(shi)(shi)驗(yan)時,被(bei)試(shi)(shi)(shi)品(pin)上(shang)的(de)(de)電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)高于(yu)試(shi)(shi)(shi)驗(yan)變(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)器(qi)的(de)(de)輸出(chu)電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya),也就是(shi)(shi)(shi)所(suo)謂容升(sheng)(sheng)現象(xiang)。感應耐(nai)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)試(shi)(shi)(shi)驗(yan)時,試(shi)(shi)(shi)驗(yan)變(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)器(qi)的(de)(de)漏抗必(bi)然存(cun)在(zai)(zai)著(zhu)(zhu)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)降(jiang)。為了(le)準(zhun)確測量(liang)(liang)被(bei)試(shi)(shi)(shi)品(pin)上(shang)所(suo)施加的(de)(de)電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya),因此常在(zai)(zai)高壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)側接入FRC阻容分壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)器(qi)來測量(liang)(liang)電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)(見(jian)圖5)。
工頻(pin)耐壓試驗(yan)操作(zuo)注意事項
1)試驗人員(yuan)應做好分工,明確(que)相互間聯系方法(fa)。并有專門人監(jian)護(hu)現場(chang)**及觀察試品狀態。
2)被(bei)試品應先清掃干凈,并**干燥,以免損壞被(bei)試品和試驗帶來的(de)誤差。
3)對(dui)于大型(xing)試(shi)驗(yan),一(yi)般(ban)都(dou)應先(xian)進行空升試(shi)驗(yan)。即不(bu)接(jie)試(shi)品時升壓至(zhi)試(shi)驗(yan)電壓,校對(dui)各(ge)種表計,調整球間(jian)隙。
4)升壓速度不能太快,并必須防(fang)止突然加壓。例(li)如(ru)調(diao)壓器不在(zai)零(ling)位時突然合閘。也不能突然切(qie)斷電源,一般應(ying)在(zai)調(diao)壓器降至零(ling)位時拉(la)閘。
5)當電(dian)(dian)壓升至試驗電(dian)(dian)壓時(shi),開(kai)始(shi)計時(shi),到1min后,迅速降壓到1/3試驗電(dian)(dian)壓以下(xia)時(shi),才能(neng)拉開(kai)電(dian)(dian)源。
6)在升壓(ya)或(huo)耐壓(ya)試(shi)驗過程中,如發(fa)現下列不正常(chang)情況時,應立(li)即降壓(ya),切斷電源。停止試(shi)驗并查明原因:①電壓(ya)表指針擺動很大(da);②發(fa)現絕緣燒焦或(huo)冒煙;③被(bei)試(shi)品內有不正常(chang)的聲音。
7)耐壓試驗前(qian)后應測量絕緣電(dian)阻(zu),檢查絕緣情(qing)況。
試驗(yan)變壓器在做被試品(pin)的直流耐壓或泄(xie)露試驗(yan)時接線原理圖(tu)如圖(tu)6。
注:此試(shi)驗應(ying)先抽出短路桿(gan)“D”,圖6中(zhong)所示。
圖(tu)中:VD—高(gao)壓(ya)(ya)硅堆 R1—限流電阻 C1—高(gao)壓(ya)(ya)濾(lv)波電容(rong) FRC—阻容(rong)分(fen)壓(ya)(ya)器(qi) CX—被試品 μA—帶(dai)保護微安表
泄露試驗中限流(liu)(liu)(liu)電(dian)(dian)(dian)阻R1選擇在額定輸出(chu)(chu)電(dian)(dian)(dian)壓(ya)(ya)時,輸出(chu)(chu)端短路(lu)電(dian)(dian)(dian)流(liu)(liu)(liu)不超(chao)過高壓(ya)(ya)硅堆的*大(da)整(zheng)流(liu)(liu)(liu)。如電(dian)(dian)(dian)壓(ya)(ya)硅堆的*大(da)整(zheng)流(liu)(liu)(liu)電(dian)(dian)(dian)流(liu)(liu)(liu)為100mA時用于60kV的試驗裝置中,限流(liu)(liu)(liu)電(dian)(dian)(dian)阻按R1=60/0.1=600kΩ選擇。限流(liu)(liu)(liu)電(dian)(dian)(dian)阻還應具有足(zu)夠的容量和沿面放(fang)電(dian)(dian)(dian)距離。
高壓濾波電容C1一般選(xuan)擇在(zai)0.01~0.1μF,當被試品(pin)的電容量很大時,C1可省略不用。
泄露試(shi)驗的(de)操作(zuo)及注(zhu)意事項
1)試驗(yan)前應先檢查(cha)被試品(pin)是(shi)否停電(dian),接(jie)地(di)放電(dian),一(yi)切對(dui)外(wai)連線(xian)是(shi)否擦(ca)干(gan)凈。要(yao)嚴防將試驗(yan)電(dian)壓(ya)加到有人工作的部位上去。
2)接好試驗(yan)裝(zhuang)置的(de)接線后(hou),應(ying)復查無誤(wu)后(hou)才可加(jia)壓。應(ying)特(te)別注意(yi)檢查高壓設備(bei)及引線與(yu)地、與(yu)操(cao)作人員的(de)**距離,被試品(pin)的(de)外殼是(shi)否(fou)可靠接地,要按**規程中所(suo)規定的(de)內容進行試驗(yan)。
3)對于(yu)大電容量(liang)設備(bei)應(ying)緩(huan)慢(man)升(sheng)壓,防止被(bei)試品的(de)充電電流燒(shao)壞(huai)微(wei)安(an)表(biao)。必要時應(ying)分級加(jia)壓,分別(bie)讀取各級電壓下微(wei)安(an)表(biao)的(de)穩(wen)定讀數。
4)試(shi)驗過程中(zhong),應密切監視被試(shi)品、試(shi)驗裝置、微(wei)安表(biao),一旦發(fa)生擊(ji)穿、閃爍(shuo)等異(yi)常現象應立即降壓,切斷電源,并(bing)查(cha)明原因,詳細記錄。
5)試(shi)驗完畢(bi),降壓,切斷(duan)電源后應將被試(shi)品及試(shi)驗裝置本身充分放(fang)電。
四、注意事項
1、按照您所進(jin)行的(de)(de)試(shi)(shi)驗(yan)接好(hao)工作(zuo)線路。試(shi)(shi)驗(yan)變壓器的(de)(de)外殼(ke)以(yi)及(ji)操作(zuo)系統的(de)(de)外殼(ke)必須可靠(kao)接地(di)。試(shi)(shi)驗(yan)變壓器高(gao)壓繞組的(de)(de)X端(duan)(高(gao)壓尾(wei))以(yi)及(ji)測量繞組的(de)(de)F端(duan)必須可靠(kao)接地(di)。
2、做串級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)驗(yan)時,**級(ji)(ji)(ji)(ji)、第三(san)級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)驗(yan)變壓(ya)(ya)(ya)器(qi)的(de)(de)低壓(ya)(ya)(ya)繞組(zu)的(de)(de)X端,測量(liang)繞組(zu)的(de)(de)F端以(yi)及高(gao)壓(ya)(ya)(ya)繞組(zu)的(de)(de)X端(高(gao)壓(ya)(ya)(ya)尾)均接本級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)驗(yan)變壓(ya)(ya)(ya)器(qi)的(de)(de)外殼。**級(ji)(ji)(ji)(ji)、第三(san)級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)驗(yan)變壓(ya)(ya)(ya)器(qi)的(de)(de)外殼必(bi)須通過(guo)絕緣支架接地。
3、接通電源前,操作系統的調壓器必須調到零位后方(fang)可接通電源,合閘,開始升(sheng)壓。
4、從零(ling)開(kai)始(shi)均勻旋(xuan)轉調(diao)壓(ya)(ya)(ya)(ya)器手(shou)輪升(sheng)(sheng)壓(ya)(ya)(ya)(ya)。升(sheng)(sheng)壓(ya)(ya)(ya)(ya)方法(fa)有:快速升(sheng)(sheng)壓(ya)(ya)(ya)(ya)法(fa),即20s逐級升(sheng)(sheng)壓(ya)(ya)(ya)(ya)法(fa);慢(man)速升(sheng)(sheng)壓(ya)(ya)(ya)(ya)法(fa),即60s逐級升(sheng)(sheng)壓(ya)(ya)(ya)(ya)法(fa);極慢(man)速升(sheng)(sheng)壓(ya)(ya)(ya)(ya)法(fa)供選用。電(dian)壓(ya)(ya)(ya)(ya)從零(ling)開(kai)始(shi)按一定(ding)(ding)的(de)(de)升(sheng)(sheng)壓(ya)(ya)(ya)(ya)方式和(he)速度(du)上(shang)升(sheng)(sheng)到您(nin)所(suo)需的(de)(de)額定(ding)(ding)試(shi)(shi)(shi)驗電(dian)壓(ya)(ya)(ya)(ya)的(de)(de)75%后(hou),在以每秒2%額定(ding)(ding)試(shi)(shi)(shi)驗電(dian)壓(ya)(ya)(ya)(ya)的(de)(de)速度(du)升(sheng)(sheng)到您(nin)所(suo)需的(de)(de)額定(ding)(ding)電(dian)壓(ya)(ya)(ya)(ya),并密切(qie)注意測(ce)(ce)量儀(yi)表(biao)的(de)(de)指示以及被(bei)試(shi)(shi)(shi)品(pin)的(de)(de)情況(kuang)。升(sheng)(sheng)壓(ya)(ya)(ya)(ya)過程中(zhong)或試(shi)(shi)(shi)驗過程中(zhong)如發(fa)現測(ce)(ce)量儀(yi)表(biao)的(de)(de)指示及被(bei)試(shi)(shi)(shi)品(pin)情況(kuang)異常,應(ying)立即降壓(ya)(ya)(ya)(ya),切(qie)斷(duan)電(dian)源,查明情況(kuang)。
5、試驗(yan)完(wan)畢(bi)后,應在數(shu)秒(miao)內勻速的將(jiang)調壓器返回至(zhi)零(ling)位,然后切斷電源。
6、本產品不得超過額定(ding)參數使(shi)用(yong)。除試驗必須(xu)外,決不允許全電壓通電或斷(duan)電。
7、 再升壓(ya)(ya)或耐壓(ya)(ya)試驗過程中,如發現以下不正常(chang)情況時(shi),應立即降壓(ya)(ya),切斷電源(yuan),停止試驗并查明(ming)原因。
⑴電壓(ya)表(biao)指針(zhen)擺(bai)動(或數字(zi)跳(tiao)動)很大
⑵電流表直(zhi)線上升
被試品內有(you)不正常的(de)聲音(yin)
8、圖1中第9項系壓(ya)(ya)力閥及(ji)壓(ya)(ya)力表,為(wei)長期關閉(bi)狀(zhuang)態。每(mei)6個月開閥一次,以檢(jian)查(cha)SF6壓(ya)(ya)力,應不小于0.2MPa(檢(jian)查(cha)壓(ya)(ya)力后立(li)即(ji)關閉(bi)閥門),低于0.2MPa時應加SF6氣(qi)體,以增(zeng)加氣(qi)絕緣。
9、耐壓(ya)實驗前后應測量被試(shi)設備的絕緣(yuan)電阻,檢查(cha)絕緣(yuan)情況。
10、當試驗變(bian)壓器長期(qi)不使用時,應放(fang)置于通風、干(gan)燥(zao)、無陽光直(zhi)射的地(di)方(fang)。
11、該(gai)產品不允許(xu)在高于45℃的溫(wen)度下長期存放、使用、放氣。
12、運輸搬運途中不得重力沖擊。
13、產品緊固件(jian)及(ji)壓力閥、壓力表不得擅自松動(dong)。
14、使用本產品做高(gao)壓(ya)(ya)試(shi)驗(yan)時(shi),出熟悉本說明書外,還必須嚴格執行國家有(you)關標(biao)準和操(cao)作規(gui)程(cheng)。可參(can)照GB311-83《高(gao)壓(ya)(ya)輸(shu)變設(she)備的絕(jue)緣配(pei)合,高(gao)壓(ya)(ya)試(shi)驗(yan)技術》;《電氣設(she)備預防性試(shi)驗(yan)規(gui)程(cheng)》等(deng)。
五(wu)、試驗(yan)變壓器(qi)的容(rong)量選(xuan)擇
標稱(cheng)試驗變壓(ya)器容量Pn的(de)確定公式:Pn=kVn 2ωCt×10-9
式(shi)中:
Pn——標稱(cheng)試驗變(bian)壓(ya)器容量(kVA)
Vn——試驗變壓(ya)器(qi)的(de)額定輸出高壓(ya)的(de)有效值(kV)
k ——**系(xi)數。k≥1,標稱電壓Vn≥1MV時,k=2;標稱電壓較低(di)時,k值可取(qu)高一些(xie)。
Ct——被試(shi)品的電容量(pF)
ω——角頻率(lv),ω=2πf,f——試驗電源的頻率(lv)
被試設備的(de)電容量Ct可由交(jiao)流電橋測(ce)出。Ct的(de)變(bian)化很(hen)大,
可由設備的(de)類型而定。
典型數據如下(xia):
簡(jian)單(dan)的(de)棒式或懸式絕(jue)緣(yuan)子 幾(ji)十微法
簡單的分級套管 100~1000pF
電壓互感器(qi) 200 ~ 500pF
電(dian)力變壓器 < 1000kVA~1000pF
> 1000kVA 1000~10000pF
高(gao)壓(ya)電力電纜和油(you)浸紙(zhi)絕緣 250~300pF/m
氣體絕緣 ~60pF/m
封閉變電站,SF6氣體(ti)絕(jue)緣 100~10000Pf;
對于不同的(de)試驗電(dian)壓Vn,選(xuan)擇不同的(de)(適當的(de))**系數k。
以下(xia)列出不同的Vn所選用的k值(zhi)供參考。
Vn =50~100kV k = 4
Vn =150~300kV k = 3
Vn > 300kV k = 2
一(yi)、概(gai)述
工(gong)頻(pin)耐壓試驗是鑒定(ding)電力設(she)(she)備絕(jue)緣強度(du)的*嚴格、*有(you)效(xiao)和*直(zhi)接的方法(fa)。它能檢查出那些危(wei)險性(xing)較(jiao)大的集(ji)中缺陷,對判斷電力設(she)(she)備能否繼續參加運行具有(you)決定(ding)性(xing)作(zuo)用,是保證設(she)(she)備絕(jue)緣水平、避免發生絕(jue)緣事故(gu)的重(zhong)要手段(duan)。
本裝置是根據國家(jia)*新電力行業標準而設計的(de)、性能先(xian)進的(de)耐壓試(shi)驗設備,用(yong)于(yu)對各(ge)種(zhong)電器產品、電氣元件、絕(jue)緣材料等進行規(gui)定電壓下(xia)的(de)絕(jue)緣強度試(shi)驗,以考核產品的(de)絕(jue)緣水平,發現被試(shi)品的(de)絕(jue)緣缺(que)陷,衡量(liang)過電壓的(de)能力。
二、產品特點(dian)
監視功能:高壓電(dian)壓 低(di)壓電(dian)流(liu) 零位指(zhi)示(shi)(shi) 電(dian)源指(zhi)示(shi)(shi) 工作指(zhi)示(shi)(shi) 計時指(zhi)示(shi)(shi)
保護功能:過流(liu)保護、零(ling)位啟動保護、聲光語言報警提醒
采用新(xin)型時間繼(ji)電器,計時范(fan)圍(wei)更廣(1S~99H)
采用新型電流繼電器,更(geng)**、更(geng)可靠(kao),確保人身及設備**。
試驗變(bian)壓(ya)(ya)器高壓(ya)(ya)線圈(quan)為圓筒多層塔式,由上等聚酯漆包線及(ji)高耐壓(ya)(ya)值(zhi)絕(jue)緣材料(liao)繞(rao)制而成。
試驗變壓(ya)器(5kVA以上)裝有可移(yi)動的鐵輪。具有重量輕、體積小、移(yi)動方(fang)便、性能優越等特(te)點。
三、設備組成
1、選型(xing)配置
標(biao)準(zhun)配置
|
□ 分體(ti)式
|
操作部分:
□箱式(shi)(不大于5kVA) / □臺式(shi)
容量(liang): kVA(小(xiao)于200kVA)
輸入:□AC220V / □AC380V
|
試驗(yan)變壓(ya)器(qi):
□交流 / □交直流
□油變 / □干(gan)變 / □氣變
容量(liang): kVA(小于200kVA)
輸出:AC kV(小(xiao)于300kVA)
|
□ 一體式
|
□箱式(shi)(shi)(不大(da)于20kV) / □臺式(shi)(shi)(不大(da)于30kV)
容量: kVA(小于300kVA)
輸入(ru):□AC220V / □AC380V 輸出:AC kV(不(bu)大(da)于30kV)
|
客戶選配
|
□標準(zhun)高壓分(fen)壓器
|
□保護球隙(xi)
|
□直流(liu)微安表
|
□放**
|
□保護(hu)水阻(zu)
|
□高壓濾波電容
|
其它(ta):
|
2、對應(ying)實物
四、技術(shu)指標
1、使用條件:
(1)工作場(chang)所應無嚴重影響絕緣的氣體、蒸汽(qi)、化學性塵埃及(ji)其它爆炸性和腐蝕性介質。
(2)環境溫度 -20~+50℃
(3)環境濕(shi)度 ≤85% RH(無(wu)凝(ning)結水)
2、控制箱(臺)參數(shu):(常規(gui)參數(shu)見(jian)下表)
規(gui)格
|
容量(liang)
|
輸 入 電(dian) 源(yuan)
|
輸 出(chu) 電 壓
|
重量(kg)
|
相數
|
(V)
|
(A)
|
(V)
|
(A)
|
2/220
|
2
|
1
|
220
|
10
|
0-250
|
8
|
14
|
3/220
|
3
|
1
|
220
|
15
|
0-250
|
12
|
16
|
5/220
|
5
|
1
|
220
|
25
|
0-250
|
20
|
18
|
10/220
|
10
|
1
|
220
|
50
|
0-250
|
40
|
80
|
15/380
|
15
|
2
|
380
|
37.5
|
0-430
|
34.8
|
90
|
20/380
|
20
|
2
|
380
|
50
|
0-430
|
46.5
|
100
|
25/380
|
25
|
2
|
380
|
62.5
|
0-430
|
58.1
|
120
|
30/380
|
30
|
2
|
380
|
75
|
0-430
|
69.7
|
140
|
50/380
|
50
|
2
|
380
|
125
|
0-430
|
116.2
|
160
|
100/380
|
100
|
2
|
380
|
250
|
0-430
|
232.5
|
250
|
說明:如有特殊參數(shu)(shu)要求,可(ke)按用(yong)戶的技術參數(shu)(shu)進行(xing)設計制作。
3、試驗變(bian)壓器參數:(常規參數見下表)
規格
|
容量
kVA
|
低壓側(ce)
|
高壓側
|
高壓側(交直(zhi)流變壓器(qi))
|
測量變比
|
60分鐘溫升(sheng)℃
|
阻抗電壓%
|
空載電流
%
|
質量
kg
|
電壓
V
|
電流
A
|
交流(liu)輸出
|
直(zhi)流輸出(chu)
|
電壓(ya)kV
|
電流
|
電壓kV
|
電流
|
1.5/50
|
1.5
|
200
|
7.5
|
50
|
30
|
70
|
21.4
|
500
|
50
|
10
|
<4
|
19.5
|
3/50
|
3
|
200
|
15
|
50
|
60
|
70
|
42.9
|
500
|
50
|
10
|
<4
|
27
|
5/50
|
5
|
200
|
25
|
50
|
100
|
70
|
71.4
|
500
|
50
|
10
|
<4
|
52
|
10/50
|
10
|
200
|
50
|
50
|
200
|
70
|
142.9
|
500
|
50
|
10
|
<4
|
80
|
15/50
|
15
|
400
|
37.5
|
50
|
300
|
70
|
214.3
|
500
|
50
|
8
|
<4
|
120
|
20/50
|
20
|
400
|
50
|
50
|
400
|
70
|
285.7
|
500
|
50
|
8
|
<4
|
140
|
30/50
|
30
|
400
|
75
|
50
|
600
|
70
|
428.6
|
500
|
50
|
8
|
<4
|
155
|
50/50
|
50
|
400
|
125
|
50
|
1000
|
70
|
714.3
|
500
|
50
|
8
|
<4
|
184
|
10/100
|
10
|
200
|
50
|
100
|
100
|
140
|
71.4
|
1000
|
50
|
10
|
<4
|
135
|
15/100
|
15
|
400
|
37.5
|
100
|
150
|
140
|
107.1
|
1000
|
50
|
8
|
<4
|
150
|
20/100
|
20
|
400
|
50
|
100
|
200
|
140
|
142.9
|
1000
|
50
|
8
|
<4
|
215
|
30/100
|
30
|
400
|
75
|
100
|
300
|
140
|
214.3
|
1000
|
50
|
8
|
<4
|
250
|
50/100
|
50
|
400
|
125
|
100
|
500
|
140
|
357.1
|
1000
|
50
|
8
|
<4
|
290
|
10/150
|
10
|
200
|
50
|
100
|
66.7
|
140
|
47.6
|
1500
|
50
|
10
|
<4
|
180
|
15/150
|
15
|
400
|
37.5
|
150
|
100
|
210
|
71.4
|
1500
|
50
|
8
|
<4
|
200
|
20/150
|
30
|
400
|
50
|
150
|
133.3
|
210
|
95.2
|
1500
|
50
|
8
|
<4
|
220
|
30/150
|
30
|
400
|
75
|
150
|
200
|
210
|
142.9
|
1500
|
50
|
8
|
<4
|
280
|
50/150
|
50
|
400
|
125
|
150
|
333.3
|
210
|
238.1
|
1500
|
50
|
8
|
<4
|
340
|
說明:如有特殊參數要求,可按用戶的技術參數進行設(she)計制作。
上表的(de)重量以油浸式(shi)試驗(yan)變壓器(qi)為例(li),干式(shi)試驗(yan)變壓器(qi)和(he)充氣(qi)式(shi)試驗(yan)變壓器(qi)稍有不同。
五、接線及工(gong)作(zuo)原(yuan)理
1、調壓部分接線及(ji)原理(li)
調(diao)壓(ya)部(bu)分(fen)(fen)由(you)控制(zhi)部(bu)分(fen)(fen)和(he)試(shi)驗(yan)變壓(ya)器(qi)組(zu)(zu)(zu)成(cheng)。控制(zhi)部(bu)分(fen)(fen)是由(you)接(jie)觸式調(diao)壓(ya)器(qi)及其控制(zhi)、保護(hu)、測量、信號電路(lu)組(zu)(zu)(zu)成(cheng)。試(shi)驗(yan)變壓(ya)器(qi)由(you)低壓(ya)繞組(zu)(zu)(zu)、高壓(ya)繞組(zu)(zu)(zu)、儀表繞組(zu)(zu)(zu)三部(bu)分(fen)(fen)組(zu)(zu)(zu)成(cheng)。
試(shi)驗變(bian)(bian)壓器(qi)為(wei)交直(zhi)流兩用時(shi),試(shi)驗變(bian)(bian)壓器(qi)配置(zhi)(zhi)了高壓硅堆(油變(bian)(bian)、氣變(bian)(bian)為(wei)內置(zhi)(zhi),干(gan)變(bian)(bian)為(wei)外(wai)置(zhi)(zhi)),高壓可(ke)輸(shu)出交流和直(zhi)流。輸(shu)出交流時(shi),要求接入(ru)短(duan)路(lu)桿(油變(bian)(bian)、氣變(bian)(bian))或去掉外(wai)置(zhi)(zhi)硅堆(干(gan)變(bian)(bian));輸(shu)出直(zhi)流時(shi),要求擰出短(duan)路(lu)桿(油變(bian)(bian)、氣變(bian)(bian))或加上(shang)外(wai)置(zhi)(zhi)硅堆(干(gan)變(bian)(bian))
通過接入工(gong)頻電源,調(diao)(diao)節調(diao)(diao)壓(ya)器(qi),以獲得所需要的(de)試驗(yan)高壓(ya)電壓(ya)值(zhi)。其工(gong)作原理見圖1:
2、試驗(yan)部分接線(xian)及原理
做耐壓(ya)(ya)試驗(yan)時,控(kong)制部(bu)分(fen)、變(bian)壓(ya)(ya)器的(de)接地端(duan)及高壓(ya)(ya)尾必須可靠接地。有條件的(de)情(qing)況下(xia),做工頻(pin)耐壓(ya)(ya)試驗(yan)請加上限流電阻、標準(zhun)高壓(ya)(ya)分(fen)壓(ya)(ya)器、球隙(xi)保(bao)護(hu)電阻及保(bao)護(hu)球隙(xi),如圖3。
做(zuo)直流耐(nai)壓(ya)試驗請另外加上微(wei)(wei)安表,微(wei)(wei)安表必須接(jie)在(zai)硅(gui)(gui)堆(dui)和被試器(qi)之(zhi)間,油(you)變或氣變一般(ban)擰(ning)(ning)在(zai)高壓(ya)頭上面(mian)(要(yao)求(qiu)擰(ning)(ning)出短路桿),干變擰(ning)(ning)在(zai)外置硅(gui)(gui)堆(dui)上面(mian);為了更準確顯(xian)示高壓(ya)直流泄漏電流,請將分壓(ya)器(qi)的(de)高壓(ya)線接(jie)在(zai)微(wei)(wei)安表和硅(gui)(gui)堆(dui)之(zhi)間,(油(you)變、氣變)如圖4,(干變)如圖5。
耐(nai)壓(ya)試驗(yan)中限(xian)流(liu)電(dian)(dian)阻R1應(ying)根(gen)據試驗(yan)變(bian)壓(ya)器的(de)(de)額定(ding)容量來(lai)選(xuan)擇。如高壓(ya)側額定(ding)輸出電(dian)(dian)流(liu)在(zai)100~300mA時,可取0.5~1Ω/V(試驗(yan)電(dian)(dian)壓(ya));高壓(ya)側額定(ding)輸出電(dian)(dian)流(liu)為(wei)1A以上時,可取1Ω/V(試驗(yan)電(dian)(dian)壓(ya))。常用(yong)水(shui)電(dian)(dian)阻作為(wei)限(xian)流(liu)電(dian)(dian)阻,管子長度可按150kV/m考慮,管子粗(cu)細(xi)應(ying)具有足夠的(de)(de)熱容量(水(shui)阻液配制方法:用(yong)蒸(zheng)餾水(shui)加入適量硫酸銅配制成各種不同(tong)的(de)(de)阻值)。
球間隙(xi)及保(bao)護電(dian)阻(zu):當電(dian)壓超過球間隙(xi)整定(ding)值(zhi)時(shi)(一般(ban)取試驗電(dian)壓的110%~120%),球間隙(xi)放電(dian),對被試品起到保(bao)護作用。球間隙(xi)保(bao)護電(dian)阻(zu)可按1Ω/V(試驗電(dian)壓)選取。
在(zai)(zai)工(gong)頻(pin)耐(nai)壓(ya)(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)中,低(di)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)側(ce)(ce)測量(liang)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(儀表電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya))不(bu)是(shi)(shi)非常(chang)準確的(de)(de),其(qi)原因是(shi)(shi)由于(yu)試(shi)(shi)驗(yan)變壓(ya)(ya)(ya)(ya)(ya)器(qi)存(cun)在(zai)(zai)著漏(lou)抗(kang),在(zai)(zai)這個漏(lou)抗(kang)上(shang)必然(ran)存(cun)在(zai)(zai)著壓(ya)(ya)(ya)(ya)(ya)降(jiang)或(huo)容升,使試(shi)(shi)品上(shang)的(de)(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)低(di)于(yu)或(huo)高(gao)于(yu)低(di)壓(ya)(ya)(ya)(ya)(ya)側(ce)(ce)測量(liang)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)表上(shang)反(fan)映出(chu)來的(de)(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)。工(gong)頻(pin)耐(nai)壓(ya)(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)時,被試(shi)(shi)品上(shang)的(de)(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)高(gao)于(yu)試(shi)(shi)驗(yan)變壓(ya)(ya)(ya)(ya)(ya)器(qi)的(de)(de)輸(shu)出(chu)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya),也就是(shi)(shi)所(suo)謂容升現象(xiang)。感應耐(nai)壓(ya)(ya)(ya)(ya)(ya)試(shi)(shi)驗(yan)時,試(shi)(shi)驗(yan)變壓(ya)(ya)(ya)(ya)(ya)器(qi)的(de)(de)漏(lou)抗(kang)必然(ran)存(cun)在(zai)(zai)著壓(ya)(ya)(ya)(ya)(ya)降(jiang)。為(wei)了準確測量(liang)被試(shi)(shi)品上(shang)所(suo)施(shi)加的(de)(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya),因此常(chang)在(zai)(zai)高(gao)壓(ya)(ya)(ya)(ya)(ya)側(ce)(ce)接入(ru)標(biao)準高(gao)壓(ya)(ya)(ya)(ya)(ya)分壓(ya)(ya)(ya)(ya)(ya)器(qi)來測量(liang)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)。
五(wu)、面板(ban)結構說明
1、操作箱面板
控制箱(xiang)為(wei)箱(xiang)式鋁合(he)金結構,面板(ban)采用拉絲鋁合(he)金工(gong)藝,所(suo)有(you)電器元(yuan)件(jian)均裝在骨架上,便于安裝和維修。面板(ban)元(yuan)件(jian)布(bu)置如下:
2、操作臺面(mian)板
操作臺為臺式(shi)結構(gou),殼體為冷扎(zha)鋼板結構(gou),面板采用鋁合(he)金拉(la)絲工(gong)藝(yi),面板元件布置如下:
六、操作指(zhi)南
本裝(zhuang)置(zhi)在(zai)操作之前應(ying)(ying)根據(ju)不同被(bei)試品的容量、電(dian)(dian)壓等級(ji),先(xian)計算好*大工作電(dian)(dian)流(liu),并調整電(dian)(dian)流(liu)保護器。其試驗接線應(ying)(ying)參考(kao)本說明書中圖(tu)1、圖(tu)2、圖(tu)3、圖(tu)4、圖(tu)5,必須可(ke)靠接地。
1、操作(zuo)要點
(1)試驗(yan)前(qian),應了解(jie)被(bei)試品的試驗(yan)電壓,同時了解(jie)被(bei)試品的其他試驗(yan)項目及以前(qian)的試驗(yan)結果。若(ruo)被(bei)試品有缺(que)陷(xian)或(huo)異常(chang),應在消除(chu)后再(zai)進行耐壓試驗(yan)。
(2)試(shi)驗(yan)現場應(ying)圍好遮攔或圍繩(sheng),掛好標(biao)示牌,并派專人監護(hu)。
(3)試驗前,被(bei)試品(pin)表面應(ying)擦拭(shi)干凈,將被(bei)試品(pin)的(de)外(wai)殼和非被(bei)試繞組可靠(kao)接地(di)。被(bei)試品(pin)為新沖油設備(bei)時(shi),應(ying)按《規程(cheng)》規定使油靜止一(yi)定時(shi)間(jian)再升壓,對110kV及以(yi)下的(de)充(chong)油電(dian)力(li)設備(bei),在(zai)注滿油后靜置時(shi)間(jian)應(ying)不少于24小時(shi),對220kV及330kV的(de)充(chong)油電(dian)力(li)設備(bei),靜置時(shi)間(jian)應(ying)不少于48小時(shi)。
(4)接(jie)(jie)好試驗接(jie)(jie)線(xian)后,應(ying)由(you)有經驗的人員檢(jian)查,確認無誤后方(fang)可升壓。
(5)升(sheng)壓(ya)前,首先檢查調壓(ya)器是否在零位。調壓(ya)器在零位方(fang)可(ke)升(sheng)壓(ya)。
(6)升(sheng)壓過(guo)程中不(bu)僅要(yao)監視(shi)電(dian)(dian)壓表的(de)變(bian)(bian)化(hua)(hua),還應監視(shi)電(dian)(dian)流表的(de)變(bian)(bian)化(hua)(hua),以及(ji)被(bei)試(shi)品(pin)電(dian)(dian)流的(de)變(bian)(bian)化(hua)(hua)。升(sheng)壓時要(yao)均(jun)勻(yun)升(sheng)壓,不(bu)能太快。升(sheng)至(zhi)規(gui)定試(shi)驗電(dian)(dian)壓時,開始計(ji)算時間,時間到后(hou),緩慢均(jun)勻(yun)降下(xia)電(dian)(dian)壓。絕不(bu)允許不(bu)降壓就先跳開電(dian)(dian)源開關。
(7)試驗中發現(xian)表針擺動或被(bei)試品有(you)異常(chang)聲響、冒(mao)煙(yan)等應(ying)立即降下電壓(ya),拉開(kai)電源,在高(gao)壓(ya)側掛上接地線(xian)后(hou),再查明原因。
(8)耐壓試(shi)驗前后均應(ying)測量被(bei)試(shi)品的絕(jue)緣電阻。
2、操作步驟
(1) 按試(shi)驗(yan)(yan)要求將控制部(bu)分(fen)、試(shi)驗(yan)(yan)變壓器、被試(shi)品正(zheng)確接好線,必(bi)須可靠接地,請參(can)考圖1、圖2、圖3、圖4、圖5。
(2) 根據試驗的要求,整定“時(shi)間繼(ji)電(dian)器(qi)”及“過流繼(ji)電(dian)器(qi)”。
A 時(shi)間(jian)繼電器設(she)置:
T1,T2,T3,T4設置0~9任意數字(zi),T可(ke)設置為H(小時),M(分鐘),S(秒)。
根據(ju)試驗要求,在1S~99H內可以任意設置定時時間。
B 過流繼電器設置(zhi):
過(guo)流(liu)(liu)(liu)動作設(she)(she)定值(zhi)(zhi)(zhi)=過(guo)流(liu)(liu)(liu)繼電(dian)(dian)(dian)器(qi)刻(ke)度盤讀數×測量(liang)變比×K,其(qi)中K為(wei)(wei)電(dian)(dian)(dian)流(liu)(liu)(liu)倍率(lv)/切(qie)除開關的(de)狀態值(zhi)(zhi)(zhi),分(fen)(fen)別(bie)為(wei)(wei)X1,X2,OFF,電(dian)(dian)(dian)流(liu)(liu)(liu)倍率(lv)/切(qie)除開關處于(yu)×1,×2位置時,K值(zhi)(zhi)(zhi)分(fen)(fen)別(bie)為(wei)(wei)1、2,切(qie)換為(wei)(wei)OFF擋時,K值(zhi)(zhi)(zhi)為(wei)(wei)+∞。(注:不要使用OFF檔,因為(wei)(wei)會使變壓器(qi)失去過(guo)流(liu)(liu)(liu)保護功能(neng)而導致設(she)(she)備損壞。測量(liang)變比為(wei)(wei)電(dian)(dian)(dian)流(liu)(liu)(liu)互感(gan)器(qi)的(de)變比,沒有電(dian)(dian)(dian)流(liu)(liu)(liu)互感(gan)器(qi)時為(wei)(wei)1)。
(3) 接(jie)入電(dian)源(yuan),此時(shi)(shi),“電(dian)源(yuan)燈”亮(liang)(liang)(liang),表(biao)示(shi)外部電(dian)源(yuan)已引(yin)入。如“零位(wei)燈”亮(liang)(liang)(liang),表(biao)示(shi)調壓(ya)器在零位(wei)。如“零位(wei)燈”不亮(liang)(liang)(liang),應(ying)逆時(shi)(shi)針旋(xuan)轉調節調壓(ya)器手柄至“零位(wei)燈”亮(liang)(liang)(liang),表(biao)示(shi)可(ke)進行調壓(ya)操作(zuo)。
(4)按(an)“啟動按(an)鈕”。此時,“送電燈(deng)”,“電源燈(deng)”和“零位燈(deng)”亮;進(jin)入送電狀態。
(5)以2kV/S勻(yun)速順時針旋轉調壓器手柄至被(bei)試品規定的(de)耐壓值(zhi),并密(mi)切(qie)注視(shi)電(dian)流表(直(zhi)流耐壓試驗(yan)時,同(tong)時密(mi)切(qie)注視(shi)直(zhi)流微安表)。此時,“電(dian)源燈”,“工作燈”亮;“零位(wei)燈”滅。
(6)根據試驗啟動(dong)“計時按(an)鈕”,計時開(kai)始(shi),并注(zhu)意被(bei)試品的情況。
(7)當耐壓計(ji)(ji)時(shi)(shi)到時(shi)(shi),操作(zuo)(zuo)臺自動聲光報警。應立即逆時(shi)(shi)針旋(xuan)轉調壓器手(shou)柄至零位,按(an)下停止按(an)鈕(niu)和解除計(ji)(ji)時(shi)(shi)按(an)鈕(niu)自鎖狀(zhuang)態。此時(shi)(shi)“電源燈”, “零位燈”亮(liang),“工作(zuo)(zuo)燈”滅。試驗即告完畢
(8)拔掉電源,拆除接線(xian),試驗結束。
(9)在升壓或耐壓過程中,如(ru)發生短路、閃絡、擊(ji)穿過流(liu)時,過流(liu)繼電器動作,切斷主回路。此時應將(jiang)調(diao)壓器逆時針旋轉(zhuan)至零(ling)位,切斷電源,并(bing)查明原因,并(bing)作詳細記錄。
(10)試驗完畢,降(jiang)壓,切斷電源后(hou)應用放**將被試品及試驗裝置(zhi)本身充分放電。
七、產品維護
1、開箱驗收時(shi),應檢(jian)查主控回路接(jie)線是(shi)否松動,調壓器電刷(shua)是(shi)否接(jie)觸(chu)良好;
2、長期(qi)不用時(shi),使用前應用500V兆歐表測(ce)量絕緣(yuan)電阻(zu),其阻(zu)值(zhi)不低于(yu)0.5MΩ;
3、電(dian)源電(dian)壓(ya)應符合控制箱(臺(tai))銘(ming)牌上的輸入電(dian)壓(ya)值;
4、本裝(zhuang)置(zhi)設有過電(dian)流(liu)保護,出廠已調整為額(e)(e)定電(dian)流(liu)的50%。用(yong)于(yu)小負載(zai)時,應根據被試品(pin)的額(e)(e)定容量電(dian)流(liu)重新設定;
5、使(shi)用完畢后,應關好控制箱(臺)門,以保持控制箱(臺)內(nei)部(bu)清(qing)潔。
八、注意事(shi)項
1、按照您所進行(xing)的(de)試驗接(jie)好(hao)工作(zuo)線路。試驗變(bian)壓(ya)(ya)器的(de)外殼(ke)以及操作(zuo)系統的(de)外殼(ke)必須(xu)可(ke)靠接(jie)地。試驗變(bian)壓(ya)(ya)器的(de)高(gao)壓(ya)(ya)繞組的(de)X端(高(gao)壓(ya)(ya)尾)以及測量繞組的(de)F端必須(xu)可(ke)靠接(jie)地。
2、做(zuo)串級(ji)(ji)試驗(yan)(yan)(yan)時,**級(ji)(ji)、第三(san)級(ji)(ji)試驗(yan)(yan)(yan)變(bian)壓器的低壓繞(rao)組成X端,測量繞(rao)組的F端以(yi)及高壓繞(rao)組的X端(高壓端)均接(jie)本級(ji)(ji)試驗(yan)(yan)(yan)變(bian)壓器具外(wai)(wai)殼(ke)。**級(ji)(ji)、第三(san)級(ji)(ji)試驗(yan)(yan)(yan)變(bian)壓器的外(wai)(wai)殼(ke)必須通過絕(jue)緣支架接(jie)地。
3、接通電(dian)(dian)(dian)源(yuan)(yuan)前,操作系統的(de)(de)調壓(ya)(ya)器必(bi)須調到(dao)零位后(hou)方可接通電(dian)(dian)(dian)源(yuan)(yuan),合(he)閘,開(kai)始升壓(ya)(ya)。從零開(kai)始勻速(su)(su)旋轉調壓(ya)(ya)器手輪升壓(ya)(ya)。升壓(ya)(ya)方式(shi)有:快速(su)(su)升壓(ya)(ya)法(fa),即20s逐級升壓(ya)(ya)法(fa);慢速(su)(su)升壓(ya)(ya)法(fa),即60s逐級升壓(ya)(ya)法(fa);極慢速(su)(su)升壓(ya)(ya)法(fa)供選用。電(dian)(dian)(dian)壓(ya)(ya)從零開(kai)始按一定(ding)的(de)(de)升壓(ya)(ya)方式(shi)和速(su)(su)度(du)上(shang)升到(dao)您(nin)所需(xu)的(de)(de)額定(ding)試(shi)驗電(dian)(dian)(dian)壓(ya)(ya)的(de)(de)75%后(hou),再以每秒2%額定(ding)試(shi)驗電(dian)(dian)(dian)壓(ya)(ya)的(de)(de)速(su)(su)度(du)升到(dao)您(nin)所需(xu)的(de)(de)試(shi)驗電(dian)(dian)(dian)壓(ya)(ya),并密(mi)切(qie)注意測(ce)量(liang)儀(yi)表的(de)(de)及被(bei)試(shi)品的(de)(de)情(qing)(qing)況。升壓(ya)(ya)過(guo)程中或試(shi)驗過(guo)程中如發現測(ce)量(liang)儀(yi)表的(de)(de)指示及被(bei)試(shi)品情(qing)(qing)況異(yi)常,應立即降(jiang)壓(ya)(ya),切(qie)斷電(dian)(dian)(dian)源(yuan)(yuan),查明情(qing)(qing)況。
4、試驗完畢后,應(ying)在數秒內勻(yun)速的將(jiang)調壓器(qi)返回至(zhi)零位,然后切斷電源(yuan)。本(ben)產品不得超(chao)過額定參數使(shi)用。
5、使用本產品做(zuo)高(gao)壓試(shi)驗(yan)時,除熟悉本說(shuo)明(ming)書外,還(huan)必須嚴格執行(xing)國(guo)家(jia)有關標(biao)準和(he)操作(zuo)規(gui)程(cheng)。可(ke)參照GB311.1 – 97《高(gao)壓輸(shu)變(bian)設備(bei)的絕緣配合,高(gao)壓試(shi)驗(yan)技術》;《電氣設備(bei)預防性試(shi)驗(yan)規(gui)程(cheng)》等
一(yi)、概(gai)述
智能(neng)耐(nai)(nai)壓試驗裝置是根據國家*新電(dian)力行(xing)業標準而設計(ji)的(de)(de)、性能(neng)先進的(de)(de)智能(neng)型耐(nai)(nai)壓試驗設備,用(yong)于對(dui)各(ge)種電(dian)器產品、電(dian)氣元件、絕(jue)(jue)緣(yuan)(yuan)(yuan)材料(liao)等進行(xing)規定(ding)電(dian)壓下的(de)(de)絕(jue)(jue)緣(yuan)(yuan)(yuan)強(qiang)度試驗,以考(kao)核產品的(de)(de)絕(jue)(jue)緣(yuan)(yuan)(yuan)水平,發現被試品的(de)(de)絕(jue)(jue)緣(yuan)(yuan)(yuan)缺(que)陷,衡量過電(dian)壓的(de)(de)能(neng)力。廣泛應用(yong)于電(dian)工制造(zao)部門、電(dian)力運行(xing)部門、科(ke)研單位和(he)高(gao)等院校。
二、產品特(te)點(dian)
1. 320×240液晶顯示(shi)器、高(gao)速熱敏(min)打(da)印機。
2. 高(gao)壓(ya)電(dian)壓(ya)、高(gao)壓(ya)電(dian)流、低壓(ya)電(dian)壓(ya)、低壓(ya)電(dian)流4路測量方式,高(gao)精度傳感器和(he)高(gao)性能14位(wei)AD采(cai)集芯(xin)片。
3. 人(ren)機(ji)對話(hua)全(quan)鍵盤操作方式(shi)(shi)(shi),智(zhi)能化工作全(quan)過程,任選自動方式(shi)(shi)(shi)和手動方式(shi)(shi)(shi)。
4. 實(shi)時顯示(shi)高(gao)壓(ya)電(dian)(dian)壓(ya)、高(gao)壓(ya)電(dian)(dian)流(liu)、低壓(ya)電(dian)(dian)壓(ya)、低壓(ya)電(dian)(dian)流(liu),時間及耐壓(ya)結果,顯示(shi)直觀明了。
5. 完善的過(guo)壓、過(guo)流保護(hu),任(ren)意(yi)設定輸出(chu)電(dian)壓、高壓電(dian)流上(shang)限、低壓電(dian)流上(shang)限和計時時間。
6. 具有回(hui)零(ling)檢(jian)測功能,回(hui)零(ling)確定后(hou)才可(ke)進行(xing)試驗,**可(ke)靠。
7. 具有絕(jue)緣電(dian)阻測試(shi)功能,直接反映被試(shi)品(pin)絕(jue)緣強(qiang)度。
8. 逼近式調壓(ya)算法,到達設(she)定電壓(ya)后自(zi)動(dong)耐(nai)壓(ya)計時,計時結(jie)束后自(zi)動(dong)降壓(ya)回(hui)零。
9. 超過設(she)定高(gao)壓電流或(huo)低壓電流時自動切斷電壓輸出,降壓回零,并發生聲光報警。
10. 精良(liang)的軟硬(ying)件抗干(gan)擾(rao)設計(ji),多種(zhong)抗干(gan)擾(rao)手(shou)段,適應惡劣電(dian)磁環境。
11. 自動(dong)錯誤診斷(duan),易于發現(xian)和解決問(wen)題。
12. 可選配無線遙(yao)控(kong)控(kong)制功能(neng)、遠程(cheng)通信、門(men)聯鎖(suo)警鈴(ling)、外接(jie)分壓器校驗接(jie)口(kou)等。
三、設備(bei)組成
1、選型(xing)配置
標(biao)準配置(zhi)
|
□ 分體式
|
操(cao)作部分:
□箱式(shi)(shi)(不大于5kVA) / □臺式(shi)(shi)
容量: kVA(小(xiao)于200kVA)
輸(shu)入:□AC220V / □AC380V
|
試驗變(bian)壓器:
□交流 / □交直(zhi)流
□油變 / □干變 / □氣變
容量: kVA(小于200kVA)
輸出:AC kV(小于300kVA)
|
□ 一體式
|
□箱式(不大于(yu)20kV) / □臺式(不大于(yu)30kV)
容量(liang): kVA(小于(yu)300kVA)
輸(shu)入:□AC220V / □AC380V 輸(shu)出(chu):AC kV(不大于30kV)
|
客戶選配
|
□標準高壓分壓器
|
□保護球隙(xi)
|
□直流微安表
|
□放**
|
□保護水(shui)阻
|
□高壓濾波電容
|
其(qi)它:
|
2、對應(ying)實物
四、技術指標
1、使(shi)用(yong)條件:
(1)工作場所(suo)應(ying)無嚴(yan)重影響(xiang)絕(jue)緣(yuan)的氣(qi)體(ti)、蒸汽(qi)、化學性(xing)塵埃及其(qi)它爆炸性(xing)和腐(fu)蝕性(xing)介質。
(2)環境(jing)溫度 -20~+50℃
(3)環境濕度 ≤85% RH(無(wu)凝結水(shui))
2、控制箱(臺)參數(shu):(常規參數(shu)見下表)
(1)計時范圍:0-999S
(3)電(dian)壓精度(du) ≤1.5% ±1個字(zi)(F.S)
(4)電流(liu)精度 ≤1.5% ±1個字(F.S)
規格
|
容(rong)量(liang)
|
輸 入 電(dian) 源
|
輸 出 電 壓
|
重(zhong)量(kg)
|
相(xiang)數
|
(V)
|
(A)
|
(V)
|
(A)
|
2/220
|
2
|
1
|
220
|
10
|
0-250
|
8
|
14
|
3/220
|
3
|
1
|
220
|
15
|
0-250
|
12
|
16
|
5/220
|
5
|
1
|
220
|
25
|
0-250
|
20
|
18
|
10/220
|
10
|
1
|
220
|
50
|
0-250
|
40
|
80
|
15/380
|
15
|
2
|
380
|
37.5
|
0-430
|
34.8
|
90
|
20/380
|
20
|
2
|
380
|
50
|
0-430
|
46.5
|
100
|
25/380
|
25
|
2
|
380
|
62.5
|
0-430
|
58.1
|
120
|
30/380
|
30
|
2
|
380
|
75
|
0-430
|
69.7
|
140
|
50/380
|
50
|
2
|
380
|
125
|
0-430
|
116.2
|
160
|
100/380
|
100
|
2
|
380
|
250
|
0-430
|
232.5
|
250
|
說明:如有特殊(shu)參數要求,可按用(yong)戶的技術參數進(jin)行設計制作。
3、試驗變壓器參數:(常規參數見下表)
規格
|
容量
kVA
|
低壓(ya)側
|
高(gao)壓側
|
高壓(ya)(ya)側(ce)(交直流變壓(ya)(ya)器)
|
測量變比
|
60分鐘溫升℃
|
阻抗電壓%
|
空載(zai)電流
%
|
質(zhi)量
kg
|
電(dian)壓
V
|
電流
A
|
交(jiao)流輸(shu)出
|
直流輸(shu)出
|
電(dian)壓kV
|
電流
|
電壓kV
|
電流
|
1.5/50
|
1.5
|
200
|
7.5
|
50
|
30
|
70
|
21.4
|
500
|
50
|
10
|
<4
|
19.5
|
3/50
|
3
|
200
|
15
|
50
|
60
|
70
|
42.9
|
500
|
50
|
10
|
<4
|
27
|
5/50
|
5
|
200
|
25
|
50
|
100
|
70
|
71.4
|
500
|
50
|
10
|
<4
|
52
|
10/50
|
10
|
200
|
50
|
50
|
200
|
70
|
142.9
|
500
|
50
|
10
|
<4
|
80
|
15/50
|
15
|
400
|
37.5
|
50
|
300
|
70
|
214.3
|
500
|
50
|
8
|
<4
|
120
|
20/50
|
20
|
400
|
50
|
50
|
400
|
70
|
285.7
|
500
|
50
|
8
|
<4
|
140
|
30/50
|
30
|
400
|
75
|
50
|
600
|
70
|
428.6
|
500
|
50
|
8
|
<4
|
155
|
50/50
|
50
|
400
|
125
|
50
|
1000
|
70
|
714.3
|
500
|
50
|
8
|
<4
|
184
|
10/100
|
10
|
200
|
50
|
100
|
100
|
140
|
71.4
|
1000
|
50
|
10
|
<4
|
135
|
15/100
|
15
|
400
|
37.5
|
100
|
150
|
140
|
107.1
|
1000
|
50
|
8
|
<4
|
150
|
20/100
|
20
|
400
|
50
|
100
|
200
|
140
|
142.9
|
1000
|
50
|
8
|
<4
|
215
|
30/100
|
30
|
400
|
75
|
100
|
300
|
140
|
214.3
|
1000
|
50
|
8
|
<4
|
250
|
50/100
|
50
|
400
|
125
|
100
|
500
|
140
|
357.1
|
1000
|
50
|
8
|
<4
|
290
|
10/150
|
10
|
200
|
50
|
100
|
66.7
|
140
|
47.6
|
1500
|
50
|
10
|
<4
|
180
|
15/150
|
15
|
400
|
37.5
|
150
|
100
|
210
|
71.4
|
1500
|
50
|
8
|
<4
|
200
|
20/150
|
30
|
400
|
50
|
150
|
133.3
|
210
|
95.2
|
1500
|
50
|
8
|
<4
|
220
|
30/150
|
30
|
400
|
75
|
150
|
200
|
210
|
142.9
|
1500
|
50
|
8
|
<4
|
280
|
50/150
|
50
|
400
|
125
|
150
|
333.3
|
210
|
238.1
|
1500
|
50
|
8
|
<4
|
340
|
說明:如有特(te)殊參數要求,可按用戶的技術參數進(jin)行設(she)計制作。
上表的(de)重量以油浸式(shi)試驗變壓器(qi)為例,干式(shi)試驗變壓器(qi)和充氣式(shi)試驗變壓器(qi)稍(shao)有不同。
五(wu)、接線及工作原(yuan)理(li)
1、調壓(ya)部分接線及原(yuan)理
調(diao)壓(ya)部分(fen)由控制部分(fen)和試驗變壓(ya)器組(zu)(zu)成。控制部分(fen)是由接觸式調(diao)壓(ya)器、單片機控制系(xi)統、液(ye)晶、打印機、信號測量、電路保護組(zu)(zu)成。試驗變壓(ya)器由低壓(ya)繞組(zu)(zu)、高壓(ya)繞組(zu)(zu)、儀表繞組(zu)(zu)三部分(fen)組(zu)(zu)成。
試(shi)驗變(bian)壓(ya)器為(wei)交(jiao)直流(liu)兩用(yong)時,試(shi)驗變(bian)壓(ya)器配置了高(gao)壓(ya)硅(gui)(gui)堆(dui)(油(you)變(bian)、氣變(bian)為(wei)內置,干(gan)變(bian)為(wei)外置),高(gao)壓(ya)可輸(shu)出交(jiao)流(liu)和直流(liu)。輸(shu)出交(jiao)流(liu)時,要求(qiu)接入(ru)短(duan)(duan)路桿(gan)(油(you)變(bian)、氣變(bian))或(huo)去掉外置硅(gui)(gui)堆(dui)(干(gan)變(bian));輸(shu)出直流(liu)時,要求(qiu)擰出短(duan)(duan)路桿(gan)(油(you)變(bian)、氣變(bian))或(huo)加(jia)上外置硅(gui)(gui)堆(dui)(干(gan)變(bian))
通過接入工頻(pin)電源(yuan),調節調壓(ya)器,以獲(huo)得(de)所需要的試(shi)驗高壓(ya)電壓(ya)值。其工作原理見圖1:
2、試驗部分(fen)接線及原理
做耐壓(ya)(ya)試(shi)驗(yan)時,控制部(bu)分、變壓(ya)(ya)器的接(jie)地端及高壓(ya)(ya)尾必須可靠接(jie)地。有(you)條件的情(qing)況下(xia),做工(gong)頻耐壓(ya)(ya)試(shi)驗(yan)請加(jia)上限流電阻、標準高壓(ya)(ya)分壓(ya)(ya)器、球(qiu)隙保護(hu)電阻及保護(hu)球(qiu)隙,如圖3。
做直(zhi)流(liu)(liu)耐(nai)壓(ya)試(shi)驗請(qing)另外加上微(wei)安表(biao),微(wei)安表(biao)必須(xu)接在(zai)(zai)硅(gui)堆(dui)和(he)被試(shi)器之間(jian),油(you)變(bian)或氣變(bian)一般(ban)擰(ning)在(zai)(zai)高(gao)壓(ya)頭上面(要求(qiu)擰(ning)出短路桿),干(gan)變(bian)擰(ning)在(zai)(zai)外置硅(gui)堆(dui)上面;為了(le)更準(zhun)確顯(xian)示(shi)高(gao)壓(ya)直(zhi)流(liu)(liu)泄漏電(dian)流(liu)(liu),請(qing)將分(fen)壓(ya)器的高(gao)壓(ya)線接在(zai)(zai)微(wei)安表(biao)和(he)硅(gui)堆(dui)之間(jian),(油(you)變(bian)、氣變(bian))如圖(tu)(tu)4,(干(gan)變(bian))如圖(tu)(tu)5。
耐(nai)壓(ya)試驗(yan)中限流電(dian)(dian)(dian)阻(zu)(zu)R1應(ying)根據(ju)試驗(yan)變壓(ya)器的(de)額(e)定(ding)容(rong)量(liang)(liang)來選擇。如高壓(ya)側額(e)定(ding)輸出電(dian)(dian)(dian)流在100~300mA時,可取0.5~1Ω/V(試驗(yan)電(dian)(dian)(dian)壓(ya));高壓(ya)側額(e)定(ding)輸出電(dian)(dian)(dian)流為(wei)1A以上時,可取1Ω/V(試驗(yan)電(dian)(dian)(dian)壓(ya))。常用(yong)水電(dian)(dian)(dian)阻(zu)(zu)作為(wei)限流電(dian)(dian)(dian)阻(zu)(zu),管子長度可按150kV/m考慮,管子粗細(xi)應(ying)具有足(zu)夠的(de)熱(re)容(rong)量(liang)(liang)(水阻(zu)(zu)液配制(zhi)(zhi)方法(fa):用(yong)蒸(zheng)餾水加入(ru)適(shi)量(liang)(liang)硫酸銅配制(zhi)(zhi)成各種(zhong)不同的(de)阻(zu)(zu)值(zhi))。
球(qiu)間(jian)隙及保(bao)護電(dian)阻:當電(dian)壓超過球(qiu)間(jian)隙整定值時(一(yi)般取試(shi)驗(yan)電(dian)壓的110%~120%),球(qiu)間(jian)隙放(fang)電(dian),對被試(shi)品起(qi)到(dao)保(bao)護作用(yong)。球(qiu)間(jian)隙保(bao)護電(dian)阻可按1Ω/V(試(shi)驗(yan)電(dian)壓)選取。
在(zai)工頻耐壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)試驗(yan)中,低(di)電(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)側(ce)測量(liang)電(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)(儀(yi)表(biao)電(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya))不是(shi)非(fei)常準確(que)的(de)(de),其(qi)原因(yin)是(shi)由于試驗(yan)變(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)器存(cun)在(zai)著漏抗,在(zai)這(zhe)個漏抗上必然(ran)存(cun)在(zai)著壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)降(jiang)或容升,使試品(pin)上的(de)(de)電(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)低(di)于或高(gao)于低(di)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)側(ce)測量(liang)電(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)表(biao)上反(fan)映出來(lai)的(de)(de)電(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)。工頻耐壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)試驗(yan)時,被(bei)試品(pin)上的(de)(de)電(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)高(gao)于試驗(yan)變(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)器的(de)(de)輸出電(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya),也(ye)就(jiu)是(shi)所謂容升現象。感應耐壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)試驗(yan)時,試驗(yan)變(bian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)器的(de)(de)漏抗必然(ran)存(cun)在(zai)著壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)降(jiang)。為了準確(que)測量(liang)被(bei)試品(pin)上所施加的(de)(de)電(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya),因(yin)此常在(zai)高(gao)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)側(ce)接入標(biao)準高(gao)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)分壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)器來(lai)測量(liang)電(dian)(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(ya)(ya)。
六、操作(zuo)要點(dian)
1、試(shi)(shi)驗(yan)前,應了解被(bei)試(shi)(shi)品(pin)(pin)的(de)試(shi)(shi)驗(yan)電壓,同時了解被(bei)試(shi)(shi)品(pin)(pin)的(de)其他試(shi)(shi)驗(yan)項(xiang)目及以(yi)前的(de)試(shi)(shi)驗(yan)結(jie)果。若被(bei)試(shi)(shi)品(pin)(pin)有缺陷或異常,應在消除(chu)后(hou)再進行耐壓試(shi)(shi)驗(yan)。
2、試驗(yan)現場應圍好遮攔或圍繩(sheng),掛好標(biao)示牌,并派專(zhuan)人監護。
3、試(shi)驗前,被(bei)(bei)試(shi)品表面應(ying)擦拭(shi)干凈,將被(bei)(bei)試(shi)品的(de)外殼和非被(bei)(bei)試(shi)繞(rao)組可靠接地。被(bei)(bei)試(shi)品為新沖油設(she)備時(shi),應(ying)按《規(gui)程(cheng)》規(gui)定(ding)使油靜止一定(ding)時(shi)間(jian)(jian)再(zai)升壓,對110kV及以下的(de)充(chong)油電力(li)設(she)備,在(zai)注滿油后靜置時(shi)間(jian)(jian)應(ying)不少于24小(xiao)時(shi),對220kV及330kV的(de)充(chong)油電力(li)設(she)備,靜置時(shi)間(jian)(jian)應(ying)不少于48小(xiao)時(shi)。
4、接好試驗(yan)接線后,應由有經驗(yan)的人員檢查,確認無誤后方(fang)可升壓。
5、升壓(ya)前,首(shou)先檢(jian)查調(diao)壓(ya)器(qi)是否(fou)在零位。調(diao)壓(ya)器(qi)在零位方可升壓(ya)。
6、升壓(ya)過程中不(bu)(bu)(bu)僅要(yao)監(jian)視電壓(ya)的(de)變化(hua),還應監(jian)視電流(liu)的(de)變化(hua),以及被試(shi)品泄漏(lou)電流(liu)的(de)變化(hua)。升壓(ya)時(shi)(shi)要(yao)均(jun)(jun)勻升壓(ya),不(bu)(bu)(bu)能太快。升至規(gui)定試(shi)驗電壓(ya)時(shi)(shi),開(kai)始計(ji)時(shi)(shi),時(shi)(shi)間到后(hou),緩慢均(jun)(jun)勻降(jiang)下(xia)電壓(ya)。絕不(bu)(bu)(bu)允許不(bu)(bu)(bu)降(jiang)壓(ya)就先跳開(kai)電源開(kai)關。
7、試(shi)驗(yan)中發現被試(shi)品有異常聲響、冒煙等應(ying)立(li)即(ji)降下電壓,拉開(kai)電源,在高壓側掛上(shang)接地(di)線后,再查(cha)明(ming)原因。耐(nai)壓試(shi)驗(yan)前后均(jun)應(ying)測(ce)量被試(shi)品的絕緣電阻(zu)。
七、面(mian)板(ban)功能說明
打(da)(da)印機:打(da)(da)印機是(shi)熱(re)敏打(da)(da)印機,當試驗完(wan)成后按鍵盤上的“打(da)(da)印”按鈕打(da)(da)印試驗結果。
RS232:RS232是與計算機相(xiang)連(lian)的串口(kou)通信接(jie)(jie)(jie)口(kou),是用(yong)戶(hu)選(xuan)配(pei)接(jie)(jie)(jie)口(kou),本裝置(zhi)沒有配(pei)置(zhi)這個接(jie)(jie)(jie)口(kou)。
LCD對比(bi)度(du)(du):因為液晶顯示屏(ping)在(zai)溫度(du)(du)和(he)光線有所不同時稍(shao)有些變化,可以通過LCD對比(bi)度(du)(du)調節背(bei)光到適合亮度(du)(du)。
液(ye)晶(jing): 320x240像(xiang)素(su)點陣白色背光液(ye)晶(jing),在強光和陰暗(an)環境下都十分(fen)清楚。
指示(shi)燈:由啟動燈、零(ling)位(wei)燈、指示(shi)燈三個燈組成,啟動燈和警示(shi)燈是高亮七彩燈。
操作提示:有一(yi)些簡(jian)短的提示語句(ju)和安裝接(jie)線圖。
緊急(ji)開關(guan):在(zai)(zai)緊急(ji)情況(kuang)下(xia)按此開關(guan),即可以切(qie)斷變(bian)壓器電源,也可以切(qie)斷工作電源。(箱式(shi)安裝(zhuang)(zhuang)在(zai)(zai)面板上,臺式(shi)安裝(zhuang)(zhuang)在(zai)(zai)柜體上)
鍵盤:由上(shang)、下(xia)、左、右(you)、設置、打印、確定(ding)、取(qu)消8個(ge)鍵組(zu)成,是用戶和設備(bei)交互的(de)終端。
電(dian)(dian)源開關:工作電(dian)(dian)源,帶通電(dian)(dian)指示(shi)燈。
八、軟件使用說明
按試(shi)驗(yan)要求(qiu)將控制部分(fen)、試(shi)驗(yan)變壓器、被試(shi)品正確接(jie)好線,必(bi)須可靠接(jie)地,請參考圖(tu)(tu)1、圖(tu)(tu)2、圖(tu)(tu)3、圖(tu)(tu)4、圖(tu)(tu)5。
1、開機使(shi)用
開(kai)機處于(yu)“歡迎界(jie)面”,如圖(tu)7:
根(gen)據鍵盤的示圖8,按上↑、下↓、左←,右→可以切換“自動耐壓(ya)試驗(yan)(yan)”或“手(shou)動耐壓(ya)試驗(yan)(yan)”,在“自動試驗(yan)(yan)”或“手(shou)動試驗(yan)(yan)”里(li)面選擇“交(jiao)流(liu)試驗(yan)(yan)方式”或“直流(liu)試驗(yan)(yan)方式”。如圖9
說(shuo)明:
(1)當配(pei)置的是(shi)交直(zhi)(zhi)流兩用控制部分時,使用直(zhi)(zhi)流輸(shu)出時軟件操(cao)(cao)作請進入(ru)直(zhi)(zhi)流試驗(yan)方式,交流輸(shu)出時軟件操(cao)(cao)作請進入(ru)交流試驗(yan)方式,如果選擇錯誤會導致儀器顯示(shi)電壓會和輸(shu)出實際電壓不(bu)一致。
(2)當配置的(de)是交直(zhi)流兩用變壓(ya)器時,使用直(zhi)流時請將(jiang)變壓(ya)器的(de)短路桿取出,當使用交流時請將(jiang)短路桿插入擰(ning)緊(jin)。
(3)如(ru)果配置(zhi)的(de)是交流控制部分時,軟(ruan)件界面里就(jiu)沒(mei)有交直流試驗方式(如(ru)圖9)的(de)選擇項(xiang)。
選中試驗方式后(hou),按確定可以進入主界面(mian),如圖10:
動態顯(xian)(xian)示區:一直處于(yu)采(cai)集信號,并顯(xian)(xian)示高壓(ya)電(dian)壓(ya)、高壓(ya)電(dian)流、低(di)壓(ya)電(dian)壓(ya)、低(di)壓(ya)電(dian)流。
結果(guo)顯示(shi)區:如果(guo)試驗沒有(you)被擊穿時,顯示(shi)平(ping)均高(gao)壓(ya)(ya)電壓(ya)(ya),平(ping)均高(gao)壓(ya)(ya)電流(liu),平(ping)均低(di)(di)壓(ya)(ya)電壓(ya)(ya),平(ping)均低(di)(di)壓(ya)(ya)電流(liu),絕緣電阻;否之(zhi),顯示(shi)峰值電壓(ya)(ya),峰值電流(liu),低(di)(di)壓(ya)(ya)電壓(ya)(ya),低(di)(di)壓(ya)(ya)電流(liu)。
設(she)置數據(ju)區:設(she)置試驗中需要的(de)參數數據(ju)輸出(chu)電(dian)壓(ya)(ya)為(wei)(wei)在自(zi)動(dong)方式下的(de)升壓(ya)(ya)目標耐(nai)壓(ya)(ya)值耐(nai)壓(ya)(ya)時間為(wei)(wei)耐(nai)壓(ya)(ya)過(guo)程(cheng)的(de)時間長度電(dian)流(liu)(liu)上限(xian)為(wei)(wei)高壓(ya)(ya)電(dian)流(liu)(liu)峰(feng)值的(de)上限(xian),高壓(ya)(ya)電(dian)流(liu)(liu)超過(guo)電(dian)流(liu)(liu)上限(xian)將認(ren)為(wei)(wei)擊穿過(guo)流(liu)(liu)保(bao)護為(wei)(wei)低壓(ya)(ya)電(dian)流(liu)(liu)峰(feng)值的(de)上限(xian),低壓(ya)(ya)電(dian)流(liu)(liu)超過(guo)過(guo)流(liu)(liu)保(bao)護將認(ren)為(wei)(wei)擊穿
信(xin)息顯(xian)示區:顯(xian)示試驗過程中(zhong)的試驗狀態和提示信(xin)息。
試驗(yan)操作區(qu):選擇設置、試驗(yan)、回零命令。
2、設置參數
在主界面上,選中“設置”,然后按確定后進入設置界面,如(ru)圖11:
按(an)左←,右(you)→時(shi)切換光(guang)標移動位(wei)置,按(an)上(shang)↑、下↓時(shi)更改光(guang)標位(wei)置數(shu)據(ju)的值(zhi)。光(guang)標位(wei)置和設置的數(shu)值(zhi)全部可以自動循環,前且(qie)在使用時(shi)有默認(ren)的標準值(zhi)。如果所有的參(can)數(shu)都(dou)設置完(wan)成,按(an)取消退出設置回到主(zhu)界面開(kai)始狀態。
3、手動試(shi)驗(yan)
零位檢查—當(dang)選中“試(shi)驗(yan)”后,按確定就進入提示(shi)試(shi)驗(yan)狀(zhuang)態。如(ru)果調(diao)壓器(qi)不在零位,將提示(shi)“試(shi)驗(yan)前(qian)請先(xian)回(hui)零”,退(tui)出試(shi)驗(yan)并(bing)且切(qie)換到回(hui)零命令(ling)。
試驗過程—回零確(que)認后,可以(yi)進行試驗。選中“試驗”后按確(que)定,接觸器合閘,這時輸出電(dian)壓(ya)幾乎(hu)為0,如圖12:
按上↑,高壓(ya)電壓(ya)將不斷(duan)升(sheng)壓(ya),松開就停(ting)止升(sheng)壓(ya),如果到上限就提示滿量程;
按下(xia)↓,高壓(ya)電壓(ya)將不斷降(jiang)壓(ya),松開就(jiu)停止降(jiang)壓(ya),如果(guo)到(dao)下(xia)限就(jiu)提示已回零;
按計(ji)時←,計(ji)時開(kai)始工作,到耐壓時間(jian)計(ji)時結束完成(cheng)試驗;
按取(qu)消→,取(qu)消試驗過程;
在升壓(ya)(ya)(ya)過(guo)程(cheng)中,如果(guo)高(gao)(gao)壓(ya)(ya)(ya)電(dian)(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu)(liu)(liu)峰(feng)(feng)值(zhi)(zhi)超(chao)過(guo)“電(dian)(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu)(liu)(liu)上限”值(zhi)(zhi)或低壓(ya)(ya)(ya)電(dian)(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu)(liu)(liu)峰(feng)(feng)值(zhi)(zhi)超(chao)過(guo)“過(guo)流(liu)(liu)(liu)(liu)(liu)(liu)(liu)保護”值(zhi)(zhi)將認為被(bei)試(shi)(shi)品被(bei)擊(ji)穿(chuan),接觸(chu)器(qi)(qi)立刻分(fen)(fen)閘并(bing)顯示(shi)試(shi)(shi)驗(yan)結(jie)果(guo),包括峰(feng)(feng)值(zhi)(zhi)電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)、峰(feng)(feng)值(zhi)(zhi)電(dian)(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu)(liu)(liu)、低壓(ya)(ya)(ya)電(dian)(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu)(liu)(liu)等(deng),調(diao)壓(ya)(ya)(ya)器(qi)(qi)開(kai)始回(hui)零(ling)(ling),回(hui)零(ling)(ling)完成試(shi)(shi)驗(yan)結(jie)束。如果(guo)在耐壓(ya)(ya)(ya)過(guo)程(cheng)中,高(gao)(gao)壓(ya)(ya)(ya)電(dian)(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu)(liu)(liu)和低壓(ya)(ya)(ya)電(dian)(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu)(liu)(liu)峰(feng)(feng)值(zhi)(zhi)沒有超(chao)設置上限值(zhi)(zhi),認為被(bei)試(shi)(shi)品未(wei)擊(ji)穿(chuan),結(jie)果(guo)顯示(shi)區就顯示(shi)耐壓(ya)(ya)(ya)電(dian)(dian)(dian)(dian)壓(ya)(ya)(ya)、高(gao)(gao)壓(ya)(ya)(ya)電(dian)(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu)(liu)(liu)、低壓(ya)(ya)(ya)電(dian)(dian)(dian)(dian)流(liu)(liu)(liu)(liu)(liu)(liu)(liu)、絕緣電(dian)(dian)(dian)(dian)阻等(deng),調(diao)壓(ya)(ya)(ya)器(qi)(qi)開(kai)始回(hui)零(ling)(ling),回(hui)零(ling)(ling)完成后接觸(chu)器(qi)(qi)分(fen)(fen)閘試(shi)(shi)驗(yan)結(jie)束。
4、自動試(shi)驗
自動試驗和手動試驗的(de)試驗過程類似(si),首先也進行回(hui)零檢查(cha),確認后進入(ru)如下界(jie)面,如圖13:
按上方法切換到“開始”確定后進(jin)行試驗(yan),與手動(dong)試驗(yan)不同之處就是升壓過(guo)程(cheng)將自(zi)動(dong)升壓到“輸出電(dian)壓”值,然后進(jin)行計時。
升壓(ya)過程為(wei)逼近方式,首先升到到接近目標(biao)值,然(ran)后再進行(xing)微調,保(bao)證高壓(ya)電(dian)壓(ya)值幾乎為(wei)輸出(chu)電(dian)壓(ya)值。
5、功(gong)能選擇
按鍵(jian)盤上(shang)的“設置”就進入(ru)功能界面,如圖(tu)14:
進入功能界面后,可以選擇“時(shi)鐘設(she)置”、“注意事項”等界面。
時(shi)鐘(zhong)設置(zhi):設置(zhi)時(shi)鐘(zhong)的時(shi)間(jian),為打印報表提供時(shi)間(jian)依據(ju)。
注意(yi)(yi)事項(xiang):為用戶(hu)提供一(yi)些操作規范和**注意(yi)(yi)事項(xiang)。
6、打印
按(an)鍵盤“打(da)印(yin)”按(an)鍵可以打(da)印(yin)試(shi)驗果,在此不贅述。
七(qi)、產(chan)品維護
1、開箱驗收時,應檢查主控回路接(jie)線(xian)是否松(song)動,調壓器(qi)電刷是否接(jie)觸良好。
2.、長期(qi)不用時(shi),使(shi)用前應用500V兆(zhao)歐表測量(liang)絕緣電阻(zu),其阻(zu)值不低于0.5MΩ。
3、電源電壓應(ying)符(fu)合控制箱(臺)說明書上的輸入(ru)電壓值要求。
4、本(ben)控制箱(臺)設(she)有(you)過(guo)電(dian)(dian)流保護,出廠已調整為額定(ding)電(dian)(dian)流的50%。用(yong)于小負載時,應根(gen)據被(bei)試品的額定(ding)容量(liang)電(dian)(dian)流重新設(she)定(ding);
5、使用完(wan)畢后,應關好(hao)控制箱(臺)門蓋,以保持內部清潔。
八、注(zhu)意事項
1、按照您(nin)所進行的(de)試(shi)驗(yan)接好工作(zuo)線路。試(shi)驗(yan)變壓器的(de)外殼(ke)以及操(cao)作(zuo)系統的(de)外殼(ke)必須可靠接地。試(shi)驗(yan)變壓器的(de)測量繞組(zu)的(de)F端和外殼(ke)必須可靠接地。
2、做(zuo)串(chuan)級(ji)試驗時,**級(ji)、第三級(ji)試驗變壓器的(de)低(di)壓繞(rao)組成X端(duan)(duan)(duan),測(ce)量繞(rao)組的(de)F端(duan)(duan)(duan)以及高(gao)壓繞(rao)組的(de)X端(duan)(duan)(duan)(高(gao)壓端(duan)(duan)(duan))均接(jie)本級(ji)試驗變壓器具外(wai)殼(ke)。**級(ji)、第三級(ji)試驗變壓器的(de)外(wai)殼(ke)必(bi)須通過(guo)絕緣支架接(jie)地。
接通電源前,控制箱(臺)的調壓(ya)器必須(xu)調到零位后方可接通電源,合閘,開始升壓(ya)。
3、從零開始(shi)勻速(su)旋轉調壓(ya)(ya)(ya)器手(shou)輪升壓(ya)(ya)(ya)。升壓(ya)(ya)(ya)方(fang)式有:快速(su)升壓(ya)(ya)(ya)法,即20s逐(zhu)級升壓(ya)(ya)(ya)法;慢速(su)升壓(ya)(ya)(ya)法,即60s逐(zhu)級升壓(ya)(ya)(ya)法;極(ji)慢速(su)升壓(ya)(ya)(ya)法供選用。電(dian)壓(ya)(ya)(ya)從零開始(shi)按(an)一定的(de)(de)升壓(ya)(ya)(ya)方(fang)式和速(su)度(du)(du)上升到您(nin)(nin)所需的(de)(de)額(e)定試(shi)驗電(dian)壓(ya)(ya)(ya)的(de)(de)75%后,再以(yi)每(mei)秒2%額(e)定試(shi)驗電(dian)壓(ya)(ya)(ya)的(de)(de)速(su)度(du)(du)升到您(nin)(nin)所需的(de)(de)試(shi)驗電(dian)壓(ya)(ya)(ya),并密切(qie)注(zhu)意測(ce)(ce)量儀表(biao)的(de)(de)及(ji)被試(shi)品的(de)(de)情況(kuang)。升壓(ya)(ya)(ya)過(guo)程(cheng)中或試(shi)驗過(guo)程(cheng)中如發現測(ce)(ce)量儀表(biao)的(de)(de)指示(shi)及(ji)被試(shi)品情況(kuang)異常(chang),應(ying)立即降壓(ya)(ya)(ya),切(qie)斷(duan)電(dian)源(yuan),查(cha)明(ming)情況(kuang)。
4、試(shi)驗完畢后(hou),應在等調壓(ya)器返(fan)回至零(ling)位,然后(hou)切斷電源。
5、本產品(pin)不得超過額定參數使用。
6、使用本產品做高壓試驗時,除熟悉本說明書外(wai),還必須(xu)嚴格(ge)執行國家有關標(biao)準和操作規程。可參(can)照(zhao)GB311.1 – 97《高壓輸(shu)變設備(bei)的絕緣配(pei)合,高壓試驗技術》;《電(dian)氣設備(bei)預(yu)防(fang)性試驗規程》等。
7、控(kong)(kong)制(zhi)箱(xiang)(臺(tai))應(ying)與試驗變壓器(qi)配套使用,控(kong)(kong)制(zhi)箱(xiang)(臺(tai))的使用方(fang)法,請詳細參閱控(kong)(kong)制(zhi)器(qi)的使用說明(ming)書。