一、WBYD2000串聯諧振耐壓機基本原理
耐壓試(shi)驗是利用電(dian)抗器的(de)電(dian)感與被試(shi)品電(dian)容組成LC串聯回路,調節變頻電(dian)源輸出的(de)電(dian)壓頻率,在被試(shi)品上獲得高電(dian)壓,是當前高電(dian)壓試(shi)驗的(de)一(yi)種新(xin)方法,深受專家好評,在國內外(wai)已經得到廣泛的(de)使用。
根據諧振原(yuan)理,我們知道當電(dian)(dian)抗(kang)器(qi)L的感(gan)抗(kang)值Xl與(yu)回(hui)(hui)路中的容抗(kang)值Xc相等時(shi),回(hui)(hui)路達到諧振狀態,此時(shi)回(hui)(hui)路中僅(jin)回(hui)(hui)路電(dian)(dian)阻(zu)R消耗(hao)有功(gong)功(gong)率,而無功(gong)功(gong)率則在電(dian)(dian)抗(kang)器(qi)與(yu)試品(pin)電(dian)(dian)容之間來回(hui)(hui)振蕩(dang),從而在試品(pin)上產生高壓。
二、WBYD2000串聯諧振耐壓機系統構成
全套試驗(yan)系統由調頻電源主機、電抗器(qi)(qi)、分壓器(qi)(qi)、激勵變壓器(qi)(qi)和(he)補償電容(rong)器(qi)(qi)(可選(xuan)器(qi)(qi)件)組成,接(jie)入被試品后組成一個(ge)諧振(zhen)系統進行交(jiao)流耐壓實(shi)驗(yan)。
主機: 就是一臺幅值和頻(pin)率可(ke)調(diao)(diao)的正弦波(bo)交流調(diao)(diao)頻(pin)電(dian)源(yuan),給諧振(zhen)回路提(ti)供激勵源(yuan),同時提(ti)供電(dian)壓顯(xian)示、電(dian)流顯(xian)示、計時、保護(hu)、報(bao)警(jing)等功能(neng)。
電(dian)(dian)(dian)抗(kang)(kang)器(qi):就是一個大電(dian)(dian)(dian)感線圈(quan),與被試品(pin)(相當于電(dian)(dian)(dian)容(rong))構成回路(lu),可配(pei)置電(dian)(dian)(dian)抗(kang)(kang)器(qi)多節電(dian)(dian)(dian)抗(kang)(kang)器(qi),使用時通過(guo)不(bu)同的(de)串聯、并聯組合(he)、實現不(bu)同的(de)電(dian)(dian)(dian)感量以適用不(bu)同的(de)試驗條(tiao)件(jian)。
分(fen)壓器:內(nei)部(bu)通過電容器分(fen)壓,從試品上高電壓分(fen)得低(di)電壓供主機測量、控制使用(yong)。
勵磁變壓(ya)器:隔離主(zhu)機電源與諧振(zhen)回路電源,并升高主(zhu)機的輸出電壓(ya)。
補(bu)償(chang)電(dian)(dian)容(rong)(rong)(rong)器(qi):當試(shi)品電(dian)(dian)容(rong)(rong)(rong)量很小時,如果要(yao)實現系統諧(xie)振(zhen)可(ke)能要(yao)求(qiu)的電(dian)(dian)源頻率超出試(shi)驗標準的規(gui)定(ding),可(ke)在試(shi)品上并聯一個(ge)補(bu)償(chang)電(dian)(dian)容(rong)(rong)(rong),以實現試(shi)驗要(yao)求(qiu),稱此電(dian)(dian)容(rong)(rong)(rong)器(qi)為(wei)補(bu)償(chang)電(dian)(dian)容(rong)(rong)(rong)器(qi)。
三、WBYD2000串聯諧振耐壓機主要技術性能
功(gong)率電源電壓(ya):AC380V±10%、50Hz;
儀器(qi)電源:220V±10%、50Hz;
諧振輸出容量(liang):200kVA;
儀器(qi)額定電壓:0~200kV;
輸出頻率范圍:30~300Hz;
輸出電(dian)壓波(bo)形:正(zheng)弦波(bo),波(bo)形畸變(bian)率(lv)<0.5%;
頻率調節靈敏度:0.1Hz,不穩定度≤0.05%;
系統噪聲(sheng):≤60db;
9、系統測量精度(du):<1級;
10.輸出電壓不(bu)穩定:<0.5%;
11.保護響(xiang)應時間:1us;
12.電感非線性(xing)度:≤0.05%;;
13.滿功率輸出下,連(lian)續工作時間(jian)為(wei)60min
14.環境溫(wen)度:-15℃~+50℃;
15.相對濕(shi)度:≤90%RH;
16.海拔高度:≤2000米。
四、WBYD2000串聯諧振耐壓機面板及部件名稱
五、WBYD2000串聯諧振耐壓機操作步驟
1、正(zheng)確(que)連(lian)線(xian),檢查無誤(wu)后方可送電。
必要時工(gong)作電源(yuan)的(de)跳過現場漏電保(bao)安器,以免不必要的(de)跳閘。
2、打開(kai)電源(yuan)開(kai)關,主機開(kai)始工作,液(ye)晶(jing)屏顯(xian)示版權頁,該頁標明(ming)本裝(zhuang)置的軟件版本號。
觸按(an)確認(ren)鍵(jian),進(jin)入(ru)系統菜單,該主菜單下有:試驗方案(an)、開(kai)始試驗、試驗幫助、系統設置、實(shi)用工具和試驗記錄(lu)等六個(ge)子菜單項。
3、 系統設(she)(she)置(zhi)菜(cai)單(dan)下有電(dian)(dian)抗(kang)器電(dian)(dian)感、日期時間設(she)(she)置(zhi)和(he)采(cai)樣系數(shu)設(she)(she)置(zhi)等三個子(zi)菜(cai)單(dan)項。按上(shang)下鍵(jian),上(shang)下移(yi)動(dong)光標(biao)系統參數(shu)設(she)(she)置(zhi)菜(cai)單(dan)項,觸按確(que)定鈕(niu)后,進入系統參數(shu)設(she)(she)置(zhi)菜(cai)單(dan),可以分別設(she)(she)定電(dian)(dian)抗(kang)器的電(dian)(dian)感—H、-年-月-日、-時-分-秒和(he)電(dian)(dian)壓和(he)電(dian)(dian)流的采(cai)樣系數(shu)也(ye)就是(shi)采(cai)樣倍率,設(she)(she)定完成后,觸按返還鍵(jian)返回上(shang)**菜(cai)單(dan)。
電抗(kang)器電感量的(de)設定:按(an)確定鍵選擇到此項,按(an)左右鍵移動光標需要(yao)改變的(de)數位(wei),按(an)上下鍵改變數值(zhi),達到所要(yao)達到的(de)數值(zhi)按(an)確定鍵確認。
日(ri)期(qi)時間(jian)的(de)設(she)定(ding):按(an)(an)確定(ding)鍵(jian)(jian)(jian)選擇到此項(xiang),按(an)(an)左右(you)鍵(jian)(jian)(jian)移(yi)動光標需要改變的(de)數位,按(an)(an)上下鍵(jian)(jian)(jian)改變數值,按(an)(an)照所要設(she)置的(de)年月日(ri)時間(jian)數值按(an)(an)確定(ding)鍵(jian)(jian)(jian)確認。
采樣(yang)系(xi)數(shu)的(de)設(she)(she)定(ding):按確(que)定(ding)鍵(jian)選(xuan)擇到高壓/電流采樣(yang)系(xi)數(shu)項(xiang)(xiang),此項(xiang)(xiang)為(wei)電壓或電流采樣(yang)倍率的(de)設(she)(she)定(ding)。一般出廠(chang)前設(she)(she)定(ding)好了。如需修改,要輸入密碼(ma)。(密碼(ma)廠(chang)家與設(she)(she)備一起提(ti)供一般設(she)(she)定(ding)為(wei):188888)
警告(gao):系(xi)統默認上一次電(dian)(dian)抗(kang)器電(dian)(dian)感、日期時間和采(cai)樣(yang)系(xi)數設(she)(she)定值。如果需改變要重新(xin)設(she)(she)定。電(dian)(dian)抗(kang)器電(dian)(dian)感量(liang)設(she)(she)定值與實際使(shi)用的電(dian)(dian)抗(kang)器電(dian)(dian)感量(liang)不(bu)對,會導致試(shi)驗(yan)報告(gao)中(zhong)的被試(shi)品(pin)電(dian)(dian)容量(liang)不(bu)準(zhun)。其他并不(bu)會影響。采(cai)樣(yang)系(xi)數設(she)(she)置不(bu)正(zheng)確,會導致顯示電(dian)(dian)壓電(dian)(dian)流不(bu)準(zhun)將很有可能會對被試(shi)品(pin)或試(shi)驗(yan)設(she)(she)備(bei)造成損壞。
4、試驗(yan)方案菜(cai)單下有預置保護(hu)電流、找(zhao)頻(pin)(pin)起始(shi)頻(pin)(pin)率(lv)(lv)、找(zhao)頻(pin)(pin)結束(shu)頻(pin)(pin)率(lv)(lv)、預定(ding)(ding)起始(shi)功(gong)率(lv)(lv)四(si)個子(zi)菜(cai)單項,分別設(she)定(ding)(ding)本次(ci)試驗(yan)的保護(hu)電流、找(zhao)頻(pin)(pin)起始(shi)頻(pin)(pin)率(lv)(lv)、找(zhao)頻(pin)(pin)結束(shu)頻(pin)(pin)率(lv)(lv)、輸出起始(shi)功(gong)率(lv)(lv),全部設(she)定(ding)(ding)完成(cheng)后(hou),觸按(an)返還鍵進入預置試驗(yan)電壓(ya)和預置試驗(yan)時(shi)間設(she)置菜(cai)單。
可以分3段時間設置試(shi)(shi)驗(yan)電壓和試(shi)(shi)驗(yan)時間, 實(shi)際試(shi)(shi)驗(yan)時,若(ruo)設定為(wei)自動試(shi)(shi)驗(yan), 裝置將(jiang)按(an)設定的3段電壓及時間,按(an)順序分別加(jia)壓, 全部(bu)完成(cheng)后自動退出.
如果**段(duan)電(dian)壓設為0, 或時(shi)間設為0, 那么(me)執行(xing)完**段(duan)試驗電(dian)壓加壓后退(tui)出試驗, 只加壓**段(duan)設定的(de)電(dian)壓.
如(ru)果第三段(duan)(duan)電壓設為(wei)0, 或時間設為(wei)0, 不執行(xing)第三段(duan)(duan)加壓.
試(shi)(shi)驗方(fang)案設(she)置的(de)(de)(de)(de)設(she)定:在(zai)試(shi)(shi)驗電壓項中(zhong),按確(que)定單(dan)鈕(niu)(niu),移動左右光標(biao)到需要改(gai)變的(de)(de)(de)(de)數(shu)位(wei),按上(shang)下單(dan)鈕(niu)(niu)以改(gai)變當前數(shu)位(wei)的(de)(de)(de)(de)數(shu)值大小,觸按返回鈕(niu)(niu)完成(cheng)當前數(shu)位(wei)的(de)(de)(de)(de)數(shu)值設(she)定,依次選擇下一項數(shu)值的(de)(de)(de)(de)設(she)定,直至分別完成(cheng)試(shi)(shi)驗時間、起(qi)始(shi)頻率、起(qi)始(shi)功率的(de)(de)(de)(de)設(she)置,方(fang)可完成(cheng)本(ben)次試(shi)(shi)驗的(de)(de)(de)(de)試(shi)(shi)驗方(fang)案設(she)置的(de)(de)(de)(de)設(she)定。
出廠(chang)默認(ren)值:試驗(yan)電壓 20kV、加壓時間 2min、激勵強度 2%、輸出電流(liu)20A、頻率范(fan)圍30-300Hz。
5、實用工具菜單下有
頻率(lv)計(ji)算:在實驗前可對諧(xie)振頻率(lv)進行計(ji)算。只需輸入(ru)具(ju)體參與(yu)試驗的(de)電感、電容值并按確定鍵試驗頻率(lv)即直接生(sheng)成。
6、開(kai)始試驗菜單下有自動試驗模式和手動試驗模式兩種(zhong)子(zi)菜單可供選擇。
按確(que)認鍵進入所(suo)選試驗步驟.
自(zi)動(dong)試驗模式的(de)(de)操(cao)作:選中自(zi)動(dong)試驗模式后,觸按菜單鈕進入正在(zai)自(zi)動(dong)尋(xun)找(zhao)諧振點(dian)(dian)(dian)(dian)菜單項,裝置(zhi)在(zai)設定(ding)的(de)(de)頻(pin)率(lv)范(fan)圍內(nei)(nei)自(zi)動(dong)尋(xun)找(zhao)諧振點(dian)(dian)(dian)(dian)(如(ru)果被試品電容C和電抗器電感L的(de)(de)實(shi)際諧振頻(pin)率(lv)不在(zai)設定(ding)的(de)(de)頻(pin)率(lv)范(fan)圍內(nei)(nei),將找(zhao)不到諧振點(dian)(dian)(dian)(dian),此(ci)時根據需(xu)要調整頻(pin)率(lv)范(fan)圍或調整被試品回路(lu)的(de)(de)LC參數)。當(dang)找(zhao)到諧振點(dian)(dian)(dian)(dian)時,會有聲音提示(shi)。
找到諧振點后,裝置(zhi)自動(dong)進入正在自動(dong)升壓菜單項,當升到試(shi)驗(yan)電(dian)壓設定(ding)的電(dian)壓時,裝置(zhi)停(ting)止加壓。
當(dang)裝(zhuang)置(zhi)升到試(shi)驗(yan)電壓(ya)(ya)設定(ding)的(de)電壓(ya)(ya)時(shi)(shi),設備停止加(jia)壓(ya)(ya),自(zi)(zi)動進(jin)入(ru)(ru)正在加(jia)壓(ya)(ya)試(shi)驗(yan)菜單(dan)項,并自(zi)(zi)動記(ji)錄試(shi)驗(yan)的(de)加(jia)壓(ya)(ya)時(shi)(shi)間,當(dang)加(jia)壓(ya)(ya)時(shi)(shi)間到達(da)設定(ding)時(shi)(shi)間時(shi)(shi),設備逐步(bu)降壓(ya)(ya)退(tui)出(chu)試(shi)驗(yan),完(wan)成本次(ci)試(shi)驗(yan),進(jin)入(ru)(ru)試(shi)驗(yan)結束菜單(dan)項。并可(ke)選(xuan)擇保存試(shi)驗(yan)數據(ju)或(huo)打印試(shi)驗(yan)數據(ju)。
試(shi)驗時間的(de)一行顯(xian)示末端,會顯(xian)示[一段]或[二段]或[三段]字樣(yang),表示當前正在進行的(de)加壓試(shi)驗是預置(zhi)的(de)一段,二段或三段.
手(shou)(shou)動(dong)試(shi)驗模(mo)式的(de)(de)操作:選中手(shou)(shou)動(dong)試(shi)驗模(mo)式后觸(chu)按(an)確(que)定鈕(niu),進入正在(zai)試(shi)驗菜(cai)單項;手(shou)(shou)動(dong)按(an)調(diao)(diao)頻鈕(niu),對應的(de)(de)光標隨(sui)之改(gai)變到(dao)輸出(chu)頻率(lv)(lv)(lv)項,可以通過上下(xia)左右鍵改(gai)變頻率(lv)(lv)(lv)大小使其試(shi)驗電(dian)壓逐(zhu)步升(sheng)高,當升(sheng)到(dao)*高電(dian)壓時,繼續向上或向下(xia)調(diao)(diao)整頻率(lv)(lv)(lv)按(an)鈕(niu),直至試(shi)驗電(dian)壓開(kai)始下(xia)降;這時反調(diao)(diao)頻率(lv)(lv)(lv),試(shi)驗電(dian)壓又逐(zhu)步回升(sheng),上下(xia)回調(diao)(diao)頻率(lv)(lv)(lv),從頻率(lv)(lv)(lv)的(de)(de)高位(wei)到(dao)低(di)位(wei)逐(zhu)位(wei)調(diao)(diao)整*高電(dian)壓值(zhi)時的(de)(de)頻率(lv)(lv)(lv)就是當前的(de)(de)諧振頻率(lv)(lv)(lv)。
找(zhao)到(dao)諧振點后(hou),手(shou)動按電(dian)壓(ya)(ya)(ya)(ya)鈕,光標(biao)到(dao)了輸出功率(lv),隨(sui)之按上下鍵(jian)增加輸出功率(lv),試(shi)驗(yan)(yan)(yan)電(dian)壓(ya)(ya)(ya)(ya)也逐步升高,當升到(dao)試(shi)驗(yan)(yan)(yan)電(dian)壓(ya)(ya)(ya)(ya)設定電(dian)壓(ya)(ya)(ya)(ya)值(zhi)時(shi)(shi),裝置停止加壓(ya)(ya)(ya)(ya),并有屏幕顯(xian)示(shi)提示(shi)和聲(sheng)音提示(shi);自動進入(ru)正在加壓(ya)(ya)(ya)(ya)試(shi)驗(yan)(yan)(yan)菜(cai)單項,并自動記(ji)錄試(shi)驗(yan)(yan)(yan)的加壓(ya)(ya)(ya)(ya)時(shi)(shi)間,當到(dao)達加壓(ya)(ya)(ya)(ya)時(shi)(shi)間設定時(shi)(shi)間時(shi)(shi),設備逐步降壓(ya)(ya)(ya)(ya)退(tui)出試(shi)驗(yan)(yan)(yan),完(wan)成本次試(shi)驗(yan)(yan)(yan),進入(ru)試(shi)驗(yan)(yan)(yan)結束菜(cai)單項。
注意:在(zai)調(diao)(diao)(diao)節頻(pin)率調(diao)(diao)(diao)整鈕(niu)(niu)的(de)(de)過程(cheng)中,觸(chu)按(an)左(zuo)右鈕(niu)(niu),可以改變頻(pin)率調(diao)(diao)(diao)節的(de)(de)速(su)度實現(xian)粗細調(diao)(diao)(diao)的(de)(de)切(qie)換(huan)。在(zai)調(diao)(diao)(diao)節電(dian)壓(ya)調(diao)(diao)(diao)整鈕(niu)(niu)的(de)(de)過程(cheng)中,向(xiang)下觸(chu)按(an)左(zuo)右鈕(niu)(niu),可以改變電(dian)壓(ya)的(de)(de)升(sheng)降(jiang)的(de)(de)速(su)度實現(xian)粗細調(diao)(diao)(diao)的(de)(de)切(qie)換(huan)。觸(chu)按(an)調(diao)(diao)(diao)頻(pin)、調(diao)(diao)(diao)壓(ya)鈕(niu)(niu),實現(xian)調(diao)(diao)(diao)頻(pin)與(yu)調(diao)(diao)(diao)壓(ya)間的(de)(de)切(qie)換(huan)。
7、進(jin)入(ru)試驗記錄(lu)查詢菜單項,查詢以往和當(dang)前試驗數(shu)(shu)據。選擇(ze)(ze)上(shang)下鍵翻看前一組數(shu)(shu)據后一組數(shu)(shu)據;選擇(ze)(ze)左右(you)鍵可選擇(ze)(ze)打印(yin)或刪(shan)除當(dang)前頁的內(nei)容。
125/456為試(shi)(shi)驗數(shu)(shu)(shu)據庫指(zhi)針,分(fen)子是試(shi)(shi)驗數(shu)(shu)(shu)據的(de)(de)在數(shu)(shu)(shu)據庫的(de)(de)順序數(shu)(shu)(shu),分(fen)母是當前的(de)(de)數(shu)(shu)(shu)據總數(shu)(shu)(shu),*多可儲存999組試(shi)(shi)驗數(shu)(shu)(shu)據。
8、裝置(zhi)和試(shi)驗狀態菜單提示(shi):設備的(de)使用(yong)和升(sheng)壓(ya)和耐壓(ya)試(shi)驗過程中(zhong),如果出(chu)現(xian)影響試(shi)驗設備、被試(shi)驗設備以及操作人的(de)**情況,設備可(ke)能出(chu)現(xian)自動保(bao)護轉臺,并在屏幕有相應的(de)提示(shi)。
不(bu)能諧振(zhen)(zhen):如果諧振(zhen)(zhen)點(dian)不(bu)在(zai)諧振(zhen)(zhen)頻率設置的范圍內(nei);系(xi)統連線不(bu)正確等現象,裝置將找不(bu)到諧振(zhen)(zhen)點(dian),這時裝置和試驗狀態菜單中的不(bu)能諧振(zhen)(zhen)項被反白并閃爍。
輸(shu)出保(bao)護(hu):如果(guo)裝(zhuang)置的(de)電源輸(shu)出電流大于輸(shu)出保(bao)護(hu)設定(ding)的(de)電流值,裝(zhuang)置自動保(bao)護(hu),這時裝(zhuang)置和試驗狀(zhuang)態(tai)菜(cai)單中的(de)輸(shu)出保(bao)護(hu)項被(bei)反白并閃爍。
試驗中止(zhi):如果在試驗升(sheng)壓或加(jia)壓過(guo)程出現閃絡現象,裝置自動保(bao)護,這時裝置和(he)試驗狀態菜單中的輸出保(bao)護項被反(fan)白并閃爍。
9、試驗幫助內容(rong)包括五(wu)大項分別為(wei):1.版(ban)本信(xin)息2.接線示(shi)意3.使用說明4.常(chang)見(jian)問題5.參考資料.如常(chang)見(jian)問題FAQ分五(wu)幅畫面(mian)顯示(shi)、各種被試品電(dian)力電(dian)纜(lan)、變壓器、發電(dian)機電(dian)容(rong)參數的查詢:
接線示意圖:
10、設備(bei)出廠參數(shu)(shu)設置是生產(chan)廠家的出廠設置參術(shu)和校驗(yan)參數(shu)(shu),不適當的設置和修改(gai)會影響設備(bei)性(xing)能和高壓試驗(yan)的**性(xing),未經廠家授權密碼,無法修改(gai)。
警告:正(zheng)常試驗狀態下,按返回鍵(jian)即可中(zhong)止試驗。中(zhong)止或結束試驗后,應分離刀閘切斷電源。在升壓或加壓過程中(zhong),非緊急(ji)情況,不要按下急(ji)停鍵(jian)。
六、本說明書的專屬名詞的定義
自動試(shi)(shi)驗:高壓(ya)試(shi)(shi)驗全過程由主機按(an)程序(xu)和預(yu)置(zhi)參數自動完(wan)成。
自動調諧:調諧由主(zhu)機按程序自動完成,升壓手動完成。
手(shou)動試(shi)驗:尋找諧振點和升壓均為手(shou)動,通(tong)過面板旋鈕完成。
系(xi)統參數設(she)置是指(zhi)對設(she)備(bei)部件參數的設(she)置。
試驗參數設置是指對試驗過程參數的(de)設置。
試驗模式選擇是指對試驗模式的選擇。
試(shi)驗結(jie)果查詢是指對試(shi)驗數據(ju)的查詢。
分(fen)壓器變比(bi)是指對分(fen)壓器的分(fen)壓比(bi)設置。
電(dian)(dian)(dian)抗器(qi)電(dian)(dian)(dian)感是指對電(dian)(dian)(dian)抗器(qi)電(dian)(dian)(dian)抗值的設置。
激勵變(bian)變(bian)比是指對勵磁變(bian)壓器的(de)變(bian)比設置。
設置電壓是高(gao)壓試(shi)驗(yan)時的(de)保護電壓設置。
試(shi)(shi)驗(yan)電壓是(shi)高壓試(shi)(shi)驗(yan)時的試(shi)(shi)驗(yan)電壓。
加壓時(shi)間是施加試驗電壓的時(shi)間。
激勵強度是(shi)指主(zhu)機(ji)電源輸出的大(da)小。
輸(shu)出電流是主機電源的輸(shu)出電流。
頻(pin)(pin)率范(fan)圍(wei)(wei)是(shi)試(shi)驗的(de)頻(pin)(pin)率范(fan)圍(wei)(wei)。
自動試(shi)驗模式是指試(shi)驗過(guo)程全部自動完成。
自動(dong)調諧(xie)模式是指自動(dong)尋找諧(xie)振點(dian)后,手動(dong)加壓(ya)完成試(shi)驗。
手動(dong)試驗模式全部由人工完成(cheng)試驗過程(cheng)。
未(wei)接(jie)(jie)地線主機(ji)電源為接(jie)(jie)地。
不(bu)能(neng)諧振(zhen)未能(neng)找(zhao)到(dao)諧振(zhen)點。
輸出保護主機電(dian)源輸出電(dian)流(liu)(liu)大(da)于整定(ding)電(dian)流(liu)(liu)。
試驗(yan)中止指在升壓(ya)或加壓(ya)過(guo)程裝置自動保護。
設(she)備出廠(chang)參數設(she)置(zhi)是廠(chang)家對(dui)設(she)備有關參數的設(she)置(zhi)。
確(que)認(ren)鍵:確(que)認(ren)當前(qian)操(cao)作。
返回(hui)鍵:返回(hui)上**菜單。
七(qi)、變頻電源(yuan)技術參數(shu):
1.額定(ding)輸(shu)出容量:15kvA;
2.儀(yi)器電源(yuan):220v±10% 50Hz;
功率電源:380v±10% 50Hz;
3.額(e)定輸入(ru)電(dian)流:39.5A;
4.額定輸出電壓:0-340v可調、單(dan)相、輸出電壓不(bu)穩定度0.05%;
5.額定(ding)輸出(chu)電流:44A;
6.頻(pin)率(lv)調節范(fan)圍:25~320Hz;
7.額(e)定容量下連(lian)續運行(xing)為規定工作時間下*高溫升≤60K;
8.顯示(shi)以下(xia)參數(shu):
a.經變頻輸出的頻率(lv)、電壓、電流;
b.過壓保護(hu)電(dian)壓值,并可任意整(zheng)定(ding),當成(cheng)套(tao)裝置(zhi)的輸出(chu)電(dian)壓值達到保護(hu)整(zheng)定(ding)時(shi),可自動切除成(cheng)套(tao)裝置(zhi);
c.過流保護(hu):當調頻電(dian)(dian)源(yuan)的輸出電(dian)(dian)流達到(dao)保護(hu)整定值時,可自動切(qie)除成套裝置;
d.擊穿保護:當高壓側發生(sheng)對地閃絡時(shi),可自(zi)動(dong)切(qie)除成套裝(zhuang)(zhuang)置,裝(zhuang)(zhuang)置帶(dai)有隔離裝(zhuang)(zhuang)置,可確保設備和人(ren)身不受(shou)損(sun)害;
e.具(ju)有全(quan)電(dian)壓(ya)(ya)(ya)輸出保護,在調(diao)壓(ya)(ya)(ya)過(guo)程中,一旦(dan)調(diao)壓(ya)(ya)(ya)失控,調(diao)頻電(dian)源立即閉鎖;
9.可實現以下操作(zuo):
a.頻(pin)(pin)率(lv)(lv)的調節(jie),上升和(he)下降頻(pin)(pin)率(lv)(lv)調節(jie)分(fen)粗調和(he)細調兩種,并可自(zi)動尋找試驗(yan)諧(xie)振點,保證諧(xie)振頻(pin)(pin)率(lv)(lv)在整個試驗(yan)過程中不發生漂移;
b.帶有設(she)置(zhi)(zhi)電壓、設(she)置(zhi)(zhi)時(shi)間(jian),電壓自動上(shang)升(sheng)到(dao)設(she)置(zhi)(zhi)值而停止(zhi)并自動計時(shi);
c.帶有(you)各(ge)種保護功(gong)能的整定按鈕,可在面板上(shang)對各(ge)種保護值進(jin)行整定;
d.帶(dai)有手動試(shi)驗功(gong)能(neng)和自動試(shi)驗功(gong)能(neng);
e.帶有試驗數據打印功能(neng)。
八、勵磁變壓器技術參(can)數:
1.結構形式:干式;
2.額(e)定容量:15kVA;
3.輸入電壓:0~340V;
4.輸(shu)出電壓:四組(zu)(zu)并聯(lian)3.75KV;四組(zu)(zu)串聯(lian)15KV;二串二并7.5KV;
5.輸出電(dian)流:四(si)組并(bing)聯4A;四(si)組串聯1A;二串二并(bing)2A;
6.工作頻率范圍:30~300Hz;
勵(li)磁變壓器的接線端子,如圖所示:
1.輸出端尾—與(yu)接(jie)地端連接(jie)。
2.輸出端(duan)頭—與電抗器連接。
3.接(jie)地(di)端—與變頻電(dian)源、分(fen)壓器(qi)及被(bei)試(shi)品共同接(jie)地(di)。
4.輸(shu)入端—接調(diao)頻電源功率(lv)輸(shu)出(chu)端。
九、諧振電抗器(qi)技術(shu)參數:
額定(ding)容(rong)量:55KVA;
額定電壓:55kV;
額定電(dian)流(liu):1.5A;
電 感 量(liang):160H;
品質因數:Q≥30
采用(yong)環(huan)氧干式。
7.接線端了如圖所示:
a.高壓(ya)側接(jie)線(xian)端子(zi)—與被試品(pin)高壓(ya)端連接(jie)。
b.低壓側接(jie)線端(duan)子—與勵磁(ci)變(bian)輸(shu)出端(duan)連接(jie)。
c.多(duo)臺電(dian)抗器串聯時上節(jie)的低(di)壓側與下節(jie)高壓側連接(jie)。諧振電(dian)抗器采(cai)用多(duo)臺串聯或并聯的連接(jie)方式。
8.額(e)定(ding)容量(liang)下連(lian)續運行為(wei)規定(ding)工作時間(jian)下,電抗器對空氣的溫(wen)升(sheng)不大(da)于60K;
9.性(xing)能(neng)及(ji)特點:電(dian)抗(kang)器設計干(gan)式、環(huan)氧澆(jiao)鑄,電(dian)抗(kang)器可以(yi)自由方便疊裝。環(huan)氧樹脂絕緣筒外殼(ke),具有足夠的(de)電(dian)氣、機械強(qiang)度,必要的(de)散(san)熱能(neng)力以(yi)及(ji)油熱脹冷(leng)縮的(de)裕度。外殼(ke)上下蓋板,顏色為橘(ju)紅色。
十、電容分壓器技術參數:
額定電壓:200kV;
工作頻(pin)率:30~300Hz;
分壓比:2000:1;
分壓比誤差:1%;
電容(rong)分壓器接線端子如圖所示:
高壓端—與電抗器(qi)高壓側(ce)及被試(shi)品高壓側(ce)相(xiang)連。
測(ce)量插座—采(cai)用專配的(de)測(ce)量電纜與控制(zhi)箱背板測(ce)量輸(shu)入(ru)端(duan)連接。
接地(di)(di)端—采(cai)用專配接地(di)(di)線按接線圖指(zhi)示接地(di)(di)。
4.性(xing)能(neng)及特點(dian):
a.額定電壓下可連續運行(xing)2小時。
b.在30~300Hz范圍內,其精度(du)和穩定度(du)保持(chi)不(bu)變(bian)。
c.在(zai)20℃溫(wen)度(du)下(xia)電容分壓器介(jie)質損(sun)耗值≤0.0025
d.電容分壓器配有支撐底架,具有足夠的穩定(ding)性。
e.電壓測(ce)量通過專用測(ce)試引線(xian)引至(zhi)調頻電源進行測(ce)量。
試(shi)驗接線圖(tu):
110kv主(zhu)變、GIS試驗接線
35kv電纜試(shi)驗接線圖(tu)
10kv電纜試驗接線圖(tu)
十二、設備保(bao)存和(he)維護
1、存(cun)放于干(gan)燥、清潔場地,防止雨(yu)水、灰塵(chen)進入部(bu)件內部(bu);
2、如若(ruo)長期不使(shi)用,正(zheng)常天氣至少2個月應(ying)通電一(yi)次時間不少于(yu)半小(xiao)時,雨(yu)季及潮(chao)(chao)濕期應(ying)每隔一(yi)個月通電一(yi)次,通電時間半小(xiao)時,以驅除設(she)備(bei)內的潮(chao)(chao)氣防止電子(zi)元器件的銹蝕,影(ying)響(xiang)正(zheng)常使(shi)用。
3、定期檢查裝置各部(bu)件,確保各接(jie)頭緊固無松動;
4、更換(huan)打印紙(zhi)(zhi),機器采用熱敏(min)打印紙(zhi)(zhi)并且是前換(huan)紙(zhi)(zhi)式當(dang)需要換(huan)紙(zhi)(zhi)時只要按POST鍵鈕打印紙(zhi)(zhi)艙門(men)就(jiu)會打開可以將(jiang)新打印紙(zhi)(zhi)裝入;
十三、常見故(gu)障(zhang)排除
故(gu)障現象
|
發(fa) 生(sheng) 原(yuan) 因
|
排 除 方 法
|
找不到諧振點(dian)
|
接(jie)線有誤(wu)。
輸出(chu)開(kai)關(guan)未開(kai),;
3、做GIS時PT二次(ci)回路未打開;
4、試品Q值太低;
5、起(qi)始(shi)激勵功率太(tai)低(di);
6、試驗(yan)回路有短路現象;
7、找頻范圍不對。
|
退出(chu)試(shi)驗(yan)狀態(tai),合上輸出(chu)開(kai)關,檢查(cha)接線;打開(kai)PT二(er)次回路;
調高(gao)起始(shi)功率(∠30%);
用兆歐(ou)表測量試(shi)品絕緣
重(zhong)新設置找頻范圍
|
諧振后,電壓升(sheng)不(bu)上去
|
1、試品Q值太(tai)低(di);
2、激(ji)勵電壓不(bu)夠;
3、電抗器底(di)部有鐵磁物體;
4、3次(ci)諧(xie)波(bo)諧(xie)振(zhen)。
|
檢查試品;
改變激勵(li)(li)變壓(ya)器(qi)繞(rao)組接法,提高勵(li)(li)磁電壓(ya)
絕緣筒架(jia)高電抗器或(huo)離(li)開鐵磁物體。
|
主(zhu)機自動復位
|
供電(dian)電(dian)源容(rong)量不夠(gou);
電(dian)源引線過長(chang)或線徑過小;
接頭(tou)處接觸(chu)**;
供電電壓波(bo)動;
按鍵死接(jie)觸。
|
增加供電(dian)電(dian)源容量;
換較粗導線(xian),減(jian)小導線(xian)長度;
檢查接頭;
減(jian)小供電電壓波動(dong)。
|
開機后線路跳(tiao)閘
|
線路漏電保護器(qi)較為敏(min)感(gan);
空氣開關容量(liang)不夠。
|
跨過漏電保護器或(huo)空氣開(kai)關(guan)的接(jie)線;
改換較大容量的(de)空(kong)氣開(kai)關。
|
電(dian)壓跌(die)落
|
試品放電或擊(ji)穿
|
檢查試品
|
輸出短路
|
電流(liu)超過本機限流(liu)值。
|
檢查接線和試品。
|
試(shi)品電(dian)壓不準
|
分壓(ya)比設(she)置錯誤或(huo)分壓(ya)器信號(hao)傳輸有問題。
|
重設分壓(ya)(ya)比或檢查分壓(ya)(ya)器(qi)接線。
|
電壓閃變
|
試驗電(dian)壓劇烈波動,變化率(lv)超過本機限(xian)定值。
|
檢查供(gong)電(dian)電(dian)源電(dian)壓穩定性或試(shi)品參(can)數的(de)變化。
|
回路無電流
|
|
檢查接線(xian)和試品。
|
未接好地(di)線
|
|
檢查接(jie)地(di)線和地(di)樁(zhuang),按說明書要求連接(jie)。
|
試品過電壓(ya)
|
手動升壓太快或失控(kong)。
|
改(gai)變調壓步距(ju)或(huo)改(gai)用自動升壓 。
|
系統不諧振
|
接線有誤或試(shi)品Q值(zhi)太(tai)低。
|
檢查接(jie)線和(he)試品
|
十(shi)四、常用設備資料參考(kao)
交(jiao)聯聚乙烯電纜(lan)單位長度電容量
電(dian)纜導體截面積(平(ping)方毫米(mi))
|
電(dian) 容 (μ/km)
|
YJV、YJLV
|
YJV、YJLV
|
YJV、YJV、YJLV
|
YJV、YJLV
|
YJV、YJLV
|
6/6kV、6/10kV
|
8.7/10kV、8.7/15kV
|
12/35kV
|
21/35kV
|
26/35kV
|
1×35
|
0.212
|
0.173
|
0.152
|
|
|
1×50
|
0.237
|
0.192
|
0.166
|
0.118
|
0.114
|
1×70
|
0.270
|
0.217
|
0.187
|
0.131
|
0.125
|
1×95
|
0.301
|
0.240
|
0.206
|
0.143
|
0.135
|
1×120
|
0.327
|
0.261
|
0.223
|
0.153
|
0.143
|
1×150
|
0.358
|
0.284
|
0.241
|
0.164
|
0.153
|
1×185
|
0.388
|
0.307
|
0.267
|
0.180
|
0.163
|
1×240
|
0.430
|
0.339
|
0.291
|
0.194
|
0.176
|
1×300
|
0.472
|
0.370
|
0.319
|
0.211
|
0.190
|
1×400
|
0.531
|
0.418
|
0.352
|
0.231
|
0.209
|
1×500
|
0.603
|
0.438
|
0.388
|
0.254
|
0.232
|
1×600
|
0.667
|
0.470
|
0.416
|
0.287
|
0.256
|
2、交聯(lian)聚(ju)乙烯電纜單位長度電容量
電纜導體(ti)截面積(平方(fang)毫米)
|
電 容 (μF/km)
|
YJV、YJLV
|
YJV、YJLV
|
YJV、YJV、YJLV
|
YJV、YJLV
|
YJV、YJLV
|
6/6kV、6/10kV
|
8.7/10kV、8.7/15kV
|
12/35kV
|
21/35kV
|
26/35kV
|
3×35
|
0.212
|
0.173
|
0.152
|
|
|
3×50
|
0.237
|
0.192
|
0.166
|
0.118
|
0.114
|
3×70
|
0.270
|
0.217
|
0.187
|
0.131
|
0.125
|
3×95
|
0.301
|
0.240
|
0.206
|
0.143
|
0.135
|
3×120
|
0.327
|
0.261
|
0.223
|
0.153
|
0.143
|
3×150
|
0.358
|
0.284
|
0.241
|
0.164
|
0.153
|
3×185
|
0.388
|
0.307
|
0.267
|
0.180
|
0.163
|
3×240
|
0.430
|
0.339
|
0.291
|
0.194
|
0.176
|
3×300
|
0.472
|
0.370
|
0.319
|
0.211
|
0.190
|
3×400
|
0.531
|
0.418
|
0.352
|
0.231
|
0.209
|
3×500
|
0.603
|
0.438
|
0.388
|
0.254
|
0.232
|
3×600
|
0.667
|
0.470
|
0.416
|
0.287
|
0.256
|
3、交(jiao)聯聚乙烯電纜單位(wei)長度(du)電容量
電(dian)纜導(dao)體截(jie)面(mian)積(平方毫米)
|
電 容 (μF/km)
|
YJV、YJLV
|
YJV、YJLV
|
64/110kV
|
128/220kV
|
3×240
|
0.129
|
|
3×300
|
0.139
|
|
3×400
|
0.156
|
0.118
|
3×500
|
0.169
|
0.124
|
3×630
|
0.188
|
0.138
|
3×800
|
0.214
|
0.155
|
3×1000
|
0.231
|
0.172
|
3×1200
|
0.242
|
0.179
|
3×1400
|
0.259
|
0.190
|
3×1600
|
0.273
|
0.198
|
3×1800
|
0.284
|
0.297
|
3×2000
|
0.296
|
0.215
|
3×2200
|
|
0.221
|
3×2500
|
|
0.232
|
4、60kV級全絕緣變壓器的電容(pF)
類 型
|
變(bian) 壓 器 容 量 kVA
|
630
|
2000
|
3150
|
6300
|
8000
|
1600
|
高壓-地(di)
|
2700
|
4100
|
4600
|
5900
|
7000
|
8200
|
低壓-地
|
4200
|
6600
|
7900
|
10000
|
11000
|
15300
|
對于表中沒有(you)的產(chan)品(pin),可根據(ju)表中的上、下容量近似地估算。同容量的雙繞組(zu)變壓器,其繞組(zu)電容要比三繞組(zu)產(chan)品(pin)小。
5、110kV級中性點分級絕緣變壓(ya)器的電容(pF)
類(lei) 型(xing)
|
變 壓(ya) 器(qi) 容 量(liang)kVA
|
50000
|
31500
|
20000
|
10000
|
5600
|
高(gao)壓-中壓、低壓、地
|
14200
|
11400
|
8700
|
6150
|
4200
|
中(zhong)壓-高壓、低壓、地
|
24800
|
11800
|
13200
|
9600
|
-
|
低壓-高壓、中壓、地(di)
|
19300
|
19300
|
12000
|
9400
|
6800
|
6、220kV級(ji)中性點非全(quan)級(ji)絕緣部分變壓器的電容(pF)
試(shi) 品 型 號
|
SEPSL-63000
|
SSPSL-120000
|
SSPSL-240000
|
類 型
|
高壓-中(zhong)壓、低壓及地
|
12100
|
13500
|
17050
|
中壓-高壓、低壓及地
|
18500
|
19700
|
23260
|
低壓(ya)-高壓(ya)、中壓(ya)及地
|
18200
|
23600
|
29940
|
試 品 型 號
|
SFPL-240000
|
SFP-360000
|
SFPSZL-120000
|
類 型(xing)
|
高壓-中(zhong)壓、低壓及地
|
32230
|
33910
|
38020
|
中壓(ya)(ya)(ya)-高壓(ya)(ya)(ya)、低(di)壓(ya)(ya)(ya)及地
|
-
|
-
|
23260
|
低壓-高壓、中壓及地
|
22470
|
23790
|
22160
|
7、油浸式電(dian)力變壓器交流試驗電(dian)壓
額定電壓
(k V)
|
*高工(gong)作(zuo)
電壓(k V)
|
線(xian)端交(jiao)流試(shi)驗電壓值(kV)
|
中(zhong)性點(dian)交(jiao)流試驗電壓(ya)值(zhi)(kV)
|
全部更換繞組
|
部分更換繞組(zu)或(huo)交接
|
全部(bu)更(geng)換繞(rao)組
|
部分更換繞組或交接(jie)
|
<1
|
≤1
|
3
|
2.5
|
3
|
2.5
|
3
|
3.5
|
18
|
15
|
18
|
15
|
6
|
6.9
|
25
|
21
|
25
|
21
|
10
|
11.5
|
35
|
30
|
35
|
30
|
15
|
17.5
|
45
|
38
|
45
|
38
|
20
|
23.0
|
55
|
47
|
55
|
47
|
35
|
40.5
|
85
|
72
|
85
|
72
|
110
|
126.0
|
200
|
170(195)
|
95
|
80
|
220
|
252.0
|
360
|
306
|
85
|
72
|
395
|
336
|
(200)
|
(170)
|
500
|
550.0
|
630
|
536
|
85
|
72
|
680
|
578
|
140
|
120
|
8、部分型號發(fa)電機(ji)定子(zi)繞組的單相對地電容量
類別
|
發(fa) 電 機
|
型號
|
生產廠(chang)家
|
額定容量(MW)
|
額(e)定電壓(kV)
|
相(xiang)電容(mF)
|
火
力
發(fa)
電
機
|
QFS-125-2
|
上海電機廠
|
125
|
13.8
|
0.08-0.12
|
QFSN-200-2
|
哈爾(er)濱電機廠
|
200
|
15.75
|
0.19-0.21
|
QFQS-200-2
|
東方電機廠
|
200
|
15.75
|
0.1928-0.21
|
QFQS-200-2
|
北京重型電機廠
|
200
|
15.75
|
0.18-0.19
|
QFS-300-2
|
上海(hai)電(dian)機(ji)廠
|
300
|
18.0
|
0.16-0.20
|
QFSN-300-2
|
上海電機廠
|
300
|
18.0
|
0.18-0.20
|
ATB-2
|
美國(guo)GE公司
|
352
|
23.0
|
0.268(設計值)
|
TBB-320-2
|
(前蘇聯)
|
320
|
20.0
|
0.31
|
2-105×234
|
美國(guo)西屋公司
|
600
|
20.0
|
0.2(工廠試驗值)
|
50WT23E-138
|
ABB
|
600
|
22.0
|
0.253(設(she)計值)
|
水 發
力 電
機
|
|
|
72.5 - 85
|
10.5
|
0.694
|
|
|
300
|
15.75
|
1.7-2.5
|
|
|
400
|
18.0
|
2-2.5
|
9、同步發電機(ji)定子繞組交流(liu)試驗電壓
1
|
全部更換定子(zi)繞(rao)組并修(xiu)好后的試(shi)驗電壓
|
容量(liang)kW或kVA
|
小于10000
|
10000及以(yi)上
|
額定電壓Un (V)
|
36以(yi)上
|
6000以下
|
6000~18000
|
18000以上
|
試驗電壓V
|
2Un+1000但*低為(wei)1500
|
2.5Un
|
2Un
+3000
|
按專門協議
|
2
|
大修前或(huo)局部更換(huan)定子繞組并修好后的試驗電壓
|
運行20年及(ji)以下者
|
1.5 Un
|
運行20年以上(shang)與架空線(xian)路直接(jie)連接(jie)者(zhe)
|
1.5 Un
|
運行20年以上不與架空線路(lu)直接連(lian)接者
|
(1.3~1.5)Un
|
十五、設備成套性:
變(bian)頻電源 1臺
勵磁變壓(ya)器 1臺
電抗(kang)器 4臺(tai)
電(dian)容分壓器 1臺
附(fu)件及測試線 1套
支架(jia) 15KV 1只
均壓罩 200KV 2只
絕(jue)緣底(di)板 2塊(kuai)
一、產品概述(shu)
YDQC系列(lie)輕型(xing)(xing)交直(zhi)流高(gao)(gao)壓(ya)(ya)試(shi)驗(yan)變(bian)壓(ya)(ya)器是在(zai)同(tong)類(lei)產品YDJ(G)型(xing)(xing)高(gao)(gao)壓(ya)(ya)試(shi)驗(yan)變(bian)壓(ya)(ya)器的(de)(de)基礎上,按試(shi)驗(yan)變(bian)壓(ya)(ya)器國家標準(zhun)ZBK41006—89要求(qiu),經改(gai)進后生產的(de)(de)一種(zhong)新(xin)型(xing)(xing)產品,本系列(lie)產品具有(you)體積小(xiao)、重量輕、結構緊湊、功能齊全、使(shi)用(yong)方(fang)便等特點(dian)。實(shi)用(yong)于電(dian)(dian)力、工(gong)礦、科研等部(bu)門,對各種(zhong)高(gao)(gao)壓(ya)(ya)電(dian)(dian)氣(qi)設備、電(dian)(dian)氣(qi)元件(jian)、絕(jue)緣(yuan)材料(liao)進行工(gong)頻耐(nai)壓(ya)(ya)試(shi)驗(yan)和(he)直(zhi)流泄漏試(shi)驗(yan),是高(gao)(gao)壓(ya)(ya)試(shi)驗(yan)中(zhong)必(bi)不可少(shao)的(de)(de)儀(yi)器。
二、產(chan)品結構(gou)
YDQC系(xi)列輕型高(gao)壓(ya)(ya)試驗變(bian)壓(ya)(ya)器鐵芯(xin)為單框式(shi)。線圈采用同(tong)芯(xin)圓(yuan)筒多層塔式(shi)結(jie)構(gou),初級低壓(ya)(ya)繞組(zu)繞在(zai)鐵芯(xin)上,次(ci)級高(gao)壓(ya)(ya)繞組(zu)繞在(zai)低壓(ya)(ya)繞組(zu)外(wai)側(ce),這種同(tong)軸布置減少了繞組(zu)間的藕合損(sun)耗。高(gao)壓(ya)(ya)硅堆用特(te)殊(shu)工藝封裝在(zai)套(tao)管內,產品的外(wai)殼制成與器芯(xin)配合較佳(jia)的八角形結(jie)構(gou),整體外(wai)型美觀大方(fang)。其內外(wai)部結(jie)構(gou)見圖(tu)1。
1-均(jun)壓(ya)球;2-硅堆(dui)短路桿;3-高(gao)壓(ya)套(tao)管;4-油閥;5-殼體;6、7-調整電壓(ya)輸入a、x端(duan)子;8、9-儀表測量E、F端(duan)子;10-高(gao)壓(ya)尾X端(duan)子;11-變(bian)壓(ya)器外(wai)殼接地端(duan);12-高(gao)壓(ya)輸出A端(duan)子;13-高(gao)壓(ya)整流硅堆(dui);14-內部均(jun)壓(ya)環;15-變(bian)壓(ya)器鐵芯;16-初(chu)級低(di)壓(ya)繞(rao)組(zu)(zu);17-測量儀表繞(rao)組(zu)(zu);18-二次級高(gao)壓(ya)繞(rao)組(zu)(zu);19-變(bian)壓(ya)器油。
三、工(gong)作原(yuan)理(li)
YDQC系(xi)列輕型高壓(ya)(ya)試(shi)(shi)驗(yan)變(bian)壓(ya)(ya)器(qi)(qi)(qi)為單相(xiang)變(bian)壓(ya)(ya)器(qi)(qi)(qi),聯結組(zu)標號II。單臺(tai)高壓(ya)(ya)試(shi)(shi)驗(yan)變(bian)壓(ya)(ya)器(qi)(qi)(qi)的(de)工(gong)作過程(cheng),用交流220V(10KVA以(yi)上(shang)為380V)電壓(ya)(ya)接入電源控(kong)(kong)制(zhi)箱(臺(tai)),經(jing)電源控(kong)(kong)制(zhi)箱(臺(tai))內自藕調(diao)壓(ya)(ya)器(qi)(qi)(qi)(50KVA以(yi)上(shang)調(diao)壓(ya)(ya)器(qi)(qi)(qi)外附)調(diao)節0~200V(10KVA以(yi)上(shang)0~400V)電壓(ya)(ya)至試(shi)(shi)驗(yan)變(bian)壓(ya)(ya)器(qi)(qi)(qi)的(de)初級繞組(zu),根據電磁感應(ying)原理,在試(shi)(shi)驗(yan)變(bian)壓(ya)(ya)器(qi)(qi)(qi)高壓(ya)(ya)繞組(zu)可(ke)獲(huo)得試(shi)(shi)驗(yan)所(suo)需的(de)高電壓(ya)(ya)。其(qi)工(gong)作原理圖見圖2所(suo)示。
1、單臺YDQC高壓(ya)試(shi)驗變壓(ya)器工(gong)作原理示(shi)意圖
在試(shi)驗變(bian)壓(ya)器中:a、x為(wei)低壓(ya)輸入(ru)端(duan);A、X 為(wei)高壓(ya)輸出端(duan);E、F為(wei)儀(yi)表測量(liang)端(duan)。
2、單臺交直流兩用型高壓試驗變壓器工作原理見圖3。圖中所示:高壓套管內裝有高壓硅堆,串接在高壓回路中作高壓整流,以獲得直流高電壓。當用一短路桿將高壓硅堆短接時,可獲得交流高電壓,其狀態為交流輸出;反之在抽出短路桿時,其狀態為直流輸出。
3、三臺高壓試驗變壓器串激獲得更高電壓原理見圖4,串激高壓試驗變壓器有很大的優越性,因為整個試驗裝置由多個單臺串激式試驗變壓器組成,單臺試驗變壓器有著體積小、重量輕、便于運輸的特點,它既可以串接成高出幾倍的單臺試驗變壓器輸出電壓組合使用,又可以分開單獨使用。整套試驗裝置投資小、經濟實惠。圖3所示:在三臺串激式試驗變壓器串激使用中,單臺試驗變壓器B1、B2、B3的輸出電壓都是U,**、二級的試驗變壓器內部都有一個激磁繞組,分別為A1、C1 和A2、C2。當控制電壓加在第**試驗變壓器B1的初級繞組a1、x1上,激磁繞組A1、C1給予試驗變壓器B2初級繞組供電,**級試驗變壓器B2的激磁繞組A2、C2給試驗變壓器B3的初級繞組供電。由于第**試驗變壓器B1的高壓尾及殼體接地,**、三級的試驗變壓器B2和B3對地有絕緣支架的隔離,這樣試驗變壓器B1、B2、B3對地輸出電壓分別為1U、2U、3U。
B1、B2、B3- 串激式高壓變壓器;1U、2U、3U-各級對地電壓;
PV- 高壓示值表(biao)(KV); ZJ1、ZJ2-絕緣支架。
四、使用方法及注意(yi)事(shi)項
1、YDQC高壓(ya)試驗(yan)變(bian)壓(ya)器(qi)做工(gong)頻耐壓(ya)試驗(yan)使用接(jie)線方法見圖5。做工(gong)頻耐壓(ya)試驗(yan)前,先根據試驗(yan)變(bian)壓(ya)器(qi)的(de)(de)額定容(rong)量(liang)選(xuan)擇好限(xian)流(liu)電(dian)阻,(水電(dian)阻)的(de)(de)阻值(zhi)(zhi),再根據被(bei)試品需(xu)加的(de)(de)高壓(ya)電(dian)壓(ya)值(zhi)(zhi)調整好放電(dian)球(qiu)隙的(de)(de)球(qiu)間距,為了提(ti)高對被(bei)試品施(shi)加電(dian)壓(ya)的(de)(de)測量(liang)精度,應在高壓(ya)側(ce)接(jie)入FRC阻容(rong)分壓(ya)器(qi)來(lai)測量(liang)電(dian)壓(ya)。
R1、R2- 限流電阻; Qx- 放(fang)電球隙(xi); Zx- 被試品(pin);
FRC- 阻容分壓器; V- 分壓器高壓表。
按照圖4、結合圖2所進行的工頻耐壓試驗接好工作線路,試驗變壓器的高壓繞阻的X端(高壓尾)、儀表測量繞組的F端、試驗變壓器的外殼以及電源控制箱(臺)的外殼必須可靠接地。
用三臺試驗變壓器串激做工頻耐壓試驗時、**、三級試驗變壓器的初級繞組X端,儀表測量繞組的F端,以及高壓繞組的X端(高壓尾)均接本級試驗變壓器的外殼,**、三級試驗變壓器的主體必須放置在絕緣支架上。除第**以外、**、三級試驗變壓器的主體不要接地線。其接線方式見圖3所示。
接電源前,電源控制箱(臺)的調壓器必須調到零位。接通電源后,綠色指示燈亮,按一下啟動按鈕,紅色指示燈亮,表示試驗變壓器已接通控制電源,開始升壓。
從零位開始按順時針方向勻速旋轉調壓器手輪升壓。(升壓方式有:快速升壓法,即20S逐級升壓法,慢速升壓法,即60S逐級升壓法,極慢速升壓法供選用)電壓從零開始按選定的升壓速度升到您所需額定試驗電壓的75%后,再以每秒2%額定試驗電壓的速度升到您所需試驗電壓,并密切注意測量儀表的指示以及被試品的情況,被試品施加電壓的時間到后。應在數秒內勻速將調壓器返回,高壓降至1/3試驗電壓以下,按一下停止按鈕,高壓、低壓輸出停止,然后切斷電源線,試驗完畢。
工頻耐壓(ya)試驗操作過程注意事項
1、試驗人員應做好責任分工,設定好試驗現場的**距離,仔細檢查好被試品及試驗變壓器的接地情況,并設有專人監護**及觀察被試品狀態工作。
2、被試品主要部位應**干凈,保持**干燥,以免損壞被試品和帶來試驗數值的誤差。
3、對大型設備的試驗,一般都應先進行試驗變壓器的空升試驗,即不接試品時升壓至試驗電壓,以便校對好儀表的指示精度,調整好放電球隙的球間距。
4、做耐壓試驗時升壓速度不能過快,并防止突然加壓,例如調壓器不在零位的突然合閘,也不能突然斷電,一般應在調壓器降至零位時分閘。
5、在升壓或耐壓試驗過程中,如發現下列不正常情況,1 電壓、電流表指針擺動很大,2 被試品發出不正常響聲,3 發現絕緣有燒焦或冒煙現象,應立即降壓,切斷電源,停止試驗并查明原因。
6、使用本產品做高壓試驗時,除熟悉本說明書外,還必須嚴格執行國家有關標準和操作規程。
2、YDQ交(jiao)直(zhi)流(liu)兩用高(gao)(gao)(gao)壓(ya)(ya)(ya)(ya)(ya)試(shi)(shi)(shi)驗變壓(ya)(ya)(ya)(ya)(ya)器(qi)做直(zhi)流(liu)耐壓(ya)(ya)(ya)(ya)(ya)和泄(xie)漏(lou)試(shi)(shi)(shi)驗使用接線方(fang)法見(jian)圖5。由于是交(jiao)直(zhi)流(liu)兩用高(gao)(gao)(gao)壓(ya)(ya)(ya)(ya)(ya)試(shi)(shi)(shi)驗變壓(ya)(ya)(ya)(ya)(ya)器(qi),應把高(gao)(gao)(gao)壓(ya)(ya)(ya)(ya)(ya)硅(gui)堆短路(lu)桿(gan)從(cong)套管中(zhong)抽(chou)出,使試(shi)(shi)(shi)驗變壓(ya)(ya)(ya)(ya)(ya)器(qi)為直(zhi)流(liu)輸(shu)出狀(zhuang)態。做直(zhi)流(liu)泄(xie)漏(lou)試(shi)(shi)(shi)驗前,先根(gen)據泄(xie)漏(lou)試(shi)(shi)(shi)驗中(zhong)輸(shu)出端斷路(lu)電流(liu)不超過高(gao)(gao)(gao)壓(ya)(ya)(ya)(ya)(ya)硅(gui)堆的(de)(de)*大整流(liu)為宜,選擇好限流(liu)電阻(zu)(zu)(水電阻(zu)(zu))的(de)(de)阻(zu)(zu)值(zhi)(zhi),再根(gen)據被試(shi)(shi)(shi)品(pin)對直(zhi)流(liu)高(gao)(gao)(gao)壓(ya)(ya)(ya)(ya)(ya)波形(xing)的(de)(de)要求選擇好高(gao)(gao)(gao)壓(ya)(ya)(ya)(ya)(ya)濾波電容(rong)的(de)(de)電容(rong)值(zhi)(zhi)。為了(le)提高(gao)(gao)(gao)對被試(shi)(shi)(shi)品(pin)施加電壓(ya)(ya)(ya)(ya)(ya)的(de)(de)測量(liang)精度(du),應在高(gao)(gao)(gao)壓(ya)(ya)(ya)(ya)(ya)側接入FRC阻(zu)(zu)容(rong)分壓(ya)(ya)(ya)(ya)(ya)器(qi)來(lai)測量(liang)電壓(ya)(ya)(ya)(ya)(ya)。
R- 限流電(dian)阻; C- 高壓濾波電(dian)容; Zx- 被試品; G- 硅堆短路桿;
FRC- 阻容分壓器;V- 分壓器高壓表;uA- 微安表;D- 高壓整流硅堆。
按照圖5、結合圖3所進行的直流泄漏試驗接好工作線路。試驗變壓器的高壓繞組的X端(高壓尾)、儀表測量繞組的F 端、試驗變壓器的外殼以及電源控制箱(臺)的外殼必須可靠接地。
接(jie)電(dian)源(yuan)前(qian)、電(dian)源(yuan)控(kong)制箱(臺)的調壓器必須(xu)調到(dao)零(ling)位。接(jie)通(tong)電(dian)源(yuan)后,綠色(se)(se)指(zhi)示燈亮,按一下啟動按鈕,紅色(se)(se)指(zhi)示燈亮,表示試驗變壓器已接(jie)通(tong)控(kong)制電(dian)源(yuan),開始升壓。
從零位(wei)開(kai)始按順時(shi)針方向勻速(su)(su)旋轉調(diao)壓(ya)器手(shou)輪升(sheng)壓(ya)。(升(sheng)壓(ya)方式有:快速(su)(su)升(sheng)壓(ya)法(fa)即20S逐級升(sheng)壓(ya)法(fa);慢(man)速(su)(su)升(sheng)壓(ya)法(fa),即60S逐級升(sheng)壓(ya)法(fa);級慢(man)速(su)(su)升(sheng)壓(ya)法(fa)供選用(yong))電(dian)(dian)壓(ya)從零開(kai)始按選定的升(sheng)壓(ya)速(su)(su)度(du)升(sheng)到您(nin)所需額定試(shi)(shi)驗(yan)電(dian)(dian)壓(ya)或額定直流(liu)(liu)電(dian)(dian)流(liu)(liu)下的參考電(dian)(dian)壓(ya)。試(shi)(shi)驗(yan)中應嚴密(mi)注意直流(liu)(liu)高(gao)壓(ya)表、泄(xie)漏電(dian)(dian)流(liu)(liu)表指示以及被試(shi)(shi)品的情況(kuang)。試(shi)(shi)驗(yan)完畢(bi)后(hou),應訊速(su)(su)均勻將高(gao)壓(ya)降至(zhi)零位(wei),按一下停止(zhi)(zhi)按鈕,高(gao)壓(ya)、低壓(ya)輸出(chu)停止(zhi)(zhi),然后(hou)切斷電(dian)(dian)源。此(ci)時(shi)應用(yong)直流(liu)(liu)高(gao)壓(ya)放**給被試(shi)(shi)品及試(shi)(shi)驗(yan)裝置本身充分放電(dian)(dian)。
直(zhi)流泄漏(lou)試驗操作過程(cheng)注(zhu)意事項
(1)試驗人員應做好責任分工,設定好試驗現場的**距離,仔細檢查好被試品及試驗變壓器的接地情況,并設有專人監護**及觀察被試品狀態工作。
(2)被試品做試驗前,應拆除所有對外連線,并充分放電,主要部位應**干凈,保持**干燥,以免損壞被試品及帶來試驗數值的誤差。
(3)對于大容量試品(電容器、超長電纜等)試驗時應緩慢升壓,防止被試品的充電電流過大而燒壞微安表,必要時應分級加壓分別讀取各電壓下微安表的穩定讀數。
(4)試驗過程中,應嚴密監視被試品、微安表及試驗裝置等,一旦發生閃爍、擊穿等現象應立即降壓,切斷電源,并查明原因。
五(wu)、配套選購產品
下列產品僅供選擇,購買時需另行計價。
1.KZX系列電源控制箱 容量:1KVA-5KVA、輸入電壓:220V
2.KZT系列電源控制臺 容量:10KVA~300KVA輸入電壓:220V或380V
3.數字微安表:SWB-II
4.高壓濾波電容: 0.01MF、40 ~ 100KV
5.高壓直流放**: FBR— 70、140、210KV
6.放電球隙: Q—50、100、150、200、250、500
7.標準試油杯: 400ml
8.折疊式手推車: 150、300型
9.絕緣支架: 50、100、200、300、400KV
10.阻容分壓器: FRC —50、100、150、200KV
11.高壓硅堆: 2DL—150、300、450KV
12.水 電 阻: 50、100
六、主(zhu)要試驗(yan)設備(bei)的選(xuan)擇
1、試驗變壓器
其高壓側額定電壓應不小于被試品的*高試驗電壓,額定電流不小于被試品的*大電容電流。被試品的電容電流和試驗變壓器所需容量計算式為:
被試品(pin)電容量(liang)Cx可由交流電橋測出。常用(yong)的被試品(pin)電容量(liang)按表(biao)1選取(qu)。
幾種常(chang)用被試品的電容量(pF) 表1
2、調壓(ya)設備
(1)自藕調壓器。其調壓范圍廣、功率損耗小、波形畸變小、選擇這種調壓方式為*好。自藕調壓器的容量按0.75 ~ 1倍的試驗變壓器的容量選擇,適用于容量為100KVA以下的試驗變壓器的調壓。
(2)感應調壓器。其調壓范圍大,波形畸形小、但結構復雜、價格較貴,當試驗變壓器的容量較大時(如100KVA以上)使用。
3、限流電阻
限流電阻的作用是,當被試品擊穿時,限制斷路電流,從而保護試驗變壓器,防止故障的擴大。其數值以*高試驗電壓為準,按0.5 ~ 1 Ω / V(有效值)選擇,限流電阻可用水電阻。注意水不能充滿玻璃管,應留有余地,以防爆裂。
4、放電球隙
放電球隙的布置方式有垂直和水平兩種,球隙間距S和球的直徑D的關系應保護在0.05D ≤S ≤0.5D范圍內,球隙上的水電阻阻值一般按0.1 ~ 1Ω/V選取,設置放電球隙的目的是為了對重要的被試品起保護作用,可以將由于誤操作或被試品擊穿引起的過電壓限制在允許的范圍內。
七、試(shi)驗(yan)變壓器技術指示
型號
|
容量
|
高壓(ya)電壓(ya)
|
高壓電流
|
低壓輸(shu)入
|
變比
|
溫升℃
|
(KVA)
|
(KV)
|
(mA)
|
電壓(V)
|
電流(A)
|
高/儀
|
30分鐘
|
YDQC-1.5/50
|
1.5
|
50
|
30
|
200
|
7.5
|
500
|
10
|
YDQC-3/50
|
3
|
50
|
60
|
200
|
15
|
500
|
10
|
YDQC-5/50
|
5
|
50
|
100
|
200
|
25
|
500
|
10
|
YDQC-10/50
|
10
|
50
|
200
|
200
|
50
|
500
|
10
|
YDQC-15/50
|
15
|
50
|
300
|
200
|
75
|
500
|
10
|
YDQC-20/50
|
20
|
50
|
400
|
380
|
53
|
500
|
10
|
YDQC-30/50
|
30
|
50
|
600
|
380
|
79
|
500
|
10
|
YDQC-50/50
|
50
|
50
|
1000
|
380
|
12
|
500
|
10
|
YDQC-5/100
|
5
|
100
|
50
|
200
|
25
|
1000
|
10
|
YDQC-10/100
|
10
|
100
|
100
|
200
|
50
|
1000
|
10
|
YDQC-20/100
|
20
|
100
|
200
|
400
|
50
|
1000
|
10
|
YDQC-30/100
|
30
|
100
|
300
|
400
|
75
|
1000
|
10
|
YDQC-50/100
|
50
|
100
|
500
|
400
|
125
|
1000
|
10
|
YDQC-20/150
|
20
|
150
|
133
|
400
|
50
|
1500
|
10
|
YDQC-30/150
|
30
|
150
|
200
|
400
|
75
|
1500
|
10
|
YDQC-50/150
|
50
|
150
|
333
|
400
|
125
|
1500
|
10
|
YDQC-100/150
|
100
|
150
|
667
|
400
|
250
|
1500
|
10
|
YDQC-50/200
|
50
|
200
|
250
|
400
|
125
|
2000
|
10
|
YDQC-100/200
|
100
|
200
|
500
|
400
|
250
|
2000
|
10
|
YDQC-150/200
|
150
|
200
|
750
|
400
|
375
|
2000
|
10
|
YDQC-200/200
|
200
|
200
|
1000
|
400
|
500
|
2000
|
10
|
YDQC-300/200
|
300
|
200
|
1500
|
400
|
600
|
2000
|
10
|
YDQC-50/300
|
50
|
300
|
170
|
400
|
125
|
3000
|
10
|
YDQC-100/300
|
100
|
300
|
333
|
400
|
250
|
3000
|
10
|
YDQC-150/300
|
150
|
300
|
500
|
400
|
375
|
3000
|
10
|
YDQC-200/300
|
200
|
300
|
667
|
400
|
500
|
3000
|
10
|
YDQC-300/300
|
300
|
300
|
3000
|
500
|
600
|
3000
|
10
|
1、使用環境條件
環境溫度不高于+40℃、不低于—20℃;空氣相對濕度不大于90%;海拔高度不超過2000米;
2、工作電壓
電源控制箱(臺)輸入電壓為工頻220V或380V、相對誤差不超過±10%;(具體使用電壓根據用戶所定試驗變壓器規格選取)
八、隨貨文件
YDQC 系列試驗變壓器產品說明書 1份
產品出廠試驗報告 1份
產品合格證 1份
裝箱單 1份
一、概述(shu)
YDQ系列高(gao)(gao)壓(ya)(ya)試(shi)(shi)驗(yan)(yan)變壓(ya)(ya)器是(shi)根據《試(shi)(shi)驗(yan)(yan)變壓(ya)(ya)器》標準(zhun),在(zai)油(you)浸(jin)式(shi)試(shi)(shi)驗(yan)(yan)變壓(ya)(ya)器的(de)(de)(de)(de)(de)基礎上而設計生產(chan)(chan)的(de)(de)(de)(de)(de)。SF6氣(qi)(qi)(qi)(qi)體(ti)具(ju)有(you)良好的(de)(de)(de)(de)(de)電(dian)氣(qi)(qi)(qi)(qi)絕緣(yuan)性能(neng)(neng)及優異的(de)(de)(de)(de)(de)滅弧性能(neng)(neng),其耐壓(ya)(ya)強(qiang)度(du)為(wei)同一(yi)壓(ya)(ya)力下(xia)(xia)氮氣(qi)(qi)(qi)(qi)的(de)(de)(de)(de)(de)2.5倍(bei),擊(ji)穿(chuan)(chuan)電(dian)壓(ya)(ya)的(de)(de)(de)(de)(de)空氣(qi)(qi)(qi)(qi)的(de)(de)(de)(de)(de)2.5倍(bei)。在(zai)0.25MPa下(xia)(xia)與油(you)的(de)(de)(de)(de)(de)擊(ji)穿(chuan)(chuan)電(dian)壓(ya)(ya)相等(deng),在(zai)0.45MPa壓(ya)(ya)力下(xia)(xia)是(shi)油(you)的(de)(de)(de)(de)(de)擊(ji)穿(chuan)(chuan)電(dian)壓(ya)(ya)的(de)(de)(de)(de)(de)2倍(bei),是(shi)一(yi)種優于油(you)的(de)(de)(de)(de)(de)新一(yi)代(dai)超高(gao)(gao)壓(ya)(ya)絕緣(yuan)介質(zhi)材料(liao)。該產(chan)(chan)品(pin)技術要(yao)求完全符合《ZBK-41006-89》標準(zhun),它是(shi)油(you)浸(jin)式(shi)輕型(xing)試(shi)(shi)驗(yan)(yan)變壓(ya)(ya)器的(de)(de)(de)(de)(de)換代(dai)產(chan)(chan)品(pin)。該產(chan)(chan)品(pin)具(ju)有(you)體(ti)積小(xiao)、重量輕、不(bu)受氣(qi)(qi)(qi)(qi)候變化影響、電(dian)暈小(xiao)、現場搬運無需(xu)靜(jing)止(zhi)可使(shi)用(yong),使(shi)用(yong)壽命長、免維修等(deng)特點(dian)。適用(yong)于電(dian)力系統、工(gong)礦(kuang)企業、科研部門等(deng)對各種高(gao)(gao)壓(ya)(ya)電(dian)氣(qi)(qi)(qi)(qi)設備、電(dian)氣(qi)(qi)(qi)(qi)元(yuan)件(jian)、絕緣(yuan)材料(liao)進(jin)行工(gong)頻(pin)或直(zhi)流高(gao)(gao)壓(ya)(ya)下(xia)(xia)的(de)(de)(de)(de)(de)絕緣(yuan)強(qiang)度(du)試(shi)(shi)驗(yan)(yan)。
二、產品(pin)結構
YDQ系列高(gao)壓試驗變壓器(qi)采用單框芯(xin)式(shi)鐵芯(xin)結(jie)構(gou)(gou),初級繞(rao)(rao)組(zu)繞(rao)(rao)在鐵芯(xin)上(shang),高(gao)壓繞(rao)(rao)組(zu)在外,這種同軸布置減少了漏磁(ci)通,因(yin)而增大了繞(rao)(rao)組(zu)間的耦(ou)合。產品的外殼為圓(yuan)柱灌(guan)式(shi)容器(qi)結(jie)構(gou)(gou),能耐受0.8MPa以上(shang)壓力。其結(jie)構(gou)(gou)見圖(tu)1:
三、工(gong)作原理
YDQ系(xi)列(lie)高(gao)(gao)壓(ya)試(shi)驗(yan)(yan)變(bian)(bian)壓(ya)器(qi)(qi)為單相變(bian)(bian)壓(ya)器(qi)(qi),聯(lian)結(jie)組標號(hao)Ⅰ.Ⅰ. 用(yong)工(gong)頻220V(10kVA以(yi)上為380V)電(dian)源接入 (為本公(gong)司(si)生產的試(shi)驗(yan)(yan)變(bian)(bian)壓(ya)器(qi)(qi)配(pei)套專用(yong)設(she)備(bei),詳細(xi)資料請見其具體使用(yong)說明書(shu))系(xi)列(lie)操作箱(臺),經操作箱內自偶調壓(ya)器(qi)(qi)(50kVA以(yi)上調壓(ya)器(qi)(qi)外附)調節至0~200V(或0~400V)電(dian)壓(ya)輸出至YDQ試(shi)驗(yan)(yan)變(bian)(bian)壓(ya)器(qi)(qi)的初級繞組,根據電(dian)磁(ci)感(gan)應原理,在試(shi)驗(yan)(yan)變(bian)(bian)壓(ya)器(qi)(qi)高(gao)(gao)壓(ya)繞組可獲得(de)試(shi)驗(yan)(yan)所需的高(gao)(gao)電(dian)壓(ya)。
單臺(tai)YDQ系列交直(zhi)流高(gao)壓(ya)試驗變壓(ya)器的(de)工作(zuo)原(yuan)理圖見圖3,圖中高(gao)壓(ya)套管中裝有高(gao)壓(ya)硅堆,串接(jie)在高(gao)壓(ya)回路中作(zuo)半波整流,以獲得(de)直(zhi)流高(gao)電壓(ya)。當用(yong)一短(duan)路桿將高(gao)壓(ya)硅堆短(duan)接(jie)時,可獲得(de)工頻(pin)高(gao)電壓(ya),作(zuo)為交流輸出狀(zhuang)態(tai);取消短(duan)路桿時,作(zuo)為直(zhi)流輸出狀(zhuang)態(tai)。
圖中(zhong):D—短路(lu)桿(gan) VD—高壓硅堆
試驗(yan)變壓器高壓套管中的高壓硅堆未畫出,其原理(li)與上圖相同。
三臺(tai)(tai)(tai)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)串(chuan)(chuan)級(ji)(ji)(ji)(ji)獲得(de)更(geng)高電(dian)(dian)壓(ya)的(de)(de)接(jie)線(xian)原理見圖(tu)4。串(chuan)(chuan)級(ji)(ji)(ji)(ji)高壓(ya)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)有(you)(you)很(hen)大的(de)(de)優越性(xing),因為整個(ge)(ge)試(shi)(shi)(shi)(shi)驗(yan)(yan)裝置由幾臺(tai)(tai)(tai)單(dan)(dan)臺(tai)(tai)(tai)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)組(zu)成(cheng)(cheng),單(dan)(dan)臺(tai)(tai)(tai)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)容(rong)量小(xiao)、電(dian)(dian)壓(ya)低、重量輕,便于運(yun)輸和(he)安裝。它既(ji)然可(ke)串(chuan)(chuan)接(jie)成(cheng)(cheng)高出幾倍的(de)(de)單(dan)(dan)臺(tai)(tai)(tai)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)輸出電(dian)(dian)壓(ya)組(zu)合使用,又可(ke)分(fen)開成(cheng)(cheng)幾套單(dan)(dan)臺(tai)(tai)(tai)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)單(dan)(dan)獨使用。整套裝置投資小(xiao),經濟(ji)實惠(hui)。圖(tu)5中,在(zai)第(di)(di)(di)**和(he)**級(ji)(ji)(ji)(ji)的(de)(de)每(mei)個(ge)(ge)單(dan)(dan)元試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)中都(dou)有(you)(you)一個(ge)(ge)勵磁(ci)繞(rao)組(zu)A1、C1和(he)A2、C2。在(zai)三臺(tai)(tai)(tai)串(chuan)(chuan)級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)基(ji)本原理中,低壓(ya)電(dian)(dian)源加(jia)在(zai)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)Ⅰ的(de)(de)初級(ji)(ji)(ji)(ji)繞(rao)組(zu)a1x1上(shang),單(dan)(dan)臺(tai)(tai)(tai)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)Ⅰ、Ⅱ、Ⅲ的(de)(de)輸出電(dian)(dian)壓(ya)都(dou)是(shi)V。勵磁(ci)繞(rao)組(zu)A1、C1給**級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)Ⅱ的(de)(de)初級(ji)(ji)(ji)(ji)繞(rao)組(zu)供電(dian)(dian);**級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)Ⅱ的(de)(de)勵磁(ci)繞(rao)組(zu)A2、C2給第(di)(di)(di)三級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)Ⅲ的(de)(de)初級(ji)(ji)(ji)(ji)繞(rao)組(zu)供電(dian)(dian)。**級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)Ⅱ和(he)第(di)(di)(di)三級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)Ⅲ的(de)(de)箱(xiang)體(ti)分(fen)別處(chu)在(zai)對(dui)(dui)地(di)為1V和(he)2V的(de)(de)高電(dian)(dian)位上(shang),所以箱(xiang)體(ti)對(dui)(dui)地(di)是(shi)絕緣的(de)(de),試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)Ⅰ的(de)(de)箱(xiang)體(ti)是(shi)接(jie)地(di)的(de)(de)。這(zhe)樣第(di)(di)(di)**、**級(ji)(ji)(ji)(ji)、第(di)(di)(di)三級(ji)(ji)(ji)(ji)試(shi)(shi)(shi)(shi)驗(yan)(yan)變(bian)(bian)(bian)壓(ya)器(qi)(qi)(qi)對(dui)(dui)地(di)的(de)(de)額(e)(e)定輸出電(dian)(dian)壓(ya)分(fen)別為1V、2V、3V;其(qi)額(e)(e)定容(rong)量分(fen)別為3P、2P、1P。
YDQ系列高壓(ya)試(shi)(shi)驗(yan)變壓(ya)器做被(bei)試(shi)(shi)品的工頻耐壓(ya)試(shi)(shi)驗(yan)使用接線原(yuan)理圖(tu)(tu)見圖(tu)(tu)5。
圖中:R1—限(xian)流電(dian)(dian)阻 FRC—阻容(rong)分壓器 RF—球間隙保護(hu)電(dian)(dian)阻 G—球間隙 CX—被試(shi)品
注:高(gao)壓尾必須可(ke)靠接地
工頻耐壓(ya)試(shi)驗中限(xian)流(liu)(liu)電(dian)阻R1應根據試(shi)驗變壓(ya)器的(de)額定(ding)(ding)容(rong)(rong)量(liang)來(lai)選(xuan)擇(ze)。如高(gao)壓(ya)側(ce)額定(ding)(ding)輸(shu)出(chu)電(dian)流(liu)(liu)在100~300mA時,可取0.5~1Ω/V(試(shi)驗電(dian)壓(ya));高(gao)壓(ya)側(ce)額定(ding)(ding)輸(shu)出(chu)電(dian)流(liu)(liu)為1A以上時,可取1Ω/V(試(shi)驗電(dian)壓(ya))。常用水(shui)(shui)電(dian)阻作為限(xian)流(liu)(liu)電(dian)阻,管(guan)(guan)子長度可按150kV/m考慮,管(guan)(guan)子粗細(xi)應具有(you)足夠(gou)的(de)熱容(rong)(rong)量(liang)(水(shui)(shui)阻液配(pei)制(zhi)方(fang)法(fa):用蒸餾水(shui)(shui)加入(ru)適量(liang)硫酸(suan)銅配(pei)制(zhi)成(cheng)各種(zhong)不同(tong)的(de)阻值)。
球間隙(xi)及保護電(dian)阻(zu):當電(dian)壓超過球間隙(xi)整定(ding)值時(shi)(一般(ban)取試驗電(dian)壓的(de)110%~120%),球間隙(xi)放電(dian),對被試品起到(dao)保護作(zuo)用。球間隙(xi)保護電(dian)阻(zu)可按(an)1Ω/V(試驗電(dian)壓)選取。
在(zai)工(gong)頻耐壓(ya)(ya)(ya)試驗(yan)中,低電(dian)(dian)(dian)壓(ya)(ya)(ya)側(ce)(ce)測(ce)量(liang)電(dian)(dian)(dian)壓(ya)(ya)(ya)(儀表電(dian)(dian)(dian)壓(ya)(ya)(ya))不(bu)是非常(chang)準確(que)的,其(qi)原因是由(you)于試驗(yan)變壓(ya)(ya)(ya)器(qi)存(cun)在(zai)著(zhu)漏抗,在(zai)這個漏抗上(shang)必(bi)然(ran)存(cun)在(zai)著(zhu)壓(ya)(ya)(ya)降或容(rong)升(sheng),使試品(pin)上(shang)的電(dian)(dian)(dian)壓(ya)(ya)(ya)低于或高于低壓(ya)(ya)(ya)側(ce)(ce)測(ce)量(liang)電(dian)(dian)(dian)壓(ya)(ya)(ya)表上(shang)反映出(chu)來的電(dian)(dian)(dian)壓(ya)(ya)(ya)。工(gong)頻耐壓(ya)(ya)(ya)試驗(yan)時(shi),被(bei)試品(pin)上(shang)的電(dian)(dian)(dian)壓(ya)(ya)(ya)高于試驗(yan)變壓(ya)(ya)(ya)器(qi)的輸(shu)出(chu)電(dian)(dian)(dian)壓(ya)(ya)(ya),也就是所謂容(rong)升(sheng)現(xian)象。感(gan)應耐壓(ya)(ya)(ya)試驗(yan)時(shi),試驗(yan)變壓(ya)(ya)(ya)器(qi)的漏抗必(bi)然(ran)存(cun)在(zai)著(zhu)壓(ya)(ya)(ya)降。為了(le)準確(que)測(ce)量(liang)被(bei)試品(pin)上(shang)所施加的電(dian)(dian)(dian)壓(ya)(ya)(ya),因此常(chang)在(zai)高壓(ya)(ya)(ya)側(ce)(ce)接入(ru)FRC阻容(rong)分壓(ya)(ya)(ya)器(qi)來測(ce)量(liang)電(dian)(dian)(dian)壓(ya)(ya)(ya)(見圖5)。
工頻耐壓試驗操作注意事項
1)試驗人員應做好分工(gong),明確相(xiang)互(hu)間聯系(xi)方法。并有(you)專門人監護現場**及觀察試品狀態。
2)被試品應先清掃(sao)干凈(jing),并**干燥,以免(mian)損壞(huai)被試品和試驗帶(dai)來(lai)的誤差。
3)對于大型(xing)試(shi)驗,一般都應先進(jin)行(xing)空升(sheng)試(shi)驗。即不接試(shi)品(pin)時(shi)升(sheng)壓至試(shi)驗電(dian)壓,校(xiao)對各種表計,調整球(qiu)間(jian)隙。
4)升壓(ya)(ya)速度不能太(tai)快,并必須防(fang)止(zhi)突(tu)然加壓(ya)(ya)。例如調(diao)(diao)壓(ya)(ya)器(qi)不在(zai)零位時突(tu)然合閘。也不能突(tu)然切斷電源,一(yi)般應在(zai)調(diao)(diao)壓(ya)(ya)器(qi)降至零位時拉閘。
5)當(dang)電(dian)壓(ya)升至(zhi)試驗(yan)電(dian)壓(ya)時(shi)(shi),開始計(ji)時(shi)(shi),到(dao)1min后(hou),迅速(su)降壓(ya)到(dao)1/3試驗(yan)電(dian)壓(ya)以下時(shi)(shi),才(cai)能拉開電(dian)源。
6)在升壓或耐壓試驗過程中,如發(fa)現下列不正(zheng)常情況時(shi),應立即(ji)降壓,切斷電源(yuan)。停(ting)止試驗并查明原因(yin):①電壓表指針擺動很大;②發(fa)現絕緣燒(shao)焦或冒煙;③被試品內有不正(zheng)常的(de)聲音。
7)耐(nai)壓試驗前后(hou)應測(ce)量絕緣電阻,檢查絕緣情(qing)況。
試驗(yan)變壓器在(zai)做被試品的直流耐壓或泄露試驗(yan)時接線原理圖如圖6。
注:此試(shi)驗(yan)應先抽出短路(lu)桿“D”,圖6中所示(shi)。
圖中:VD—高壓硅堆(dui) R1—限流電阻 C1—高壓濾(lv)波電容(rong) FRC—阻容(rong)分壓器 CX—被試品 μA—帶(dai)保護微安表(biao)
泄(xie)露試驗中限流(liu)電(dian)阻(zu)(zu)R1選擇(ze)在(zai)額定輸(shu)出電(dian)壓(ya)時,輸(shu)出端短(duan)路電(dian)流(liu)不超過高壓(ya)硅堆的(de)*大整流(liu)。如電(dian)壓(ya)硅堆的(de)*大整流(liu)電(dian)流(liu)為100mA時用于60kV的(de)試驗裝置中,限流(liu)電(dian)阻(zu)(zu)按R1=60/0.1=600kΩ選擇(ze)。限流(liu)電(dian)阻(zu)(zu)還應(ying)具有足夠的(de)容量和(he)沿面(mian)放電(dian)距(ju)離。
高壓濾波電容C1一(yi)般選擇在0.01~0.1μF,當被試品的電容量(liang)很大時,C1可(ke)省(sheng)略不(bu)用(yong)。
泄露試驗的操作及注意事項
1)試(shi)驗前(qian)應先檢查(cha)被(bei)試(shi)品是否停電,接地放電,一切對外連線是否擦干凈。要(yao)嚴防將試(shi)驗電壓加(jia)到有人工(gong)作的(de)部位上(shang)去(qu)。
2)接好試驗(yan)裝置的接線(xian)(xian)后,應復查無(wu)誤(wu)后才可(ke)加(jia)壓。應特別注意檢查高壓設備及引線(xian)(xian)與(yu)(yu)地、與(yu)(yu)操作人員的**距離(li),被試品的外殼是否可(ke)靠接地,要按**規程中所規定的內容進行試驗(yan)。
3)對于大電(dian)容量(liang)設備應緩慢升壓(ya),防止被試品的(de)充電(dian)電(dian)流(liu)燒(shao)壞微安表(biao)。必要(yao)時應分級(ji)加壓(ya),分別讀取各級(ji)電(dian)壓(ya)下微安表(biao)的(de)穩(wen)定讀數。
4)試(shi)(shi)驗過程中,應密切監視(shi)被(bei)試(shi)(shi)品、試(shi)(shi)驗裝置、微安表(biao),一旦發(fa)生擊穿、閃爍等異常現象(xiang)應立即降壓,切斷(duan)電源,并查(cha)明原(yuan)因,詳細記錄。
5)試驗完(wan)畢,降(jiang)壓,切斷(duan)電(dian)源后應將(jiang)被試品及試驗裝置本身充分放電(dian)。
四(si)、注意事項
1、按照您所進行的(de)試(shi)驗接好工作線(xian)路。試(shi)驗變壓(ya)器的(de)外(wai)殼以及操作系統的(de)外(wai)殼必須(xu)可靠接地。試(shi)驗變壓(ya)器高壓(ya)繞(rao)(rao)組(zu)的(de)X端(高壓(ya)尾)以及測量繞(rao)(rao)組(zu)的(de)F端必須(xu)可靠接地。
2、做(zuo)串級(ji)(ji)試(shi)驗(yan)時,**級(ji)(ji)、第(di)三級(ji)(ji)試(shi)驗(yan)變壓器的(de)(de)低壓繞組的(de)(de)X端,測量繞組的(de)(de)F端以及高壓繞組的(de)(de)X端(高壓尾)均接(jie)本級(ji)(ji)試(shi)驗(yan)變壓器的(de)(de)外殼。**級(ji)(ji)、第(di)三級(ji)(ji)試(shi)驗(yan)變壓器的(de)(de)外殼必(bi)須通過絕緣支架接(jie)地(di)。
3、接通電(dian)源前,操作系統的調壓器必(bi)須調到零(ling)位(wei)后方可接通電(dian)源,合閘,開始升壓。
4、從零開始均勻旋(xuan)轉調壓(ya)(ya)(ya)(ya)器手輪升壓(ya)(ya)(ya)(ya)。升壓(ya)(ya)(ya)(ya)方(fang)法(fa)(fa)有(you):快速升壓(ya)(ya)(ya)(ya)法(fa)(fa),即(ji)20s逐(zhu)(zhu)級升壓(ya)(ya)(ya)(ya)法(fa)(fa);慢速升壓(ya)(ya)(ya)(ya)法(fa)(fa),即(ji)60s逐(zhu)(zhu)級升壓(ya)(ya)(ya)(ya)法(fa)(fa);極慢速升壓(ya)(ya)(ya)(ya)法(fa)(fa)供選(xuan)用。電壓(ya)(ya)(ya)(ya)從零開始按一定(ding)的(de)升壓(ya)(ya)(ya)(ya)方(fang)式和速度上(shang)升到您所(suo)需的(de)額(e)定(ding)試(shi)驗電壓(ya)(ya)(ya)(ya)的(de)75%后,在以每秒2%額(e)定(ding)試(shi)驗電壓(ya)(ya)(ya)(ya)的(de)速度升到您所(suo)需的(de)額(e)定(ding)電壓(ya)(ya)(ya)(ya),并(bing)密切注意測(ce)量(liang)儀表的(de)指(zhi)示以及被試(shi)品的(de)情況。升壓(ya)(ya)(ya)(ya)過程中或試(shi)驗過程中如發現測(ce)量(liang)儀表的(de)指(zhi)示及被試(shi)品情況異常,應立即(ji)降壓(ya)(ya)(ya)(ya),切斷(duan)電源,查(cha)明情況。
5、試驗(yan)完(wan)畢后,應在數秒內勻速的將調(diao)壓器返回至零(ling)位,然后切斷電源。
6、本產品不得超過額定參數使用。除(chu)試驗(yan)必須外,決(jue)不允許全電(dian)(dian)壓通(tong)電(dian)(dian)或斷(duan)電(dian)(dian)。
7、 再升壓(ya)(ya)或耐壓(ya)(ya)試(shi)驗過程中,如發現以下不正(zheng)常(chang)情況時,應立(li)即(ji)降壓(ya)(ya),切(qie)斷電源,停止試(shi)驗并查(cha)明(ming)原因(yin)。
⑴電(dian)壓表指針(zhen)擺動(dong)(dong)(或數(shu)字跳動(dong)(dong))很大
⑵電流表直線上升
被試品(pin)內有不正常的(de)聲(sheng)音
8、圖1中第9項系壓(ya)力(li)閥及壓(ya)力(li)表,為長(chang)期關(guan)閉狀態。每6個月開閥一(yi)次,以檢查(cha)(cha)SF6壓(ya)力(li),應不小于(yu)0.2MPa(檢查(cha)(cha)壓(ya)力(li)后立即(ji)關(guan)閉閥門),低于(yu)0.2MPa時應加(jia)SF6氣體,以增加(jia)氣絕緣。
9、耐壓(ya)實(shi)驗前(qian)后應測量被試設備的絕(jue)緣電阻,檢(jian)查(cha)絕(jue)緣情況。
10、當試驗變(bian)壓器長期不使用(yong)時,應(ying)放(fang)置(zhi)于通風(feng)、干燥、無(wu)陽光(guang)直射(she)的地方(fang)。
11、該產品(pin)不(bu)允許在高于45℃的溫度下長期存放(fang)、使用、放(fang)氣。
12、運(yun)輸(shu)搬運(yun)途(tu)中不得重力沖(chong)擊。
13、產品緊固件及(ji)壓力閥、壓力表不得擅自松(song)動。
14、使用本(ben)產品(pin)做高(gao)壓(ya)試(shi)驗時,出熟悉本(ben)說(shuo)明書外(wai),還必須嚴格執(zhi)行(xing)國家有關標準和操作(zuo)規(gui)程。可參照(zhao)GB311-83《高(gao)壓(ya)輸變(bian)設備的絕緣配(pei)合,高(gao)壓(ya)試(shi)驗技術》;《電氣設備預(yu)防(fang)性(xing)試(shi)驗規(gui)程》等。
五、試驗(yan)變壓器的容量選(xuan)擇(ze)
標稱試驗變壓器(qi)容量Pn的確定公式:Pn=kVn 2ωCt×10-9
式(shi)中:
Pn——標稱試驗變壓器容量(kVA)
Vn——試驗變壓(ya)器的額定輸出高壓(ya)的有效(xiao)值(zhi)(kV)
k ——**系數。k≥1,標(biao)稱電(dian)壓Vn≥1MV時,k=2;標(biao)稱電(dian)壓較低時,k值可取高(gao)一些。
Ct——被試品的(de)電容(rong)量(pF)
ω——角(jiao)頻率(lv),ω=2πf,f——試驗(yan)電源的頻率(lv)
被試設備的電容(rong)量Ct可由(you)交流電橋測(ce)出。Ct的變化很大,
可由設備的(de)類型(xing)而定。
典型數據如下:
簡單的(de)棒式(shi)或懸式(shi)絕緣(yuan)子 幾十(shi)微法(fa)
簡單(dan)的分級套管(guan) 100~1000pF
電壓互感(gan)器 200 ~ 500pF
電力(li)變(bian)壓器 < 1000kVA~1000pF
> 1000kVA 1000~10000pF
高壓電力電纜和油浸(jin)紙絕(jue)緣(yuan) 250~300pF/m
氣(qi)體絕緣 ~60pF/m
封閉變電站,SF6氣體絕緣 100~10000Pf;
對于不(bu)同的(de)試驗電壓(ya)Vn,選擇不(bu)同的(de)(適當的(de))**系數k。
以下(xia)列出不同的(de)Vn所選用的(de)k值供參考。
Vn =50~100kV k = 4
Vn =150~300kV k = 3
Vn > 300kV k = 2
一、概述
工(gong)頻耐壓試驗是鑒定電(dian)力(li)設備絕(jue)緣強度的(de)*嚴格(ge)、*有(you)效和*直接的(de)方法。它能檢查出那些危險性較大的(de)集中缺陷(xian),對(dui)判斷電(dian)力(li)設備能否繼續參加運行具有(you)決定性作(zuo)用,是保(bao)證設備絕(jue)緣水平、避免發生(sheng)絕(jue)緣事故的(de)重要(yao)手段。
本裝置是根(gen)據國(guo)家*新電力(li)行業標(biao)準而設計的、性能先進的耐壓試(shi)驗設備,用于對各種電器產品、電氣元件、絕(jue)緣(yuan)(yuan)材料(liao)等進行規定電壓下的絕(jue)緣(yuan)(yuan)強度(du)試(shi)驗,以考核產品的絕(jue)緣(yuan)(yuan)水(shui)平,發現被試(shi)品的絕(jue)緣(yuan)(yuan)缺陷,衡量(liang)過電壓的能力(li)。
二、產(chan)品特點
監視功能:高壓(ya)(ya)電壓(ya)(ya) 低壓(ya)(ya)電流 零位指(zhi)示(shi) 電源指(zhi)示(shi) 工作指(zhi)示(shi) 計時(shi)指(zhi)示(shi)
保護(hu)(hu)功能:過流保護(hu)(hu)、零位啟(qi)動保護(hu)(hu)、聲光語(yu)言報警提醒
采用新(xin)型時(shi)間繼電器,計(ji)時(shi)范圍更廣(1S~99H)
采(cai)用新型電(dian)(dian)流繼電(dian)(dian)器,更(geng)(geng)**、更(geng)(geng)可靠(kao),確(que)保人身及設備**。
試驗變壓(ya)器(qi)高壓(ya)線圈為圓筒多(duo)層塔式,由(you)上等聚酯漆(qi)包(bao)線及高耐壓(ya)值絕(jue)緣材料(liao)繞制而成。
試驗變壓器(5kVA以上)裝有(you)可移動(dong)的鐵(tie)輪。具有(you)重量輕、體積小、移動(dong)方便、性能(neng)優越(yue)等特點。
三、設備組成
1、選型配置
標準配置
|
□ 分體式
|
操作部分:
□箱式(不大(da)于5kVA) / □臺式
容(rong)量: kVA(小于200kVA)
輸入:□AC220V / □AC380V
|
試驗變(bian)壓(ya)器:
□交流 / □交直流
□油變(bian) / □干變(bian) / □氣變(bian)
容量: kVA(小于200kVA)
輸出(chu):AC kV(小(xiao)于300kVA)
|
□ 一體式
|
□箱式(shi)(不大于20kV) / □臺式(shi)(不大于30kV)
容(rong)量(liang): kVA(小于(yu)300kVA)
輸入:□AC220V / □AC380V 輸出:AC kV(不大于30kV)
|
客戶選配
|
□標準高壓(ya)分(fen)壓(ya)器
|
□保護(hu)球隙
|
□直流(liu)微安表
|
□放**
|
□保(bao)護水阻(zu)
|
□高壓濾波電容
|
其它(ta):
|
2、對應實物
四、技術指標
1、使用條件(jian):
(1)工作場所應無嚴重影響絕緣的氣體、蒸(zheng)汽(qi)、化學(xue)性塵埃(ai)及其它爆炸性和腐蝕性介(jie)質。
(2)環境溫(wen)度(du) -20~+50℃
(3)環境(jing)濕度 ≤85% RH(無凝結水)
2、控制箱(臺)參數:(常(chang)規(gui)參數見下表)
規格(ge)
|
容量(liang)
|
輸(shu) 入 電 源
|
輸 出 電 壓(ya)
|
重量(liang)(kg)
|
相(xiang)數(shu)
|
(V)
|
(A)
|
(V)
|
(A)
|
2/220
|
2
|
1
|
220
|
10
|
0-250
|
8
|
14
|
3/220
|
3
|
1
|
220
|
15
|
0-250
|
12
|
16
|
5/220
|
5
|
1
|
220
|
25
|
0-250
|
20
|
18
|
10/220
|
10
|
1
|
220
|
50
|
0-250
|
40
|
80
|
15/380
|
15
|
2
|
380
|
37.5
|
0-430
|
34.8
|
90
|
20/380
|
20
|
2
|
380
|
50
|
0-430
|
46.5
|
100
|
25/380
|
25
|
2
|
380
|
62.5
|
0-430
|
58.1
|
120
|
30/380
|
30
|
2
|
380
|
75
|
0-430
|
69.7
|
140
|
50/380
|
50
|
2
|
380
|
125
|
0-430
|
116.2
|
160
|
100/380
|
100
|
2
|
380
|
250
|
0-430
|
232.5
|
250
|
說明:如有(you)特殊參(can)數(shu)(shu)要求,可按用戶的技術參(can)數(shu)(shu)進行設計制(zhi)作。
3、試驗變壓器參數:(常規參數見下表(biao))
規(gui)格(ge)
|
容量
kVA
|
低壓側(ce)
|
高壓(ya)側
|
高(gao)壓(ya)側(交直(zhi)流變(bian)壓(ya)器(qi))
|
測量變(bian)比
|
60分鐘溫升℃
|
阻抗電壓%
|
空載電流(liu)
%
|
質量(liang)
kg
|
電壓
V
|
電(dian)流
A
|
交流輸出
|
直流輸出
|
電壓kV
|
電流
|
電壓(ya)kV
|
電流
|
1.5/50
|
1.5
|
200
|
7.5
|
50
|
30
|
70
|
21.4
|
500
|
50
|
10
|
<4
|
19.5
|
3/50
|
3
|
200
|
15
|
50
|
60
|
70
|
42.9
|
500
|
50
|
10
|
<4
|
27
|
5/50
|
5
|
200
|
25
|
50
|
100
|
70
|
71.4
|
500
|
50
|
10
|
<4
|
52
|
10/50
|
10
|
200
|
50
|
50
|
200
|
70
|
142.9
|
500
|
50
|
10
|
<4
|
80
|
15/50
|
15
|
400
|
37.5
|
50
|
300
|
70
|
214.3
|
500
|
50
|
8
|
<4
|
120
|
20/50
|
20
|
400
|
50
|
50
|
400
|
70
|
285.7
|
500
|
50
|
8
|
<4
|
140
|
30/50
|
30
|
400
|
75
|
50
|
600
|
70
|
428.6
|
500
|
50
|
8
|
<4
|
155
|
50/50
|
50
|
400
|
125
|
50
|
1000
|
70
|
714.3
|
500
|
50
|
8
|
<4
|
184
|
10/100
|
10
|
200
|
50
|
100
|
100
|
140
|
71.4
|
1000
|
50
|
10
|
<4
|
135
|
15/100
|
15
|
400
|
37.5
|
100
|
150
|
140
|
107.1
|
1000
|
50
|
8
|
<4
|
150
|
20/100
|
20
|
400
|
50
|
100
|
200
|
140
|
142.9
|
1000
|
50
|
8
|
<4
|
215
|
30/100
|
30
|
400
|
75
|
100
|
300
|
140
|
214.3
|
1000
|
50
|
8
|
<4
|
250
|
50/100
|
50
|
400
|
125
|
100
|
500
|
140
|
357.1
|
1000
|
50
|
8
|
<4
|
290
|
10/150
|
10
|
200
|
50
|
100
|
66.7
|
140
|
47.6
|
1500
|
50
|
10
|
<4
|
180
|
15/150
|
15
|
400
|
37.5
|
150
|
100
|
210
|
71.4
|
1500
|
50
|
8
|
<4
|
200
|
20/150
|
30
|
400
|
50
|
150
|
133.3
|
210
|
95.2
|
1500
|
50
|
8
|
<4
|
220
|
30/150
|
30
|
400
|
75
|
150
|
200
|
210
|
142.9
|
1500
|
50
|
8
|
<4
|
280
|
50/150
|
50
|
400
|
125
|
150
|
333.3
|
210
|
238.1
|
1500
|
50
|
8
|
<4
|
340
|
說明:如有特(te)殊參數要求(qiu),可按用戶的技術參數進行(xing)設(she)計制作。
上(shang)表的重(zhong)量以(yi)油(you)浸式試(shi)驗變(bian)壓(ya)器(qi)(qi)為(wei)例(li),干式試(shi)驗變(bian)壓(ya)器(qi)(qi)和(he)充氣式試(shi)驗變(bian)壓(ya)器(qi)(qi)稍有(you)不同。
五、接線及工作原理
1、調(diao)壓部分接線及原理
調(diao)壓部(bu)(bu)分(fen)由(you)控制部(bu)(bu)分(fen)和試驗(yan)變壓器組成。控制部(bu)(bu)分(fen)是由(you)接觸式調(diao)壓器及其控制、保護、測量、信號電路組成。試驗(yan)變壓器由(you)低壓繞組、高壓繞組、儀(yi)表繞組三部(bu)(bu)分(fen)組成。
試(shi)(shi)驗(yan)變(bian)(bian)壓(ya)(ya)器為交直流兩用時(shi)(shi),試(shi)(shi)驗(yan)變(bian)(bian)壓(ya)(ya)器配置(zhi)了高壓(ya)(ya)硅(gui)堆(油變(bian)(bian)、氣變(bian)(bian)為內置(zhi),干變(bian)(bian)為外(wai)置(zhi)),高壓(ya)(ya)可輸(shu)出(chu)(chu)(chu)交流和直流。輸(shu)出(chu)(chu)(chu)交流時(shi)(shi),要求接入短(duan)路桿(油變(bian)(bian)、氣變(bian)(bian))或去掉外(wai)置(zhi)硅(gui)堆(干變(bian)(bian));輸(shu)出(chu)(chu)(chu)直流時(shi)(shi),要求擰出(chu)(chu)(chu)短(duan)路桿(油變(bian)(bian)、氣變(bian)(bian))或加上(shang)外(wai)置(zhi)硅(gui)堆(干變(bian)(bian))
通過接入(ru)工頻(pin)電(dian)源,調(diao)節調(diao)壓器,以獲(huo)得所需要的試驗高壓電(dian)壓值(zhi)。其(qi)工作原理見圖1:
2、試驗部分接線及原理
做耐(nai)壓試(shi)驗時,控制部分、變(bian)壓器的(de)接地端(duan)及(ji)高壓尾必須(xu)可靠接地。有條件的(de)情況(kuang)下,做工頻耐(nai)壓試(shi)驗請加上(shang)限(xian)流(liu)電阻(zu)、標準高壓分壓器、球隙保(bao)護電阻(zu)及(ji)保(bao)護球隙,如圖(tu)3。
做(zuo)直流(liu)耐壓(ya)試驗(yan)請另外加上微安表(biao),微安表(biao)必須接在(zai)(zai)硅堆和被(bei)試器之間,油(you)變(bian)或氣(qi)變(bian)一般(ban)擰(ning)在(zai)(zai)高(gao)(gao)壓(ya)頭上面(要求(qiu)擰(ning)出短路桿),干變(bian)擰(ning)在(zai)(zai)外置(zhi)硅堆上面;為了更準確顯(xian)示(shi)高(gao)(gao)壓(ya)直流(liu)泄漏電流(liu),請將分壓(ya)器的高(gao)(gao)壓(ya)線接在(zai)(zai)微安表(biao)和硅堆之間,(油(you)變(bian)、氣(qi)變(bian))如圖4,(干變(bian))如圖5。
耐(nai)壓試(shi)驗中限流電(dian)阻(zu)(zu)(zu)(zu)R1應根據試(shi)驗變壓器的額定(ding)容(rong)(rong)量來選擇。如高壓側額定(ding)輸出電(dian)流在100~300mA時,可(ke)取0.5~1Ω/V(試(shi)驗電(dian)壓);高壓側額定(ding)輸出電(dian)流為1A以上時,可(ke)取1Ω/V(試(shi)驗電(dian)壓)。常用(yong)水(shui)電(dian)阻(zu)(zu)(zu)(zu)作為限流電(dian)阻(zu)(zu)(zu)(zu),管子長度可(ke)按150kV/m考(kao)慮,管子粗細應具(ju)有(you)足夠(gou)的熱容(rong)(rong)量(水(shui)阻(zu)(zu)(zu)(zu)液(ye)配制方(fang)法:用(yong)蒸餾水(shui)加(jia)入適量硫酸銅配制成各種不同的阻(zu)(zu)(zu)(zu)值)。
球(qiu)間(jian)隙(xi)及保護(hu)電(dian)(dian)阻(zu):當電(dian)(dian)壓(ya)超(chao)過(guo)球(qiu)間(jian)隙(xi)整定(ding)值時(shi)(一般(ban)取試驗電(dian)(dian)壓(ya)的110%~120%),球(qiu)間(jian)隙(xi)放電(dian)(dian),對(dui)被試品起到保護(hu)作用。球(qiu)間(jian)隙(xi)保護(hu)電(dian)(dian)阻(zu)可按1Ω/V(試驗電(dian)(dian)壓(ya))選(xuan)取。
在工頻耐壓(ya)(ya)(ya)(ya)(ya)試(shi)驗(yan)(yan)中,低(di)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)側(ce)測(ce)量(liang)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)(儀表電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya))不是(shi)非常準確的(de),其(qi)原(yuan)因是(shi)由于試(shi)驗(yan)(yan)變(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)器(qi)存(cun)在著(zhu)(zhu)漏(lou)抗,在這(zhe)個漏(lou)抗上(shang)必然存(cun)在著(zhu)(zhu)壓(ya)(ya)(ya)(ya)(ya)降或容升,使(shi)試(shi)品上(shang)的(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)低(di)于或高于低(di)壓(ya)(ya)(ya)(ya)(ya)側(ce)測(ce)量(liang)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)表上(shang)反映出來(lai)的(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)。工頻耐壓(ya)(ya)(ya)(ya)(ya)試(shi)驗(yan)(yan)時,被(bei)試(shi)品上(shang)的(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)高于試(shi)驗(yan)(yan)變(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)器(qi)的(de)輸出電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya),也就是(shi)所謂容升現象。感應耐壓(ya)(ya)(ya)(ya)(ya)試(shi)驗(yan)(yan)時,試(shi)驗(yan)(yan)變(bian)(bian)壓(ya)(ya)(ya)(ya)(ya)器(qi)的(de)漏(lou)抗必然存(cun)在著(zhu)(zhu)壓(ya)(ya)(ya)(ya)(ya)降。為了準確測(ce)量(liang)被(bei)試(shi)品上(shang)所施加的(de)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya),因此常在高壓(ya)(ya)(ya)(ya)(ya)側(ce)接入標準高壓(ya)(ya)(ya)(ya)(ya)分(fen)壓(ya)(ya)(ya)(ya)(ya)器(qi)來(lai)測(ce)量(liang)電(dian)(dian)壓(ya)(ya)(ya)(ya)(ya)。
五(wu)、面(mian)板結構說明
1、操作(zuo)箱面板(ban)
控制箱為(wei)箱式(shi)鋁合(he)金(jin)結構,面板(ban)采用(yong)拉(la)絲(si)鋁合(he)金(jin)工藝,所有電器元件均裝(zhuang)(zhuang)在骨架上,便于(yu)安裝(zhuang)(zhuang)和維(wei)修。面板(ban)元件布置如(ru)下(xia):
2、操作臺面板
操作臺為臺式結構(gou),殼體為冷(leng)扎鋼板結構(gou),面(mian)板采用鋁合金拉(la)絲工藝(yi),面(mian)板元件布置如下:
六、操(cao)作指南
本(ben)裝置在操作之前應根據不(bu)同(tong)被試(shi)品的容量(liang)、電壓等級(ji),先計算好*大(da)工(gong)作電流,并(bing)調整(zheng)電流保護器(qi)。其試(shi)驗接線應參考本(ben)說明(ming)書(shu)中圖(tu)(tu)1、圖(tu)(tu)2、圖(tu)(tu)3、圖(tu)(tu)4、圖(tu)(tu)5,必須(xu)可靠(kao)接地。
1、操(cao)作(zuo)要點(dian)
(1)試(shi)(shi)驗(yan)(yan)(yan)前,應了(le)解(jie)被(bei)試(shi)(shi)品(pin)的試(shi)(shi)驗(yan)(yan)(yan)電壓,同時了(le)解(jie)被(bei)試(shi)(shi)品(pin)的其他試(shi)(shi)驗(yan)(yan)(yan)項目及以(yi)前的試(shi)(shi)驗(yan)(yan)(yan)結果。若被(bei)試(shi)(shi)品(pin)有缺陷(xian)或(huo)異(yi)常,應在消(xiao)除(chu)后再(zai)進行耐(nai)壓試(shi)(shi)驗(yan)(yan)(yan)。
(2)試驗現場應圍好遮攔(lan)或圍繩,掛(gua)好標示牌,并派專人監護。
(3)試(shi)驗前,被(bei)(bei)(bei)試(shi)品表(biao)面應擦拭干凈,將(jiang)被(bei)(bei)(bei)試(shi)品的外殼和非被(bei)(bei)(bei)試(shi)繞組可靠接地(di)。被(bei)(bei)(bei)試(shi)品為新沖(chong)油設備(bei)時,應按《規(gui)程》規(gui)定使油靜(jing)止(zhi)一定時間(jian)再升壓,對110kV及以下的充(chong)油電力(li)設備(bei),在注滿油后靜(jing)置時間(jian)應不少(shao)于(yu)24小時,對220kV及330kV的充(chong)油電力(li)設備(bei),靜(jing)置時間(jian)應不少(shao)于(yu)48小時。
(4)接好試驗接線(xian)后,應(ying)由有(you)經驗的(de)人(ren)員(yuan)檢查,確認無誤后方可(ke)升壓。
(5)升壓(ya)(ya)前,首先檢(jian)查調(diao)壓(ya)(ya)器(qi)是否在零(ling)位。調(diao)壓(ya)(ya)器(qi)在零(ling)位方可升壓(ya)(ya)。
(6)升壓過程中(zhong)不(bu)僅要(yao)監視電壓表的(de)變(bian)化(hua),還(huan)應監視電流表的(de)變(bian)化(hua),以(yi)及(ji)被試(shi)品電流的(de)變(bian)化(hua)。升壓時(shi)要(yao)均勻(yun)(yun)升壓,不(bu)能(neng)太快(kuai)。升至(zhi)規定試(shi)驗(yan)電壓時(shi),開始計算(suan)時(shi)間,時(shi)間到(dao)后,緩慢均勻(yun)(yun)降(jiang)(jiang)下電壓。絕不(bu)允許不(bu)降(jiang)(jiang)壓就先跳開電源開關(guan)。
(7)試驗中發現表針擺動或被試品有異(yi)常聲響、冒煙等應立(li)即(ji)降下(xia)電(dian)壓(ya),拉(la)開電(dian)源,在高(gao)壓(ya)側掛(gua)上(shang)接地(di)線后(hou),再查明原因。
(8)耐壓試驗(yan)前后均應測量被試品的絕(jue)緣電(dian)阻。
2、操作步驟(zou)
(1) 按試驗(yan)要求(qiu)將控制部分、試驗(yan)變壓(ya)器(qi)、被試品正確接(jie)(jie)好線,必須可(ke)靠接(jie)(jie)地,請參考圖(tu)1、圖(tu)2、圖(tu)3、圖(tu)4、圖(tu)5。
(2) 根據試驗的要求,整定“時間(jian)繼電器(qi)(qi)”及“過流(liu)繼電器(qi)(qi)”。
A 時間(jian)繼(ji)電器(qi)設置(zhi):
T1,T2,T3,T4設(she)置0~9任(ren)意數字(zi),T可設(she)置為H(小時),M(分鐘),S(秒)。
根據(ju)試驗要求,在1S~99H內可(ke)以任意設置定時時間。
B 過流繼電器設置:
過流(liu)(liu)動作設定值=過流(liu)(liu)繼(ji)電(dian)器刻度盤讀(du)數×測量變(bian)比×K,其(qi)中K為(wei)電(dian)流(liu)(liu)倍率/切除(chu)開(kai)關(guan)的狀態值,分(fen)別為(wei)X1,X2,OFF,電(dian)流(liu)(liu)倍率/切除(chu)開(kai)關(guan)處(chu)于×1,×2位(wei)置時,K值分(fen)別為(wei)1、2,切換為(wei)OFF擋(dang)時,K值為(wei)+∞。(注:不要使用OFF檔,因為(wei)會(hui)使變(bian)壓(ya)器失去過流(liu)(liu)保護功能而導致(zhi)設備(bei)損壞(huai)。測量變(bian)比為(wei)電(dian)流(liu)(liu)互感器的變(bian)比,沒有電(dian)流(liu)(liu)互感器時為(wei)1)。
(3) 接入(ru)電(dian)源,此(ci)時,“電(dian)源燈”亮,表示(shi)外部(bu)電(dian)源已引入(ru)。如“零(ling)(ling)位(wei)燈”亮,表示(shi)調壓器(qi)在零(ling)(ling)位(wei)。如“零(ling)(ling)位(wei)燈”不(bu)亮,應(ying)逆時針旋(xuan)轉調節(jie)調壓器(qi)手柄至“零(ling)(ling)位(wei)燈”亮,表示(shi)可(ke)進行調壓操作。
(4)按“啟(qi)動按鈕”。此時,“送電燈(deng)”,“電源(yuan)燈(deng)”和“零位燈(deng)”亮(liang);進入(ru)送電狀(zhuang)態。
(5)以2kV/S勻速(su)順時(shi)針(zhen)旋轉調壓(ya)器手柄至被試品規定的耐壓(ya)值,并密(mi)切注視電(dian)流(liu)表(直(zhi)流(liu)耐壓(ya)試驗時(shi),同(tong)時(shi)密(mi)切注視直(zhi)流(liu)微安表)。此時(shi),“電(dian)源燈”,“工作燈”亮;“零位燈”滅。
(6)根(gen)據(ju)試(shi)(shi)驗啟動“計時(shi)按鈕”,計時(shi)開始,并(bing)注意被試(shi)(shi)品的情況(kuang)。
(7)當耐壓(ya)計時(shi)到時(shi),操作臺(tai)自(zi)動聲光報警(jing)。應立(li)即逆時(shi)針旋轉調(diao)壓(ya)器(qi)手柄至零位,按(an)下停止(zhi)按(an)鈕和解除計時(shi)按(an)鈕自(zi)鎖狀態。此(ci)時(shi)“電源(yuan)燈(deng)(deng)”, “零位燈(deng)(deng)”亮,“工作燈(deng)(deng)”滅。試驗即告(gao)完畢
(8)拔掉電(dian)源,拆除接線,試驗(yan)結束。
(9)在升壓或(huo)耐壓過程中,如發生短路、閃絡、擊穿(chuan)過流時,過流繼電器動作,切(qie)斷(duan)主(zhu)回路。此時應將(jiang)調壓器逆時針(zhen)旋轉至(zhi)零位,切(qie)斷(duan)電源,并查(cha)明原因,并作詳細記錄。
(10)試(shi)(shi)驗完畢,降壓,切斷電源后應用放**將被試(shi)(shi)品(pin)及試(shi)(shi)驗裝置(zhi)本身充(chong)分放電。
七(qi)、產品(pin)維護
1、開箱驗收時(shi),應檢查主控回路接(jie)(jie)線(xian)是否松動(dong),調壓器電刷是否接(jie)(jie)觸良好;
2、長期不用(yong)時,使用(yong)前應用(yong)500V兆歐表測(ce)量絕緣電阻,其(qi)阻值不低于0.5MΩ;
3、電源電壓應符合(he)控制(zhi)箱(臺)銘牌(pai)上(shang)的輸(shu)入電壓值;
4、本裝置設(she)有過電(dian)流(liu)保(bao)護,出廠已調整為額(e)定(ding)(ding)電(dian)流(liu)的50%。用于(yu)小負載時,應根據被試(shi)品的額(e)定(ding)(ding)容量電(dian)流(liu)重新設(she)定(ding)(ding);
5、使用完畢(bi)后,應關好控(kong)制(zhi)箱(臺)門,以(yi)保(bao)持控(kong)制(zhi)箱(臺)內部清潔。
八、注(zhu)意事項
1、按(an)照您所進行(xing)的(de)試(shi)驗接(jie)(jie)好工作(zuo)線路。試(shi)驗變壓器(qi)的(de)外(wai)殼(ke)以及操作(zuo)系統的(de)外(wai)殼(ke)必(bi)須可(ke)靠接(jie)(jie)地。試(shi)驗變壓器(qi)的(de)高壓繞組的(de)X端(高壓尾(wei))以及測量繞組的(de)F端必(bi)須可(ke)靠接(jie)(jie)地。
2、做串級試(shi)驗(yan)時(shi),**級、第(di)三級試(shi)驗(yan)變(bian)壓器的(de)低(di)壓繞組成X端,測量繞組的(de)F端以及高(gao)壓繞組的(de)X端(高(gao)壓端)均接本級試(shi)驗(yan)變(bian)壓器具外(wai)殼。**級、第(di)三級試(shi)驗(yan)變(bian)壓器的(de)外(wai)殼必(bi)須通過絕緣支架(jia)接地。
3、接通電(dian)源前,操作系統的調(diao)壓(ya)(ya)器(qi)(qi)必須調(diao)到零位后(hou)方(fang)可(ke)接通電(dian)源,合閘,開(kai)始(shi)升(sheng)壓(ya)(ya)。從零開(kai)始(shi)勻(yun)速(su)旋(xuan)轉(zhuan)調(diao)壓(ya)(ya)器(qi)(qi)手輪升(sheng)壓(ya)(ya)。升(sheng)壓(ya)(ya)方(fang)式有:快速(su)升(sheng)壓(ya)(ya)法(fa)(fa),即(ji)20s逐級升(sheng)壓(ya)(ya)法(fa)(fa);慢速(su)升(sheng)壓(ya)(ya)法(fa)(fa),即(ji)60s逐級升(sheng)壓(ya)(ya)法(fa)(fa);極慢速(su)升(sheng)壓(ya)(ya)法(fa)(fa)供(gong)選用。電(dian)壓(ya)(ya)從零開(kai)始(shi)按一定(ding)的升(sheng)壓(ya)(ya)方(fang)式和速(su)度上升(sheng)到您所需(xu)的額(e)定(ding)試驗(yan)(yan)電(dian)壓(ya)(ya)的75%后(hou),再以每秒2%額(e)定(ding)試驗(yan)(yan)電(dian)壓(ya)(ya)的速(su)度升(sheng)到您所需(xu)的試驗(yan)(yan)電(dian)壓(ya)(ya),并(bing)密(mi)切注意測量(liang)儀表的及(ji)被試品的情況(kuang)。升(sheng)壓(ya)(ya)過程中(zhong)或試驗(yan)(yan)過程中(zhong)如發(fa)現測量(liang)儀表的指示(shi)及(ji)被試品情況(kuang)異(yi)常(chang),應(ying)立即(ji)降壓(ya)(ya),切斷電(dian)源,查明情況(kuang)。
4、試驗完畢后,應在數秒內勻速的將(jiang)調壓器返(fan)回(hui)至零(ling)位,然后切斷電(dian)源。本(ben)產品(pin)不得超過額(e)定參數使用。
5、使(shi)用本產品做高壓(ya)試驗(yan)時,除(chu)熟悉(xi)本說明書(shu)外(wai),還必(bi)須嚴格(ge)執行國家有關標準和操作規(gui)程。可參(can)照GB311.1 – 97《高壓(ya)輸變設(she)備(bei)的絕(jue)緣配合,高壓(ya)試驗(yan)技術》;《電氣設(she)備(bei)預防性試驗(yan)規(gui)程》等
一、概述
智能耐壓(ya)試(shi)驗裝置(zhi)是根(gen)據國(guo)家(jia)*新電(dian)力(li)行(xing)業標準而(er)設(she)計的、性能先進(jin)的智能型耐壓(ya)試(shi)驗設(she)備,用于對各(ge)種電(dian)器產品、電(dian)氣元件(jian)、絕(jue)(jue)(jue)緣材料(liao)等進(jin)行(xing)規定電(dian)壓(ya)下的絕(jue)(jue)(jue)緣強度(du)試(shi)驗,以(yi)考(kao)核(he)產品的絕(jue)(jue)(jue)緣水平,發現(xian)被試(shi)品的絕(jue)(jue)(jue)緣缺(que)陷,衡量過電(dian)壓(ya)的能力(li)。廣泛(fan)應用于電(dian)工制造部(bu)門、電(dian)力(li)運行(xing)部(bu)門、科(ke)研單位和高等院(yuan)校。
二(er)、產品特(te)點(dian)
1. 320×240液晶顯示器、高速熱敏打印機。
2. 高(gao)壓(ya)電壓(ya)、高(gao)壓(ya)電流(liu)、低壓(ya)電壓(ya)、低壓(ya)電流(liu)4路測量方(fang)式,高(gao)精度傳感器和高(gao)性能14位(wei)AD采集芯片。
3. 人機對話全鍵盤操作(zuo)方式,智(zhi)能化工作(zuo)全過程,任選自動方式和手動方式。
4. 實時顯示高(gao)壓(ya)電壓(ya)、高(gao)壓(ya)電流(liu)、低(di)壓(ya)電壓(ya)、低(di)壓(ya)電流(liu),時間(jian)及耐(nai)壓(ya)結果(guo),顯示直觀明(ming)了。
5. 完善(shan)的過壓(ya)、過流保護,任意設定(ding)輸(shu)出電(dian)壓(ya)、高(gao)壓(ya)電(dian)流上(shang)限、低壓(ya)電(dian)流上(shang)限和(he)計時時間。
6. 具有回(hui)(hui)零(ling)檢測功能,回(hui)(hui)零(ling)確定后(hou)才可(ke)(ke)進行(xing)試驗,**可(ke)(ke)靠(kao)。
7. 具有(you)絕緣(yuan)電阻測試功(gong)能,直接反映被試品(pin)絕緣(yuan)強度(du)。
8. 逼近式調(diao)壓(ya)算法(fa),到達設(she)定電壓(ya)后自動(dong)耐壓(ya)計時(shi),計時(shi)結(jie)束(shu)后自動(dong)降壓(ya)回零。
9. 超過設定高壓電(dian)(dian)流(liu)或低壓電(dian)(dian)流(liu)時自動切斷電(dian)(dian)壓輸出,降壓回零,并發生聲(sheng)光報警(jing)。
10. 精良的(de)軟硬件抗干(gan)擾(rao)設計,多種(zhong)抗干(gan)擾(rao)手段(duan),適應惡(e)劣電磁(ci)環境。
11. 自動錯誤診(zhen)斷(duan),易于發現和解(jie)決(jue)問題。
12. 可選配無線遙控(kong)控(kong)制功能、遠程通信、門聯鎖(suo)警鈴(ling)、外接(jie)(jie)分壓(ya)器校驗接(jie)(jie)口等。
三、設備組(zu)成
1、選型配置(zhi)
標(biao)準配置
|
□ 分體式
|
操作(zuo)部(bu)分:
□箱式(shi)(不(bu)大于5kVA) / □臺式(shi)
容(rong)量: kVA(小于200kVA)
輸入:□AC220V / □AC380V
|
試(shi)驗變壓器:
□交(jiao)流(liu) / □交(jiao)直流(liu)
□油變 / □干(gan)變 / □氣變
容量: kVA(小(xiao)于200kVA)
輸出(chu):AC kV(小于300kVA)
|
□ 一體式
|
□箱式(不大于20kV) / □臺式(不大于30kV)
容量: kVA(小于(yu)300kVA)
輸入:□AC220V / □AC380V 輸出(chu):AC kV(不大于30kV)
|
客(ke)戶選配
|
□標準高(gao)壓(ya)分壓(ya)器
|
□保護球(qiu)隙
|
□直流微安表
|
□放**
|
□保護水(shui)阻
|
□高壓濾波電容
|
其它:
|
2、對應實(shi)物(wu)
四、技(ji)術指(zhi)標
1、使用條件:
(1)工作場所(suo)應(ying)無嚴重影(ying)響(xiang)絕(jue)緣(yuan)的氣體、蒸(zheng)汽、化(hua)學性塵埃及(ji)其它爆炸性和腐蝕性介質。
(2)環境(jing)溫度 -20~+50℃
(3)環境(jing)濕度 ≤85% RH(無(wu)凝結水)
2、控制箱(xiang)(臺(tai))參(can)數:(常(chang)規參(can)數見下表)
(1)計時范(fan)圍(wei):0-999S
(3)電壓精度 ≤1.5% ±1個字(F.S)
(4)電(dian)流精度 ≤1.5% ±1個(ge)字(F.S)
規(gui)格
|
容(rong)量
|
輸 入 電(dian) 源
|
輸(shu) 出 電(dian) 壓
|
重量(kg)
|
相數(shu)
|
(V)
|
(A)
|
(V)
|
(A)
|
2/220
|
2
|
1
|
220
|
10
|
0-250
|
8
|
14
|
3/220
|
3
|
1
|
220
|
15
|
0-250
|
12
|
16
|
5/220
|
5
|
1
|
220
|
25
|
0-250
|
20
|
18
|
10/220
|
10
|
1
|
220
|
50
|
0-250
|
40
|
80
|
15/380
|
15
|
2
|
380
|
37.5
|
0-430
|
34.8
|
90
|
20/380
|
20
|
2
|
380
|
50
|
0-430
|
46.5
|
100
|
25/380
|
25
|
2
|
380
|
62.5
|
0-430
|
58.1
|
120
|
30/380
|
30
|
2
|
380
|
75
|
0-430
|
69.7
|
140
|
50/380
|
50
|
2
|
380
|
125
|
0-430
|
116.2
|
160
|
100/380
|
100
|
2
|
380
|
250
|
0-430
|
232.5
|
250
|
說明:如有特殊參數要求(qiu),可按用戶的(de)技術參數進(jin)行設計制作。
3、試(shi)驗變(bian)壓器參數(shu):(常規參數(shu)見(jian)下表)
規(gui)格
|
容量
kVA
|
低(di)壓側
|
高壓側
|
高(gao)壓側(交直流變壓器)
|
測(ce)量變比
|
60分(fen)鐘(zhong)溫升℃
|
阻(zu)抗電壓(ya)%
|
空載電流(liu)
%
|
質量
kg
|
電(dian)壓(ya)
V
|
電流(liu)
A
|
交流輸(shu)出
|
直流輸出(chu)
|
電壓kV
|
電流
|
電壓kV
|
電流
|
1.5/50
|
1.5
|
200
|
7.5
|
50
|
30
|
70
|
21.4
|
500
|
50
|
10
|
<4
|
19.5
|
3/50
|
3
|
200
|
15
|
50
|
60
|
70
|
42.9
|
500
|
50
|
10
|
<4
|
27
|
5/50
|
5
|
200
|
25
|
50
|
100
|
70
|
71.4
|
500
|
50
|
10
|
<4
|
52
|
10/50
|
10
|
200
|
50
|
50
|
200
|
70
|
142.9
|
500
|
50
|
10
|
<4
|
80
|
15/50
|
15
|
400
|
37.5
|
50
|
300
|
70
|
214.3
|
500
|
50
|
8
|
<4
|
120
|
20/50
|
20
|
400
|
50
|
50
|
400
|
70
|
285.7
|
500
|
50
|
8
|
<4
|
140
|
30/50
|
30
|
400
|
75
|
50
|
600
|
70
|
428.6
|
500
|
50
|
8
|
<4
|
155
|
50/50
|
50
|
400
|
125
|
50
|
1000
|
70
|
714.3
|
500
|
50
|
8
|
<4
|
184
|
10/100
|
10
|
200
|
50
|
100
|
100
|
140
|
71.4
|
1000
|
50
|
10
|
<4
|
135
|
15/100
|
15
|
400
|
37.5
|
100
|
150
|
140
|
107.1
|
1000
|
50
|
8
|
<4
|
150
|
20/100
|
20
|
400
|
50
|
100
|
200
|
140
|
142.9
|
1000
|
50
|
8
|
<4
|
215
|
30/100
|
30
|
400
|
75
|
100
|
300
|
140
|
214.3
|
1000
|
50
|
8
|
<4
|
250
|
50/100
|
50
|
400
|
125
|
100
|
500
|
140
|
357.1
|
1000
|
50
|
8
|
<4
|
290
|
10/150
|
10
|
200
|
50
|
100
|
66.7
|
140
|
47.6
|
1500
|
50
|
10
|
<4
|
180
|
15/150
|
15
|
400
|
37.5
|
150
|
100
|
210
|
71.4
|
1500
|
50
|
8
|
<4
|
200
|
20/150
|
30
|
400
|
50
|
150
|
133.3
|
210
|
95.2
|
1500
|
50
|
8
|
<4
|
220
|
30/150
|
30
|
400
|
75
|
150
|
200
|
210
|
142.9
|
1500
|
50
|
8
|
<4
|
280
|
50/150
|
50
|
400
|
125
|
150
|
333.3
|
210
|
238.1
|
1500
|
50
|
8
|
<4
|
340
|
說明:如有特殊(shu)參(can)數(shu)(shu)要求,可按用(yong)戶的技術參(can)數(shu)(shu)進行設計制作。
上表的重量以油浸式試驗變(bian)壓(ya)(ya)器(qi)為例(li),干(gan)式試驗變(bian)壓(ya)(ya)器(qi)和充氣(qi)式試驗變(bian)壓(ya)(ya)器(qi)稍有不同(tong)。
五(wu)、接線(xian)及工作原理
1、調(diao)壓(ya)部分接線及原理
調壓(ya)部(bu)分(fen)由(you)控(kong)制(zhi)部(bu)分(fen)和試驗(yan)變(bian)壓(ya)器(qi)組成(cheng)。控(kong)制(zhi)部(bu)分(fen)是由(you)接觸式調壓(ya)器(qi)、單片(pian)機控(kong)制(zhi)系統、液晶、打印(yin)機、信號測(ce)量、電(dian)路保護(hu)組成(cheng)。試驗(yan)變(bian)壓(ya)器(qi)由(you)低壓(ya)繞組、高壓(ya)繞組、儀(yi)表繞組三部(bu)分(fen)組成(cheng)。
試(shi)驗(yan)變壓(ya)(ya)器(qi)為交直流兩用(yong)時(shi)(shi),試(shi)驗(yan)變壓(ya)(ya)器(qi)配置了高壓(ya)(ya)硅堆(油變、氣變為內置,干變為外置),高壓(ya)(ya)可輸(shu)(shu)出交流和直流。輸(shu)(shu)出交流時(shi)(shi),要求接入短路桿(油變、氣變)或去(qu)掉(diao)外置硅堆(干變);輸(shu)(shu)出直流時(shi)(shi),要求擰(ning)出短路桿(油變、氣變)或加上外置硅堆(干變)
通過(guo)接入工頻電源,調節調壓(ya)器,以獲得所需(xu)要的試驗高壓(ya)電壓(ya)值。其工作(zuo)原理(li)見圖1:
2、試驗部分接線(xian)及原理(li)
做(zuo)耐壓試驗時,控制部分、變壓器(qi)的(de)接(jie)地端及(ji)(ji)高壓尾必(bi)須可(ke)靠接(jie)地。有(you)條件的(de)情況(kuang)下,做(zuo)工頻耐壓試驗請加上限流電阻(zu)、標準高壓分壓器(qi)、球隙保(bao)(bao)護電阻(zu)及(ji)(ji)保(bao)(bao)護球隙,如圖3。
做直流耐壓(ya)試驗請另外(wai)加上微(wei)安(an)表(biao),微(wei)安(an)表(biao)必須(xu)接(jie)在(zai)(zai)硅堆(dui)和(he)被(bei)試器之(zhi)間,油(you)變或氣變一(yi)般(ban)擰在(zai)(zai)高壓(ya)頭上面(mian)(要求擰出短(duan)路桿(gan)),干(gan)變擰在(zai)(zai)外(wai)置硅堆(dui)上面(mian);為了更準確顯(xian)示高壓(ya)直流泄漏電流,請將分壓(ya)器的高壓(ya)線接(jie)在(zai)(zai)微(wei)安(an)表(biao)和(he)硅堆(dui)之(zhi)間,(油(you)變、氣變)如圖4,(干(gan)變)如圖5。
耐壓(ya)試驗(yan)中(zhong)限(xian)流(liu)電(dian)阻(zu)R1應根據(ju)試驗(yan)變壓(ya)器(qi)的額(e)定(ding)(ding)容量(liang)來選擇。如(ru)高壓(ya)側額(e)定(ding)(ding)輸出電(dian)流(liu)在100~300mA時(shi),可取(qu)0.5~1Ω/V(試驗(yan)電(dian)壓(ya));高壓(ya)側額(e)定(ding)(ding)輸出電(dian)流(liu)為(wei)1A以上時(shi),可取(qu)1Ω/V(試驗(yan)電(dian)壓(ya))。常用水(shui)(shui)電(dian)阻(zu)作為(wei)限(xian)流(liu)電(dian)阻(zu),管(guan)子(zi)長度可按(an)150kV/m考慮(lv),管(guan)子(zi)粗(cu)細(xi)應具有足夠的熱(re)容量(liang)(水(shui)(shui)阻(zu)液(ye)配制方(fang)法:用蒸餾(liu)水(shui)(shui)加(jia)入適量(liang)硫酸銅配制成(cheng)各種不同(tong)的阻(zu)值)。
球(qiu)間隙(xi)(xi)及保(bao)護(hu)電(dian)阻(zu):當(dang)電(dian)壓(ya)超過球(qiu)間隙(xi)(xi)整(zheng)定值(zhi)時(一般取(qu)試(shi)驗電(dian)壓(ya)的110%~120%),球(qiu)間隙(xi)(xi)放電(dian),對被試(shi)品起到保(bao)護(hu)作用。球(qiu)間隙(xi)(xi)保(bao)護(hu)電(dian)阻(zu)可按1Ω/V(試(shi)驗電(dian)壓(ya))選取(qu)。
在(zai)工(gong)頻(pin)耐壓(ya)(ya)(ya)(ya)(ya)試驗(yan)中,低(di)電(dian)壓(ya)(ya)(ya)(ya)(ya)側測(ce)量電(dian)壓(ya)(ya)(ya)(ya)(ya)(儀表電(dian)壓(ya)(ya)(ya)(ya)(ya))不是非常準(zhun)確的(de)(de),其(qi)原因是由(you)于試驗(yan)變壓(ya)(ya)(ya)(ya)(ya)器存在(zai)著漏(lou)抗(kang)(kang),在(zai)這個漏(lou)抗(kang)(kang)上(shang)(shang)必然存在(zai)著壓(ya)(ya)(ya)(ya)(ya)降(jiang)或(huo)容(rong)(rong)升,使試品上(shang)(shang)的(de)(de)電(dian)壓(ya)(ya)(ya)(ya)(ya)低(di)于或(huo)高(gao)(gao)于低(di)壓(ya)(ya)(ya)(ya)(ya)側測(ce)量電(dian)壓(ya)(ya)(ya)(ya)(ya)表上(shang)(shang)反映出來的(de)(de)電(dian)壓(ya)(ya)(ya)(ya)(ya)。工(gong)頻(pin)耐壓(ya)(ya)(ya)(ya)(ya)試驗(yan)時,被試品上(shang)(shang)的(de)(de)電(dian)壓(ya)(ya)(ya)(ya)(ya)高(gao)(gao)于試驗(yan)變壓(ya)(ya)(ya)(ya)(ya)器的(de)(de)輸出電(dian)壓(ya)(ya)(ya)(ya)(ya),也就(jiu)是所謂容(rong)(rong)升現象。感(gan)應耐壓(ya)(ya)(ya)(ya)(ya)試驗(yan)時,試驗(yan)變壓(ya)(ya)(ya)(ya)(ya)器的(de)(de)漏(lou)抗(kang)(kang)必然存在(zai)著壓(ya)(ya)(ya)(ya)(ya)降(jiang)。為(wei)了準(zhun)確測(ce)量被試品上(shang)(shang)所施加的(de)(de)電(dian)壓(ya)(ya)(ya)(ya)(ya),因此常在(zai)高(gao)(gao)壓(ya)(ya)(ya)(ya)(ya)側接入標準(zhun)高(gao)(gao)壓(ya)(ya)(ya)(ya)(ya)分(fen)壓(ya)(ya)(ya)(ya)(ya)器來測(ce)量電(dian)壓(ya)(ya)(ya)(ya)(ya)。
六、操(cao)作要點
1、試驗(yan)(yan)前,應(ying)了(le)解(jie)被(bei)試品的(de)試驗(yan)(yan)電壓,同時了(le)解(jie)被(bei)試品的(de)其他試驗(yan)(yan)項目及以前的(de)試驗(yan)(yan)結(jie)果。若被(bei)試品有缺陷或異常,應(ying)在消除后再進行耐壓試驗(yan)(yan)。
2、試驗現場應圍好(hao)遮攔或圍繩,掛好(hao)標示牌,并派專人監護。
3、試(shi)(shi)驗前,被(bei)(bei)試(shi)(shi)品(pin)表面應(ying)擦拭干凈(jing),將被(bei)(bei)試(shi)(shi)品(pin)的外(wai)殼和非(fei)被(bei)(bei)試(shi)(shi)繞組可靠接地。被(bei)(bei)試(shi)(shi)品(pin)為新(xin)沖油(you)(you)設(she)(she)備(bei)(bei)時(shi),應(ying)按(an)《規(gui)程》規(gui)定使油(you)(you)靜止一定時(shi)間再升壓,對(dui)110kV及以(yi)下的充(chong)(chong)油(you)(you)電力設(she)(she)備(bei)(bei),在注(zhu)滿油(you)(you)后(hou)靜置時(shi)間應(ying)不少于24小時(shi),對(dui)220kV及330kV的充(chong)(chong)油(you)(you)電力設(she)(she)備(bei)(bei),靜置時(shi)間應(ying)不少于48小時(shi)。
4、接(jie)好(hao)試驗接(jie)線后(hou),應由有經驗的人員檢查(cha),確認無誤后(hou)方可升壓(ya)。
5、升壓(ya)(ya)前,首(shou)先檢查(cha)調壓(ya)(ya)器是否在零位。調壓(ya)(ya)器在零位方可升壓(ya)(ya)。
6、升(sheng)壓(ya)(ya)過(guo)程中不(bu)(bu)(bu)僅要監(jian)視電(dian)(dian)壓(ya)(ya)的變(bian)化,還應監(jian)視電(dian)(dian)流的變(bian)化,以及被(bei)試品泄漏電(dian)(dian)流的變(bian)化。升(sheng)壓(ya)(ya)時要均勻升(sheng)壓(ya)(ya),不(bu)(bu)(bu)能(neng)太快。升(sheng)至規定試驗電(dian)(dian)壓(ya)(ya)時,開(kai)始計時,時間到后,緩慢均勻降(jiang)下電(dian)(dian)壓(ya)(ya)。絕不(bu)(bu)(bu)允(yun)許不(bu)(bu)(bu)降(jiang)壓(ya)(ya)就先跳開(kai)電(dian)(dian)源開(kai)關(guan)。
7、試(shi)驗中發現(xian)被(bei)試(shi)品(pin)有異(yi)常聲(sheng)響、冒煙(yan)等應立即降(jiang)下電壓(ya),拉開電源(yuan),在高(gao)壓(ya)側掛上(shang)接地線后,再查(cha)明原因。耐壓(ya)試(shi)驗前后均(jun)應測量(liang)被(bei)試(shi)品(pin)的絕緣電阻。
七、面板功能說明
打(da)印機(ji)(ji):打(da)印機(ji)(ji)是熱敏打(da)印機(ji)(ji),當試驗(yan)完(wan)成后(hou)按鍵盤上(shang)的(de)“打(da)印”按鈕打(da)印試驗(yan)結果(guo)。
RS232:RS232是與計算機相連的串(chuan)口通信接口,是用戶選配(pei)接口,本(ben)裝置沒有配(pei)置這個接口。
LCD對比度(du)(du):因(yin)為液晶顯示屏在溫度(du)(du)和光線(xian)有(you)所不同時稍有(you)些(xie)變化,可以通(tong)過LCD對比度(du)(du)調(diao)節背光到適合(he)亮度(du)(du)。
液(ye)晶(jing): 320x240像素點(dian)陣(zhen)白色背光液(ye)晶(jing),在強光和陰暗環(huan)境下都十(shi)分清楚。
指示(shi)燈:由啟動燈、零位燈、指示(shi)燈三(san)個燈組(zu)成,啟動燈和警示(shi)燈是高亮(liang)七彩燈。
操作提示(shi):有(you)一些簡短的提示(shi)語句和安裝接線圖。
緊急(ji)開關(guan):在(zai)緊急(ji)情(qing)況(kuang)下按此(ci)開關(guan),即可以切(qie)斷(duan)變(bian)壓器(qi)電源(yuan),也可以切(qie)斷(duan)工作電源(yuan)。(箱式安裝(zhuang)在(zai)面板上,臺式安裝(zhuang)在(zai)柜(ju)體上)
鍵盤:由(you)上、下、左、右(you)、設(she)置、打印、確(que)定、取(qu)消8個鍵組(zu)成,是用戶(hu)和(he)設(she)備交互的終(zhong)端。
電(dian)源開關:工(gong)作電(dian)源,帶通電(dian)指(zhi)示燈(deng)。
八、軟件使用說明(ming)
按試(shi)驗(yan)要求將控制部分、試(shi)驗(yan)變(bian)壓器、被試(shi)品(pin)正(zheng)確接好線,必須(xu)可靠接地,請參考圖(tu)(tu)1、圖(tu)(tu)2、圖(tu)(tu)3、圖(tu)(tu)4、圖(tu)(tu)5。
1、開機使用
開機處于“歡(huan)迎(ying)界面”,如圖7:
根據鍵盤的(de)示圖8,按上(shang)↑、下↓、左←,右→可(ke)以切(qie)換“自(zi)動(dong)耐壓(ya)試(shi)驗(yan)”或(huo)“手(shou)(shou)動(dong)耐壓(ya)試(shi)驗(yan)”,在“自(zi)動(dong)試(shi)驗(yan)”或(huo)“手(shou)(shou)動(dong)試(shi)驗(yan)”里面選擇“交流試(shi)驗(yan)方(fang)式”或(huo)“直(zhi)流試(shi)驗(yan)方(fang)式”。如圖9
說(shuo)明:
(1)當(dang)配置的是交直(zhi)(zhi)流(liu)(liu)兩用控(kong)制部分時,使用直(zhi)(zhi)流(liu)(liu)輸出時軟(ruan)件操(cao)作請進(jin)入直(zhi)(zhi)流(liu)(liu)試(shi)驗方式(shi),交流(liu)(liu)輸出時軟(ruan)件操(cao)作請進(jin)入交流(liu)(liu)試(shi)驗方式(shi),如(ru)果選擇錯(cuo)誤(wu)會導致儀器顯示電(dian)壓(ya)(ya)會和(he)輸出實際電(dian)壓(ya)(ya)不一致。
(2)當(dang)配置的是交直流(liu)(liu)兩(liang)用變壓器時(shi),使(shi)用直流(liu)(liu)時(shi)請將變壓器的短(duan)路桿取出(chu),當(dang)使(shi)用交流(liu)(liu)時(shi)請將短(duan)路桿插入擰緊。
(3)如果配置的是交流(liu)(liu)控(kong)制部分(fen)時,軟件界面里(li)就(jiu)沒有(you)交直流(liu)(liu)試驗方式(如圖9)的選擇項。
選中試驗方(fang)式(shi)后,按(an)確定可(ke)以進入主界面,如圖10:
動態(tai)顯示區:一直(zhi)處于(yu)采集信號(hao),并顯示高(gao)壓電壓、高(gao)壓電流、低(di)壓電壓、低(di)壓電流。
結果(guo)顯(xian)(xian)(xian)示區:如果(guo)試驗沒(mei)有被擊穿時(shi),顯(xian)(xian)(xian)示平均(jun)(jun)高(gao)壓電(dian)壓,平均(jun)(jun)高(gao)壓電(dian)流(liu)(liu),平均(jun)(jun)低(di)壓電(dian)壓,平均(jun)(jun)低(di)壓電(dian)流(liu)(liu),絕(jue)緣電(dian)阻;否之,顯(xian)(xian)(xian)示峰(feng)值電(dian)壓,峰(feng)值電(dian)流(liu)(liu),低(di)壓電(dian)壓,低(di)壓電(dian)流(liu)(liu)。
設(she)置數(shu)據區:設(she)置試驗中需要的(de)參數(shu)數(shu)據輸(shu)出電(dian)壓(ya)為(wei)在自動(dong)方式(shi)下的(de)升壓(ya)目標耐壓(ya)值耐壓(ya)時(shi)間為(wei)耐壓(ya)過(guo)程的(de)時(shi)間長度電(dian)流(liu)(liu)上(shang)限(xian)為(wei)高壓(ya)電(dian)流(liu)(liu)峰值的(de)上(shang)限(xian),高壓(ya)電(dian)流(liu)(liu)超過(guo)電(dian)流(liu)(liu)上(shang)限(xian)將認為(wei)擊穿過(guo)流(liu)(liu)保(bao)護為(wei)低壓(ya)電(dian)流(liu)(liu)峰值的(de)上(shang)限(xian),低壓(ya)電(dian)流(liu)(liu)超過(guo)過(guo)流(liu)(liu)保(bao)護將認為(wei)擊穿
信息顯(xian)示(shi)區:顯(xian)示(shi)試(shi)驗過程(cheng)中的試(shi)驗狀態和提示(shi)信息。
試驗(yan)操作區:選(xuan)擇設(she)置、試驗(yan)、回零命令。
2、設置參數
在主界(jie)面上(shang),選中“設置”,然后按(an)確定后進入設置界(jie)面,如圖11:
按左←,右→時(shi)(shi)切換光標移動位置(zhi),按上↑、下↓時(shi)(shi)更(geng)改光標位置(zhi)數(shu)據的(de)值(zhi)。光標位置(zhi)和設(she)置(zhi)的(de)數(shu)值(zhi)全(quan)部可以自動循環(huan),前(qian)且(qie)在使用時(shi)(shi)有默認(ren)的(de)標準值(zhi)。如果所有的(de)參(can)數(shu)都(dou)設(she)置(zhi)完(wan)成,按取(qu)消退出設(she)置(zhi)回到主界面開始狀(zhuang)態。
3、手動試驗
零(ling)位檢查—當選中“試(shi)(shi)驗”后,按確(que)定就進入提示試(shi)(shi)驗狀態。如果調(diao)壓器不(bu)在零(ling)位,將提示“試(shi)(shi)驗前請(qing)先回零(ling)”,退出(chu)試(shi)(shi)驗并且(qie)切換(huan)到回零(ling)命令。
試(shi)驗(yan)過程(cheng)—回零確(que)認后,可以進(jin)行試(shi)驗(yan)。選中(zhong)“試(shi)驗(yan)”后按確(que)定(ding),接觸器合閘(zha),這時(shi)輸出電壓(ya)幾乎為0,如圖(tu)12:
按上↑,高壓(ya)電(dian)壓(ya)將(jiang)不(bu)斷(duan)升壓(ya),松(song)開就(jiu)停止升壓(ya),如(ru)果(guo)到上限就(jiu)提示滿量程;
按下↓,高(gao)壓(ya)電壓(ya)將不斷降壓(ya),松開就停(ting)止降壓(ya),如果到下限就提示(shi)已回零;
按計時(shi)←,計時(shi)開始工作,到耐壓時(shi)間計時(shi)結束完成試驗(yan);
按取(qu)(qu)消(xiao)→,取(qu)(qu)消(xiao)試(shi)驗過程;
在升壓(ya)(ya)過(guo)程中(zhong),如果(guo)(guo)(guo)(guo)高(gao)(gao)壓(ya)(ya)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)(liu)峰值(zhi)超(chao)過(guo)“電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)(liu)上(shang)限”值(zhi)或低(di)壓(ya)(ya)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)(liu)峰值(zhi)超(chao)過(guo)“過(guo)流(liu)(liu)(liu)保護”值(zhi)將認為(wei)被試(shi)(shi)品(pin)被擊穿,接(jie)觸器立(li)刻分(fen)(fen)閘(zha)并(bing)顯(xian)示(shi)試(shi)(shi)驗結果(guo)(guo)(guo)(guo),包括(kuo)峰值(zhi)電(dian)(dian)(dian)(dian)(dian)壓(ya)(ya)、峰值(zhi)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)(liu)、低(di)壓(ya)(ya)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)(liu)等(deng),調壓(ya)(ya)器開始回(hui)零(ling)(ling),回(hui)零(ling)(ling)完(wan)成(cheng)試(shi)(shi)驗結束(shu)(shu)。如果(guo)(guo)(guo)(guo)在耐壓(ya)(ya)過(guo)程中(zhong),高(gao)(gao)壓(ya)(ya)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)(liu)和低(di)壓(ya)(ya)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)(liu)峰值(zhi)沒有超(chao)設置上(shang)限值(zhi),認為(wei)被試(shi)(shi)品(pin)未(wei)擊穿,結果(guo)(guo)(guo)(guo)顯(xian)示(shi)區就顯(xian)示(shi)耐壓(ya)(ya)電(dian)(dian)(dian)(dian)(dian)壓(ya)(ya)、高(gao)(gao)壓(ya)(ya)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)(liu)、低(di)壓(ya)(ya)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)(liu)、絕緣電(dian)(dian)(dian)(dian)(dian)阻等(deng),調壓(ya)(ya)器開始回(hui)零(ling)(ling),回(hui)零(ling)(ling)完(wan)成(cheng)后接(jie)觸器分(fen)(fen)閘(zha)試(shi)(shi)驗結束(shu)(shu)。
4、自動試驗
自動試(shi)驗(yan)和手(shou)動試(shi)驗(yan)的試(shi)驗(yan)過程類似,首先(xian)也進(jin)行回零檢查,確認后進(jin)入如下界面,如圖13:
按(an)上(shang)方法切換到“開始”確定后進行(xing)試驗(yan),與手動試驗(yan)不同之處就(jiu)是升壓過程將自動升壓到“輸出電壓”值,然后進行(xing)計時。
升(sheng)壓(ya)(ya)過(guo)程(cheng)為(wei)逼近(jin)方式,首(shou)先升(sheng)到到接近(jin)目標值,然后(hou)再進行(xing)微(wei)調,保證高壓(ya)(ya)電壓(ya)(ya)值幾乎為(wei)輸出電壓(ya)(ya)值。
5、功能選(xuan)擇
按鍵盤上(shang)的“設置”就進入(ru)功(gong)能界面(mian),如圖14:
進入功能界面(mian)后,可以(yi)選擇“時鐘設置”、“注意事項”等界面(mian)。
時鐘設置:設置時鐘的時間,為打印(yin)報表提供時間依(yi)據。
注(zhu)意事項(xiang):為用戶提供一些操作規范(fan)和**注(zhu)意事項(xiang)。
6、打(da)印
按(an)鍵(jian)盤(pan)“打印”按(an)鍵(jian)可以打印試驗果,在此不贅(zhui)述。
七、產品維護
1、開箱驗收時,應檢查(cha)主控(kong)回路接線(xian)是否松動(dong),調壓(ya)器(qi)電刷(shua)是否接觸良好。
2.、長期不用時,使(shi)用前應用500V兆歐表測量絕緣電阻,其阻值不低于0.5MΩ。
3、電源電壓(ya)應符合控制箱(臺)說(shuo)明書上的輸(shu)入(ru)電壓(ya)值要求。
4、本控(kong)制箱(臺(tai))設有過(guo)電流(liu)保(bao)護,出廠已(yi)調整(zheng)為額定(ding)電流(liu)的50%。用于(yu)小負載時(shi),應根據(ju)被試品(pin)的額定(ding)容量電流(liu)重新設定(ding);
5、使用(yong)完畢后,應關好控制箱(xiang)(臺)門蓋,以保持(chi)內部清潔(jie)。
八、注意事項
1、按照您所(suo)進行的(de)(de)試驗接好工(gong)作(zuo)線路。試驗變(bian)壓(ya)器(qi)的(de)(de)外(wai)殼(ke)(ke)以及操(cao)作(zuo)系統的(de)(de)外(wai)殼(ke)(ke)必須可(ke)靠(kao)接地(di)。試驗變(bian)壓(ya)器(qi)的(de)(de)測量(liang)繞(rao)組的(de)(de)F端和外(wai)殼(ke)(ke)必須可(ke)靠(kao)接地(di)。
2、做串(chuan)級(ji)(ji)試驗(yan)時,**級(ji)(ji)、第三級(ji)(ji)試驗(yan)變(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)的低壓(ya)(ya)(ya)(ya)繞組(zu)(zu)成X端,測(ce)量(liang)繞組(zu)(zu)的F端以及(ji)高(gao)壓(ya)(ya)(ya)(ya)繞組(zu)(zu)的X端(高(gao)壓(ya)(ya)(ya)(ya)端)均接本級(ji)(ji)試驗(yan)變(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)具外殼。**級(ji)(ji)、第三級(ji)(ji)試驗(yan)變(bian)壓(ya)(ya)(ya)(ya)器(qi)(qi)的外殼必須通過絕緣(yuan)支架接地(di)。
接(jie)通電(dian)源前,控制箱(xiang)(臺)的調(diao)壓器必須調(diao)到零位后方(fang)可接(jie)通電(dian)源,合(he)閘,開始升壓。
3、從(cong)(cong)零開始勻速(su)(su)旋轉調(diao)壓器手輪升(sheng)壓。升(sheng)壓方式有:快(kuai)速(su)(su)升(sheng)壓法,即20s逐級(ji)升(sheng)壓法;慢速(su)(su)升(sheng)壓法,即60s逐級(ji)升(sheng)壓法;極慢速(su)(su)升(sheng)壓法供(gong)選用。電(dian)壓從(cong)(cong)零開始按一(yi)定(ding)(ding)的升(sheng)壓方式和速(su)(su)度(du)上升(sheng)到(dao)您所需的額定(ding)(ding)試(shi)(shi)(shi)驗(yan)電(dian)壓的75%后,再以每秒2%額定(ding)(ding)試(shi)(shi)(shi)驗(yan)電(dian)壓的速(su)(su)度(du)升(sheng)到(dao)您所需的試(shi)(shi)(shi)驗(yan)電(dian)壓,并密(mi)切(qie)注意測量(liang)(liang)儀表的及被(bei)試(shi)(shi)(shi)品的情況(kuang)。升(sheng)壓過(guo)(guo)程中或(huo)試(shi)(shi)(shi)驗(yan)過(guo)(guo)程中如發現測量(liang)(liang)儀表的指示及被(bei)試(shi)(shi)(shi)品情況(kuang)異(yi)常,應立(li)即降壓,切(qie)斷電(dian)源,查明(ming)情況(kuang)。
4、試驗(yan)完畢后(hou)(hou),應(ying)在等調壓器(qi)返回至零位,然后(hou)(hou)切(qie)斷電源。
5、本產品(pin)不得超(chao)過額定參(can)數使用。
6、使用(yong)本(ben)產品做高壓(ya)(ya)試(shi)驗時(shi),除熟悉本(ben)說明書外,還必須嚴(yan)格執行國(guo)家有關標準(zhun)和操作(zuo)規程(cheng)。可參照(zhao)GB311.1 – 97《高壓(ya)(ya)輸變設備的(de)絕(jue)緣配合,高壓(ya)(ya)試(shi)驗技術》;《電氣設備預防性試(shi)驗規程(cheng)》等(deng)。
7、控(kong)(kong)制(zhi)(zhi)箱(xiang)(臺(tai))應與試驗(yan)變壓器配套使(shi)(shi)用(yong),控(kong)(kong)制(zhi)(zhi)箱(xiang)(臺(tai))的使(shi)(shi)用(yong)方法,請詳細參閱(yue)控(kong)(kong)制(zhi)(zhi)器的使(shi)(shi)用(yong)說明(ming)書。